RKC FB100/FB400/FB900 controller (needs C5/C6 comms option)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Measured value (PV)0I161
Current transformer 1 (CT1) input value monitor1U160.1A
Current transformer 2 (CT2) input value monitor2U160.1A
Set value (SV) monitor3I161
Remote setting (RS) input value monitor4I161
Burnout state monitor5U161
Burnout state monitor of feedback resistance input6U161
Event 1 state monitor7U161
Event 2 state monitor8U161
Event 3 state monitor9U161
Event 4 state monitor10U161
Heater break alarm 1 (HBA1) state monitor11U161
Heater break alarm 2 (HBA2) state monitor12U161
Manipulated output value (MV1) monitor [heat-side]13I160.1%
Manipulated output value (MV2) monitor [cool-side]14I160.1%
Error code15U161
Digital input (DI) state monitor16U161
Output state monitor17U161
Operation mode state monitor18U161
Memory area soak time monitor19U161
Integrated operating time monitor20U161hours
Holding peak value ambient temperature monitor21I160.1°C
Power feed forward input value monitor22U160.1%
Backup memory state monitor23U161
PID/AT transfer32U161
Auto/Manual transfer33U161
Remote/Local transfer34U161
RUN/STOP transfer35U161
Memory area transfer36U161
Interlock release37U161
Event 1 set value (EV1)38I161
Event 2 set value (EV2)39I161
Event 3 set value (EV3)40I161
Event 4 set value (EV4)41I161
Control loop break alarm (LBA) time42U161seconds
LBA deadband43U161
Set value (SV)44I161
Proportional band [heat-side]45U161
Integral time [heat-side]46U161seconds
Derivative time [heat-side]47U161seconds
Control response parameter48U161
Proportional band [cool-side]49U161
Integral time [cool-side]50U161seconds
Derivative time [cool-side]51U161seconds
Overlap/Deadband52I161
Manual reset53I161%
Setting change rate limiter (up)54U161
Setting change rate limiter (down)55U161
Area soak time56U161
Link area number57U161
Heater break alarm 1 (HBA1) set value58U160.1A
Heater break determination point 159U160.1%
Heater melting determination point 160U160.1%
Heater break alarm 2 (HBA2) set value61U160.1A
Heater break determination point 262U160.1%
Heater melting determination point 263U160.1%
PV bias64I161
PV digital filter65U160.1seconds
PV ratio66U160.001
PV low input cut-off67U160.01%
RS bias68I161
RS digital filter69U160.1seconds
RS ratio70U160.001
Proportional cycle time [heat-side]71U160.1seconds
Proportional cycle time [cool-side]72U160.1seconds
Manual manipulated output value73I161
Set lock level74U161
STOP display75U161
Bar graph display76U161
Bar graph display resolution77U161digit/dot
Direct key 178U161
Direct key 279U161
Direct key 380U161
Direct key type81U161
Input type82U161
Display unit83U161
Decimal point position84U161
Input scale high85I161
Input scale low86I161
Input error determination point (high)87I161
Input error determination point (low)88I161
Burnout direction89U161
Square root extraction90U161
Power supply frequency91U161Hz
Sampling cycle92U161ms
Remote setting input type93U161
Digital input (DI) assignment94U161
Output assignment95U161
Timer 196U160.1seconds
Timer 297U160.1seconds
Timer 398U160.1seconds
Timer 499U160.1seconds
Energized/De-energized100U161
Alarm (ALM) lamp lighting condition 1101U161
Alarm (ALM) lamp lighting condition 2102U161
Output status at STOP mode103U161
Transmission output type110U161
Transmission output scale high111I161
Transmission output scale low112I161
Event 1 type113U161
Event 1 hold action114U161
Event 1 interlock115U161
Event 1 differential gap116I161
Event 1 delay timer117U160.1seconds
Force ON of Event 1 action118U161
Event 2 type119U161
Event 2 hold action120U161
Event 2 interlock121U161
Event 2 differential gap122I161
Event 2 delay timer123U160.1seconds
Force ON of Event 2 action124U161
Event 3 type125U161
Event 3 hold action126U161
Event 3 interlock127U161
Event 3 differential gap128I161
Event 3 delay timer129U160.1seconds
Force ON of Event 3 action130U161
Event 4 type131U161
Event 4 hold action132U161
Event 4 interlock133U161
Event 4 differential gap134I161
Event 4 delay timer135U160.1seconds
Force ON of Event 4 action136U161
CT1 ratio137U161
CT1 assignment138U161
Heater break alarm 1 (HBA1) type139U161
Number of heater break alarm 1 (HBA1) delay times140U161times
CT2 ratio141U161
CT2 assignment142U161
Heater break alarm 2 (HBA2) type143U161
Number of heater break alarm 2 (HBA2) delay times144U161times
Hot/Cold start145U161
Start determination point146I161
External input type147U161
Master channel selection148U161
SV tracking149U161
MV transfer function150U161
Control action151U161
Integral/derivative time decimal point position152U161
Derivative action153U161
Undershoot suppression factor154U160.001
Derivative gain155U160.1
ON/OFF action differential gap (upper)156I161
ON/OFF action differential gap (lower)157I161
Action (high) at input error158U161
Action (low) at input error159U161
Manipulated output value at input error160I160.1%
Manipulated output value (MV1) at STOP mode161I160.1%
Manipulated output value (MV2) at STOP mode162I160.1%
Output change rate limiter (up) [MV1]163I160.1%/seconds
Output change rate limiter (down) [MV1]164I160.1%/seconds
Output limiter high (MV1)165I160.1%
Output limiter low (MV1)166I160.1%
Output change rate limiter (up) [MV2]167I160.1%/seconds
Output change rate limiter (down) [MV2]168I160.1%/seconds
Output limiter high (MV2)169I160.1%
Output limiter low (MV2)170I160.1%
Power feed forward selection171U161
Power feed forward gain172U160.01
AT bias173I161
AT cycles174U161
Output value with AT turned on175I160.1%
Output value with AT turned off176I160.1%
AT differential gap time177U160.1seconds
Proportional band adjusting factor [heat-side]178U160.01times
Integral time adjusting factor [heat-side]179U160.01times
Derivative time adjusting factor [heat-side]180U160.01times
Proportional band adjusting factor [cool-side]181U160.01times
Integral time adjusting factor [cool-side]182U160.01times
Derivative time adjusting factor [cool-side]183U160.01times
Proportional band limiter (high) [heat-side]184I161
Proportional band limiter (low) [heat-side]185I161
Integral time limiter (high) [heat-side]186I161seconds
Integral time limiter (low) [heat-side]187I161seconds
Derivative time limiter (high) [heat-side]188I161seconds
Derivative time limiter (low) [heat-side]189I161seconds
Proportional band limiter (high) [cool-side]190I161
Proportional band limiter (low) [cool-side]191I161
Integral time limiter (high) [cool-side]192I161seconds
Integral time limiter (low) [cool-side]193I161seconds
Derivative time limiter (high) [cool-side]194I161seconds
Derivative time limiter (low) [cool-side]195I161seconds
Open/Close output neutral zone196U160.1%
Open/Close output differential gap197U160.1%
Action at feedback resistance (FBR) input error198U161
Feedback adjustment199U161
Control motor time200U161seconds
Integrated output limiter201U160.1%
Valve action at STOP202U161
Startup tuning (ST)203U161
ST proportional band adjusting factor204U160.01times
ST integral time adjusting factor205U160.01times
ST derivative time adjusting factor206U160.01times
ST start condition207U161
Automatic temperature rise group208U161
Automatic temperature rise learning209U161
Automatic temperature rise dead time210U160.1seconds
Automatic temperature rise gradient data211U160.1
RUN/STOP group212U161
Setting change rate limiter unit time213U161seconds
Soak time unit214U161
Setting limiter high215I161
Setting limiter low216I161
PV transfer function217U161
PV flashing display at input error218U161
Overlap/Deadband reference point219U160.1
Action at saturated output220U161
Control area Local/External transfer224U161
Setting memory area number1280U161
Event 1 set value (EV1)1281I161
Event 2 set value (EV2)1282I161
Event 3 set value (EV3)1283I161
Event 4 set value (EV4)1284I161
Control loop break alarm (LBA) time1285U161seconds
LBA deadband1286U161
Set value (SV)1287I161
Proportional band [heat-side]1288I161
Integral time [heat-side]1289I161seconds
Derivative time [heat-side]1290I161seconds
Control response parameter1291U161
Proportional band [cool-side]1292I161
Integral time [cool-side]1293I161seconds
Derivative time [cool-side]1294I161seconds
Overlap/Deadband1295I161
Manual reset1296I160.1%
Setting change rate limiter (up)1297I161
Setting change rate limiter (down)1298I161
Area soak time1299U161
Link area number1300U161
Register address setting 14096U161
Register address setting 24097U161
Register address setting 34098U161
Register address setting 44099U161
Register address setting 54100U161
Register address setting 64101U161
Register address setting 74102U161
Register address setting 84103U161
Register address setting 94104U161
Register address setting 104105U161
Register address setting 114106U161
Register address setting 124107U161
Register address setting 134108U161
Register address setting 144109U161
Register address setting 154110U161
Register address setting 164111U161
Data specified by register address setting 15376U161
Data specified by register address setting 25377U161
Data specified by register address setting 35378U161
Data specified by register address setting 45379U161
Data specified by register address setting 55380U161
Data specified by register address setting 65381U161
Data specified by register address setting 75382U161
Data specified by register address setting 85383U161
Data specified by register address setting 95384U161
Data specified by register address setting 105385U161
Data specified by register address setting 115386U161
Data specified by register address setting 125387U161
Data specified by register address setting 135388U161
Data specified by register address setting 145389U161
Data specified by register address setting 155390U161
Data specified by register address setting 165391U161

link settings as documented (unverified): RTU; default 19200 8N1; unit ID 0; FC 03,06,08,16; Modbus protocol identifies the host computer as master, the controller as slave.

⚠ An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or injury to personnel. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsFB100: 13 (SG), 14 (T/R A), 15 (T/R B). FB400/900: 25 (SG), 26 (T/R A), 27 (T/R B)
A/B polarityV(A) - V(B) >= 2V -> 0 (SPACE), V(A) - V(B) <= -2V -> 1 (MARK)
terminationExternally terminal connected (RS-485)
connectorScrew terminals (M3 x 7 with 5.8 x 5.8 square washer)
isolationReinforced insulation between input signal wires and power supply/load wires
shield/groundShielded twisted pair wire recommended
max registers/read125
inter-frame delay4 ms
broadcastnot supported
protocol notesCommands should be sent at time intervals of 30 bits after the master receives the response message.
doc revisionIMR01W04-E6
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms.baud_rates: [2400, 4800, 9600, 19200, 38400] — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: comms.default_baud: 19200 — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: comms.default_unit_id: 0 — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: comms.function_codes: [3, 6, 8, 16] — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: facts.doc_revision: IMR01W04-E6 — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: physical.connector: Screw terminals (M3 x 7 with 5.8 x 5.8 square washer) — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: physical.terminals: FB100: 13 (SG), 14 (T/R A), 15 (T/R B). FB400/900: 25 (SG), 26 (T/R A), 27 (T/R B) — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)
  • confirmed: physical.polarity: V(A) - V(B) >= 2V -> 0 (SPACE), V(A) - V(B) <= -2V -> 1 (MARK) — confirmed by RKC FB100/FB400/FB900 Communication Instruction Manual (IMR01W04-E6)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.