Rosemount 8732EM mag flow transmitter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
status_register_00U161
status_register_11U161
status_register_22U161
flow_rate200F32BE1ft/s
totalizer_a_value202F32BE1gal
totalizer_b_value204F32BE1gal
totalizer_c_value206F32BE1gal
electronics_temperature_value208F32BE1°F
line_noise_value210F32BE1mV
snr_5hz212F32BE1
snr_37hz214F32BE1
signal_power216F32BE1
empty_pipe_value218F32BE1
electrode_coating_value220F32BE1kΩ
electrode_resistance_value224F32BE1Ω
coil_resistance_value226F32BE1Ω
coil_inductance_value228F32BE1
coil_current236F32BE1mA

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; Modbus RS-485 output. Transmitters with a Modbus output provide an RS-485 signal to a Modbus host system; data rates can be configured from 1200 baud to 115.2 kilobaud.

bench facts as documented (unverified)
terminalsTerminal 1: Modbus (B), Terminal 2: Modbus (A). Terminal block screws: 6-32 (No. 6) suitable for up to 14 AWG wire.
A/B polarityModbus (A) and Modbus (B)
terminationTypically 120 ohms.
connectorTerminal block
isolationGalvanically isolated frequency signal (for pulse). Modbus output circuit is internally powered (Active): Outputs up to 3.3 VDC, 100 mA, 100 mW.
shield/groundSafety grounding screws: External stainless assembly, M5; internal 8-32 (No. 8).
wiring notesConduit entries available in 1/2 inch NPT or M20.
protocol notesMinimum response delay is used to synchronize Modbus communications with hosts that operate at a slower speed than the transmitter. This value can be configured as an integer from 0 to 250 ms. The default value is 10 ms.
model register120
serial register151
firmware register16
identification notesRegister 120 is Manufacturers Device Type Code, Register 121 is Manufacturers Id Code, Register 151 is Device Identification Number, Register 153 is Primary Variable Sensor Serial Number, Register 16 is Transmitter software revision.
powerAC power: 90–250 VAC, 0.45 A, 40 VA; Standard DC power: 12–42 VDC, 1.2 A, 15 W; Low power DC: 12–30 VDC, 0.25 A, 4 W
environmentIngress protection: IP66, IP69. NEMA 4X. Pollution Degree 2. Operating temperature: -58 to 140 °F (-50 to 60 °C) without LOI/Display, -4 to 140 °F (-20 to 60 °C) with LOI/Display. Humidity: 0-95% RH to 140 °F (60 °C).
accuracy0.25% Standard 0.15% High Accuracy Option
certificationsRosemount 8700M Approval Document - IECEx and ATEX, Class Division, North America Zone, NEPSI EN Zone 1 China
doc revision00809-0400-4444, Rev AC, August 2024
firmware applicability4.4 software or later
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Modbus RS-485 output with configurable baud rates from 1200 to 115200 (default 19200), default unit ID 1, and Even parity with 1 stop bit — confirmed by Rosemount 8732EM Transmitter with Modbus Protocol Reference Manual (00809-0400-4444)
  • confirmed: Terminal block connections with Terminal 1 as Modbus (B) and Terminal 2 as Modbus (A) — confirmed by Rosemount 8732EM Transmitter with Modbus Protocol Reference Manual (00809-0400-4444)
  • confirmed: Register map 0-based addresses (e.g., flow_rate @ 200, totalizer_a_value @ 202, electronics_temperature_value @ 208, empty_pipe_value @ 218) — confirmed by Rosemount 8732EM Transmitter with Modbus Protocol Reference Manual (00809-0400-4444) which lists these at 1-based registers 201, 203, 209, and 219 respectively

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.