Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| system_status | 0 | U16 | 1 | |
| ch_1a_state_status | 1 | U16 | 1 | |
| ch_1a_reading | 19 | U16 | 1 | |
| ch_1b_state_status | 21 | U16 | 1 | |
| ch_1b_reading | 39 | U16 | 1 | |
| ch_1c_state_status | 41 | U16 | 1 | |
| ch_1c_reading | 59 | U16 | 1 | |
| ch_1d_state_status | 61 | U16 | 1 | |
| ch_1d_reading | 79 | U16 | 1 | |
| ch_2a_state_status | 81 | U16 | 1 | |
| ch_2a_reading | 99 | U16 | 1 | |
| ch_2b_state_status | 101 | U16 | 1 | |
| ch_2b_reading | 119 | U16 | 1 | |
| ch_2c_state_status | 121 | U16 | 1 | |
| ch_2c_reading | 139 | U16 | 1 | |
| ch_2d_state_status | 141 | U16 | 1 | |
| ch_2d_reading | 159 | U16 | 1 |
| terminals | RS-485 Modbus Terminal Strips (Master and Slave) are located in the lower left corner of the main PCB. |
| A/B polarity | A is TX/RX+, B is TX/RX-, C is Common |
| termination | Ground and termination jumpers on board. 120 Ohm, 3/4W termination resistor required for the last T3A/VOC Pro slave device. |
| connector | Terminal Strips and RJ45 LAN Connector |
| shield/ground | Field ground stud on the bottom right corner of the main PCB is typically used to connect the shield drain wire. |
| wiring notes | Supports a max cable length of 4,000 feet with recommended impedance of 120 ohms. |
| broadcast | supported |
| protocol notes | When the Beacon 3200 is in any operating menu other than normal operation, the channel registers simply hold their existing values. Once the Beacon 3200 returns to normal operation, the channel registers are updated each second. |
| identification notes | The warmup screen shows the instrument's firmware version. |
| power | 100V/115V/220V AC, 50/60Hz or 24V DC ± 10% |
| environment | Indoor or outdoor (Type 4X), 2000m max altitude, -40°C to 40°C ambient, 80% max relative humidity, Overvoltage Category II, Pollution Degree 2. Cannot be mounted in direct sunlight. |
| certifications | QPS, CSA |
| doc revision | 0 |
⚠ disputed: Ambient temperature range is -40°C to 40°C — disputed by RKI Instruments website and some manual revisions which state -40°C to 50°C (-40°F to 122°F)
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.