Schneider Conext AGS generator start module

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Device Name0U161
FGA Number10U161
Unique ID Number20U161
Firmware Version30U161
Modbus Address40U161
Device Number41U161
System Instance42U161
Hardware Serial Number43U161
Configuration Status53U161
Configuration Refresh Counter54U32BE1
Device State64U161
Device Present65U161
Auto Generator State66U161
Auto Generator Action67U161
Generator On Reason68U161
Generator Off Reason69U161
Active Faults Flag70U161
Active Warnings Flag71U161
Fault Bitmap 072U161
Warning Bitmap 073U161
Configuration Errors74U32BE1
Operating Mode76U161
Generator Mode77U161
Reset78U161
Clear79U161
Generator Quiet Time Start80U161min
Generator Quiet Time Stop81U161min
Generator Quiet Time Enable / Disable82U161
Generator Auto Start On DC V83U161
Generator Auto Stop On DC V84U161
Generator Auto Start On Battery SOC85U161
Generator Auto Stop On Battery SOC86U161
Inverter Load Start/Stop Triggers87U161
Generator Auto Stop On AC I88U161
Generator Stop At Absorption Stage89U161
Generator Stop At Float Stage90U161
Maximum Automatic Cycles with No User Intervention91U161
Thermostat 195U161
Thermostat 296U161
Generator Type97U161
Generator Preheat Time99U161s
Generator Crank Start Delay100U161s
Generator Crank Time101U161s
Shutdown Bypass Time102U161s
Starter Cool Down Time103U161s
Generator Crank Retry Time104U161s
Generator Warmup Time105U161s
Maximum Generator Run Time106U160.016667hours
Generator Cool Down Time107U161s
Generator Spin Down Time108U161s
Generator Stop Timeout109U161s
Generator Start Tries110U161
Generator Exercise Period111U161days
Generator Exercise Duration112U161min
Generator Exercise Start Time113U161min
Generator Run Signal Hold Time114U160.01s
Relay 3 Function115U161
AC Current Level to Stop116U32BE0.001A
AC Current Level to Start118U32BE0.001A
Starting Battery Voltage (30 Seconds)120I32BE0.001V
Starting Battery Voltage (15 Minutes)122I32BE0.001V
Starting Battery Voltage (2 Hours)124I32BE0.001V
Starting Battery Voltage (24 Hours)126I32BE0.001V
Stop Voltage128I32BE0.001V
Refresh Configuration Data130U161
Generator Association131U161
AC Output Association132U161
AC Input Association133U161
DC Input Association134U161
State of Charge Level to Stop Generator135U161%
State of Charge Level to Start Generator136U161%

link settings as documented (unverified): Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. To confirm that a Modbus Register is correctly written, you should read it back and compare it with the expected value.

⚠ UNINTENDED OPERATION: The use of this product with Modbus communications requires expertise in the design, operation, and programming of the device. LOSS OF CONTROL: Do not assign the same address to two Modbus devices. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
protocol notesModbus does not provide an error response when data written to a Modbus Register is out of range or invalid.
model register0x0000
serial register0x002B
firmware register0x001E
doc revisionRevision A.4
firmware applicabilityConext AGS (Product ID 865-1060)

⚠ disputed: configuration_status @ 53 — disputed by Home Assistant Modbus YAML mapping (derived from Schneider spec 990-6274A) which places configuration_status at 0x0035 (53 decimal), but configuration_refresh_counter is at 0x0036 (54 decimal), device_state is at 0x0040 (64 decimal), device_present is at 0x0041 (65 decimal), auto_generator_state is at 0x0042 (66 decimal), auto_generator_action is at 0x0043 (67 decimal), generator_on_reason is at 0x0044 (68 decimal), generator_off_reason is at 0x0045 (69 decimal), active_faults_flag is at 0x0046 (70 decimal), active_warnings_flag is at 0x0047 (71 decimal), fault_bitmap_0 is at 0x0048 (72 decimal), warning_bitmap_0 is at 0x0049 (73 decimal), configuration_errors is at 0x004A (74 decimal), operating_mode is at 0x004C (76 decimal), generator_mode is at 0x004D (77 decimal), generator_quiet_time_start is at 0x0050 (80 decimal), generator_quiet_time_stop is at 0x0051 (81 decimal), generator_quiet_time_enable_disable is at 0x0052 (82 decimal), generator_auto_start_on_dc_v is at 0x0053 (83 decimal), generator_auto_stop_on_dc_v is at 0x0054 (84 decimal), generator_auto_start_on_battery_soc is at 0x0055 (85 decimal), generator_auto_stop_on_battery_soc is at 0x0056 (86 decimal), inverter_load_start_stop_triggers is at 0x0057 (87 decimal), generator_auto_stop_on_ac_i is at 0x0058 (88 decimal), generator_stop_at_absorption_stage is at 0x0059 (89 decimal), generator_stop_at_float_stage is at 0x005A (90 decimal), maximum_automatic_cycles_with_no_user_intervention is at 0x005B (91 decimal), thermostat_1 is at 0x005F (95 decimal), thermostat_2 is at 0x0060 (96 decimal), generator_type is at 0x0061 (97 decimal), generator_preheat_time is at 0x0063 (99 decimal), generator_crank_start_delay is at 0x0064 (100 decimal), generator_crank_time is at 0x0065 (101 decimal), shutdown_bypass_time is at 0x0066 (102 decimal), starter_cool_down_time is at 0x0067 (103 decimal), generator_crank_retry_time is at 0x0068 (104 decimal), generator_warmup_time is at 0x0069 (105 decimal), maximum_generator_run_time is at 0x006A (106 decimal), generator_cool_down_time is at 0x006B (107 decimal), generator_spin_down_time is at 0x006C (108 decimal). Note that the provided register map summary lists decimal addresses that match these hex values exactly (e.g., 0x0035 = 53, 0x0040 = 64, 0x0050 = 80, 0x0061 = 97), confirming the 0-based decimal addresses are correct.

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Conext AGS (Product ID 865-1060) — confirmed by Conext ComBox and Modbus Converter manuals listing Product No. 865-1060
  • confirmed: UNINTENDED OPERATION: The use of this product with Modbus communications requires expertise... — confirmed by Conext Configuration Tool Manual warning text
  • confirmed: Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. — confirmed by Conext Battery Monitor and AGS Modbus documentation guidelines

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.