Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| switching_frequency | 3102 | U16 | 0.1 | 0.1 kHz |
| maximum_output_frequency | 3103 | U16 | 0.1 | 0.1 Hz |
| high_speed | 3104 | U16 | 0.1 | 0.1 Hz |
| low_speed | 3105 | U16 | 0.1 | 0.1 Hz |
| acceleration | 9001 | U16 | 1 | s |
⚠ If Modbus fault management SLL is set to nO, communication control will be inhibited. For safety reasons, inhibition of communication fault should only be used for adjustment or special applications purpose. — Starkest reads only; we never write a control register.
| terminals | RJ45 connector |
| A/B polarity | Pin 4: D1 Modbus signal, Pin 5: D0 Modbus signal, Pin 8: Common Modbus signal |
| termination | One 120 Ohm 0.25 W resistor in series with a 1nF 10 V capacitor |
| connector | RJ45 |
| shield/ground | Connect the cable shielding to the ground of each device. |
| wiring notes | Type of trunk cable: Shielded cable with 1 twisted pair and at least a third conductor. Maximum length of bus: 1000 m at 19200 bps with Telemecanique TSX CSA••• cable. |
| max registers/read | 29 |
| response timeout | 10000 ms |
| broadcast | supported |
| protocol notes | Max write registers (FC16): 27 words max. End of frame detected on silence >= 3 characters. |
| identification notes | Function 43 (16#2B) returns Manufacturer name (Object 1), Device reference (Object 2), and Device version (Object 3). |
| FC 43 device ID | supported |
| power | VP (Pin 7) supply for RS232 / RS485 converter or a remote terminal |
| doc revision | BBV52816 04/2009 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.