Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Measured value (PV) | 0 | I16 | 1 | |
| Current transformer 1 (CT1) input value monitor | 1 | U16 | 0.1 | A |
| Current transformer 2 (CT2) input value monitor | 2 | U16 | 0.1 | A |
| Set value (SV) monitor | 3 | I16 | 1 | |
| Remote setting (RS) input value monitor | 4 | I16 | 1 | |
| Burnout state monitor | 5 | U16 | 1 | |
| Burnout state monitor of feedback resistance input | 6 | U16 | 1 | |
| Event 1 state monitor | 7 | U16 | 1 | |
| Event 2 state monitor | 8 | U16 | 1 | |
| Event 3 state monitor | 9 | U16 | 1 | |
| Event 4 state monitor | 10 | U16 | 1 | |
| Heater break alarm 1 (HBA1) state monitor | 11 | U16 | 1 | |
| Heater break alarm 2 (HBA2) state monitor | 12 | U16 | 1 | |
| Manipulated output value (MV1) monitor [heat-side] | 13 | I16 | 0.1 | % |
| Manipulated output value (MV2) monitor [cool-side] | 14 | I16 | 0.1 | % |
| Error code | 15 | U16 | 1 | |
| Digital input (DI) state monitor | 16 | U16 | 1 | |
| Output state monitor | 17 | U16 | 1 | |
| Operation mode state monitor | 18 | U16 | 1 | |
| Memory area soak time monitor | 19 | U16 | 1 | |
| Integrated operating time monitor | 20 | U16 | 1 | hours |
| Holding peak value ambient temperature monitor | 21 | I16 | 0.1 | °C |
| Power feed forward input value monitor | 22 | U16 | 0.1 | % |
| Backup memory state monitor | 23 | U16 | 1 | |
| PID/AT transfer | 32 | U16 | 1 | |
| Auto/Manual transfer | 33 | U16 | 1 | |
| Remote/Local transfer | 34 | U16 | 1 | |
| RUN/STOP transfer | 35 | U16 | 1 | |
| Memory area transfer | 36 | U16 | 1 | |
| Interlock release | 37 | U16 | 1 | |
| Event 1 set value (EV1) | 38 | I16 | 1 | |
| Event 2 set value (EV2) | 39 | I16 | 1 | |
| Event 3 set value (EV3) | 40 | I16 | 1 | |
| Event 4 set value (EV4) | 41 | I16 | 1 | |
| Control loop break alarm (LBA) time | 42 | U16 | 1 | seconds |
| LBA deadband | 43 | U16 | 1 | |
| Set value (SV) | 44 | I16 | 1 | |
| Proportional band [heat-side] | 45 | U16 | 1 | |
| Integral time [heat-side] | 46 | U16 | 1 | seconds |
| Derivative time [heat-side] | 47 | U16 | 1 | seconds |
| Control response parameter | 48 | U16 | 1 | |
| Proportional band [cool-side] | 49 | U16 | 1 | |
| Integral time [cool-side] | 50 | U16 | 1 | seconds |
| Derivative time [cool-side] | 51 | U16 | 1 | seconds |
| Overlap/Deadband | 52 | I16 | 1 | |
| Manual reset | 53 | I16 | 1 | % |
| Setting change rate limiter (up) | 54 | U16 | 1 | |
| Setting change rate limiter (down) | 55 | U16 | 1 | |
| Area soak time | 56 | U16 | 1 | |
| Link area number | 57 | U16 | 1 | |
| Heater break alarm 1 (HBA1) set value | 58 | U16 | 0.1 | A |
| Heater break determination point 1 | 59 | U16 | 0.1 | % |
| Heater melting determination point 1 | 60 | U16 | 0.1 | % |
| Heater break alarm 2 (HBA2) set value | 61 | U16 | 0.1 | A |
| Heater break determination point 2 | 62 | U16 | 0.1 | % |
| Heater melting determination point 2 | 63 | U16 | 0.1 | % |
| PV bias | 64 | I16 | 1 | |
| PV digital filter | 65 | U16 | 0.1 | seconds |
| PV ratio | 66 | U16 | 0.001 | |
| PV low input cut-off | 67 | U16 | 0.01 | % |
| RS bias | 68 | I16 | 1 | |
| RS digital filter | 69 | U16 | 0.1 | seconds |
| RS ratio | 70 | U16 | 0.001 | |
| Proportional cycle time [heat-side] | 71 | U16 | 0.1 | seconds |
| Proportional cycle time [cool-side] | 72 | U16 | 0.1 | seconds |
| Manual manipulated output value | 73 | I16 | 1 | |
| Set lock level | 74 | U16 | 1 | |
| STOP display | 75 | U16 | 1 | |
| Bar graph display | 76 | U16 | 1 | |
| Bar graph display resolution | 77 | U16 | 1 | digit/dot |
| Direct key 1 | 78 | U16 | 1 | |
| Direct key 2 | 79 | U16 | 1 | |
| Direct key 3 | 80 | U16 | 1 | |
| Direct key type | 81 | U16 | 1 | |
| Input type | 82 | U16 | 1 | |
| Display unit | 83 | U16 | 1 | |
| Decimal point position | 84 | U16 | 1 | |
| Input scale high | 85 | I16 | 1 | |
| Input scale low | 86 | I16 | 1 | |
| Input error determination point (high) | 87 | I16 | 1 | |
| Input error determination point (low) | 88 | I16 | 1 | |
| Burnout direction | 89 | U16 | 1 | |
| Square root extraction | 90 | U16 | 1 | |
| Power supply frequency | 91 | U16 | 1 | Hz |
| Sampling cycle | 92 | U16 | 1 | ms |
| Remote setting input type | 93 | U16 | 1 | |
| Digital input (DI) assignment | 94 | U16 | 1 | |
| Output assignment | 95 | U16 | 1 | |
| Timer 1 | 96 | U16 | 0.1 | seconds |
| Timer 2 | 97 | U16 | 0.1 | seconds |
| Timer 3 | 98 | U16 | 0.1 | seconds |
| Timer 4 | 99 | U16 | 0.1 | seconds |
| Energized/De-energized | 100 | U16 | 1 | |
| Alarm (ALM) lamp lighting condition 1 | 101 | U16 | 1 | |
| Alarm (ALM) lamp lighting condition 2 | 102 | U16 | 1 | |
| Output status at STOP mode | 103 | U16 | 1 | |
| Transmission output type | 110 | U16 | 1 | |
| Transmission output scale high | 111 | I16 | 1 | |
| Transmission output scale low | 112 | I16 | 1 | |
| Event 1 type | 113 | U16 | 1 | |
| Event 1 hold action | 114 | U16 | 1 | |
| Event 1 interlock | 115 | U16 | 1 | |
| Event 1 differential gap | 116 | I16 | 1 | |
| Event 1 delay timer | 117 | U16 | 0.1 | seconds |
| Force ON of Event 1 action | 118 | U16 | 1 | |
| Event 2 type | 119 | U16 | 1 | |
| Event 2 hold action | 120 | U16 | 1 | |
| Event 2 interlock | 121 | U16 | 1 | |
| Event 2 differential gap | 122 | I16 | 1 | |
| Event 2 delay timer | 123 | U16 | 0.1 | seconds |
| Force ON of Event 2 action | 124 | U16 | 1 | |
| Event 3 type | 125 | U16 | 1 | |
| Event 3 hold action | 126 | U16 | 1 | |
| Event 3 interlock | 127 | U16 | 1 | |
| Event 3 differential gap | 128 | I16 | 1 | |
| Event 3 delay timer | 129 | U16 | 0.1 | seconds |
| Force ON of Event 3 action | 130 | U16 | 1 | |
| Event 4 type | 131 | U16 | 1 | |
| Event 4 hold action | 132 | U16 | 1 | |
| Event 4 interlock | 133 | U16 | 1 | |
| Event 4 differential gap | 134 | I16 | 1 | |
| Event 4 delay timer | 135 | U16 | 0.1 | seconds |
| Force ON of Event 4 action | 136 | U16 | 1 | |
| CT1 ratio | 137 | U16 | 1 | |
| CT1 assignment | 138 | U16 | 1 | |
| Heater break alarm 1 (HBA1) type | 139 | U16 | 1 | |
| Number of heater break alarm 1 (HBA1) delay times | 140 | U16 | 1 | times |
| CT2 ratio | 141 | U16 | 1 | |
| CT2 assignment | 142 | U16 | 1 | |
| Heater break alarm 2 (HBA2) type | 143 | U16 | 1 | |
| Number of heater break alarm 2 (HBA2) delay times | 144 | U16 | 1 | times |
| Hot/Cold start | 145 | U16 | 1 | |
| Start determination point | 146 | I16 | 1 | |
| External input type | 147 | U16 | 1 | |
| Master channel selection | 148 | U16 | 1 | |
| SV tracking | 149 | U16 | 1 | |
| MV transfer function | 150 | U16 | 1 | |
| Control action | 151 | U16 | 1 | |
| Integral/derivative time decimal point position | 152 | U16 | 1 | |
| Derivative action | 153 | U16 | 1 | |
| Undershoot suppression factor | 154 | U16 | 0.001 | |
| Derivative gain | 155 | U16 | 0.1 | |
| ON/OFF action differential gap (upper) | 156 | I16 | 1 | |
| ON/OFF action differential gap (lower) | 157 | I16 | 1 | |
| Action (high) at input error | 158 | U16 | 1 | |
| Action (low) at input error | 159 | U16 | 1 | |
| Manipulated output value at input error | 160 | I16 | 0.1 | % |
| Manipulated output value (MV1) at STOP mode | 161 | I16 | 0.1 | % |
| Manipulated output value (MV2) at STOP mode | 162 | I16 | 0.1 | % |
| Output change rate limiter (up) [MV1] | 163 | I16 | 0.1 | %/seconds |
| Output change rate limiter (down) [MV1] | 164 | I16 | 0.1 | %/seconds |
| Output limiter high (MV1) | 165 | I16 | 0.1 | % |
| Output limiter low (MV1) | 166 | I16 | 0.1 | % |
| Output change rate limiter (up) [MV2] | 167 | I16 | 0.1 | %/seconds |
| Output change rate limiter (down) [MV2] | 168 | I16 | 0.1 | %/seconds |
| Output limiter high (MV2) | 169 | I16 | 0.1 | % |
| Output limiter low (MV2) | 170 | I16 | 0.1 | % |
| Power feed forward selection | 171 | U16 | 1 | |
| Power feed forward gain | 172 | U16 | 0.01 | |
| AT bias | 173 | I16 | 1 | |
| AT cycles | 174 | U16 | 1 | |
| Output value with AT turned on | 175 | I16 | 0.1 | % |
| Output value with AT turned off | 176 | I16 | 0.1 | % |
| AT differential gap time | 177 | U16 | 0.1 | seconds |
| Proportional band adjusting factor [heat-side] | 178 | U16 | 0.01 | times |
| Integral time adjusting factor [heat-side] | 179 | U16 | 0.01 | times |
| Derivative time adjusting factor [heat-side] | 180 | U16 | 0.01 | times |
| Proportional band adjusting factor [cool-side] | 181 | U16 | 0.01 | times |
| Integral time adjusting factor [cool-side] | 182 | U16 | 0.01 | times |
| Derivative time adjusting factor [cool-side] | 183 | U16 | 0.01 | times |
| Proportional band limiter (high) [heat-side] | 184 | I16 | 1 | |
| Proportional band limiter (low) [heat-side] | 185 | I16 | 1 | |
| Integral time limiter (high) [heat-side] | 186 | I16 | 1 | seconds |
| Integral time limiter (low) [heat-side] | 187 | I16 | 1 | seconds |
| Derivative time limiter (high) [heat-side] | 188 | I16 | 1 | seconds |
| Derivative time limiter (low) [heat-side] | 189 | I16 | 1 | seconds |
| Proportional band limiter (high) [cool-side] | 190 | I16 | 1 | |
| Proportional band limiter (low) [cool-side] | 191 | I16 | 1 | |
| Integral time limiter (high) [cool-side] | 192 | I16 | 1 | seconds |
| Integral time limiter (low) [cool-side] | 193 | I16 | 1 | seconds |
| Derivative time limiter (high) [cool-side] | 194 | I16 | 1 | seconds |
| Derivative time limiter (low) [cool-side] | 195 | I16 | 1 | seconds |
| Open/Close output neutral zone | 196 | U16 | 0.1 | % |
| Open/Close output differential gap | 197 | U16 | 0.1 | % |
| Action at feedback resistance (FBR) input error | 198 | U16 | 1 | |
| Feedback adjustment | 199 | U16 | 1 | |
| Control motor time | 200 | U16 | 1 | seconds |
| Integrated output limiter | 201 | U16 | 0.1 | % |
| Valve action at STOP | 202 | U16 | 1 | |
| Startup tuning (ST) | 203 | U16 | 1 | |
| ST proportional band adjusting factor | 204 | U16 | 0.01 | times |
| ST integral time adjusting factor | 205 | U16 | 0.01 | times |
| ST derivative time adjusting factor | 206 | U16 | 0.01 | times |
| ST start condition | 207 | U16 | 1 | |
| Automatic temperature rise group | 208 | U16 | 1 | |
| Automatic temperature rise learning | 209 | U16 | 1 | |
| Automatic temperature rise dead time | 210 | U16 | 0.1 | seconds |
| Automatic temperature rise gradient data | 211 | U16 | 0.1 | |
| RUN/STOP group | 212 | U16 | 1 | |
| Setting change rate limiter unit time | 213 | U16 | 1 | seconds |
| Soak time unit | 214 | U16 | 1 | |
| Setting limiter high | 215 | I16 | 1 | |
| Setting limiter low | 216 | I16 | 1 | |
| PV transfer function | 217 | U16 | 1 | |
| PV flashing display at input error | 218 | U16 | 1 | |
| Overlap/Deadband reference point | 219 | U16 | 0.1 | |
| Action at saturated output | 220 | U16 | 1 | |
| Control area Local/External transfer | 224 | U16 | 1 | |
| Setting memory area number | 1280 | U16 | 1 | |
| Event 1 set value (EV1) | 1281 | I16 | 1 | |
| Event 2 set value (EV2) | 1282 | I16 | 1 | |
| Event 3 set value (EV3) | 1283 | I16 | 1 | |
| Event 4 set value (EV4) | 1284 | I16 | 1 | |
| Control loop break alarm (LBA) time | 1285 | U16 | 1 | seconds |
| LBA deadband | 1286 | U16 | 1 | |
| Set value (SV) | 1287 | I16 | 1 | |
| Proportional band [heat-side] | 1288 | I16 | 1 | |
| Integral time [heat-side] | 1289 | I16 | 1 | seconds |
| Derivative time [heat-side] | 1290 | I16 | 1 | seconds |
| Control response parameter | 1291 | U16 | 1 | |
| Proportional band [cool-side] | 1292 | I16 | 1 | |
| Integral time [cool-side] | 1293 | I16 | 1 | seconds |
| Derivative time [cool-side] | 1294 | I16 | 1 | seconds |
| Overlap/Deadband | 1295 | I16 | 1 | |
| Manual reset | 1296 | I16 | 0.1 | % |
| Setting change rate limiter (up) | 1297 | I16 | 1 | |
| Setting change rate limiter (down) | 1298 | I16 | 1 | |
| Area soak time | 1299 | U16 | 1 | |
| Link area number | 1300 | U16 | 1 | |
| Register address setting 1 | 4096 | U16 | 1 | |
| Register address setting 2 | 4097 | U16 | 1 | |
| Register address setting 3 | 4098 | U16 | 1 | |
| Register address setting 4 | 4099 | U16 | 1 | |
| Register address setting 5 | 4100 | U16 | 1 | |
| Register address setting 6 | 4101 | U16 | 1 | |
| Register address setting 7 | 4102 | U16 | 1 | |
| Register address setting 8 | 4103 | U16 | 1 | |
| Register address setting 9 | 4104 | U16 | 1 | |
| Register address setting 10 | 4105 | U16 | 1 | |
| Register address setting 11 | 4106 | U16 | 1 | |
| Register address setting 12 | 4107 | U16 | 1 | |
| Register address setting 13 | 4108 | U16 | 1 | |
| Register address setting 14 | 4109 | U16 | 1 | |
| Register address setting 15 | 4110 | U16 | 1 | |
| Register address setting 16 | 4111 | U16 | 1 | |
| Data specified by register address setting 1 | 5376 | U16 | 1 | |
| Data specified by register address setting 2 | 5377 | U16 | 1 | |
| Data specified by register address setting 3 | 5378 | U16 | 1 | |
| Data specified by register address setting 4 | 5379 | U16 | 1 | |
| Data specified by register address setting 5 | 5380 | U16 | 1 | |
| Data specified by register address setting 6 | 5381 | U16 | 1 | |
| Data specified by register address setting 7 | 5382 | U16 | 1 | |
| Data specified by register address setting 8 | 5383 | U16 | 1 | |
| Data specified by register address setting 9 | 5384 | U16 | 1 | |
| Data specified by register address setting 10 | 5385 | U16 | 1 | |
| Data specified by register address setting 11 | 5386 | U16 | 1 | |
| Data specified by register address setting 12 | 5387 | U16 | 1 | |
| Data specified by register address setting 13 | 5388 | U16 | 1 | |
| Data specified by register address setting 14 | 5389 | U16 | 1 | |
| Data specified by register address setting 15 | 5390 | U16 | 1 | |
| Data specified by register address setting 16 | 5391 | U16 | 1 |
⚠ An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or injury to personnel. — Starkest reads only; we never write a control register.
| terminals | FB100: 13 (SG), 14 (T/R A), 15 (T/R B). FB400/900: 25 (SG), 26 (T/R A), 27 (T/R B) |
| A/B polarity | V(A) - V(B) >= 2V -> 0 (SPACE), V(A) - V(B) <= -2V -> 1 (MARK) |
| termination | Externally terminal connected (RS-485) |
| connector | Screw terminals (M3 x 7 with 5.8 x 5.8 square washer) |
| isolation | Reinforced insulation between input signal wires and power supply/load wires |
| shield/ground | Shielded twisted pair wire recommended |
| max registers/read | 125 |
| inter-frame delay | 4 ms |
| broadcast | not supported |
| protocol notes | Commands should be sent at time intervals of 30 bits after the master receives the response message. |
| doc revision | IMR01W04-E6 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.