device library

Schneider Conext Core XC central inverter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Product Model Designation1U161
Finished Goods Assembly Number10U161
Product Serial Number20U161
Product status109U161
Resistance1000F32BE1
Capacitance1002F32BE1
Injection status1008U161
Insulation alarm status1100U161
kWh Energy Produced2050U32BE0.1kWhr
Energy Today2052U32BE1kWhr
Operating Hours2078U32BE1Hours
Operational Mode State5888U161
Temperature Power Board5889I160.1C
Temperature Heatsink 15890I160.1C
Temperature Heatsink 25891I160.1C
Temperature Heatsink 35892I160.1C
Grid Current5893I160.1Arms
Apparent Power6129U160.1kVA
Reactive Power6132I160.1kVAr
Grid Voltage V126136I160.1Vrms
Grid Voltage V236137I160.1Vrms
Grid Voltage V316138I160.1Vrms
Grid Current Line 16139I160.1Arms
Grid Current Line 26140I160.1Arms
Grid Current Line 36141I160.1Arms
Active Power6142I160.1kW
PV Voltage6143I160.1VDC
PV Current6144I160.1ADC
PV Power6145I160.1kW
Grid Frequency6146I160.1Hz
Grid Frequency (Hi Res)6147I160.01Hz
DC Voltage6157I160.1VDC
Thermal Loading6158U160.1%
Phase A Frequency6168U160.1Hz
Phase B Frequency6169U160.1Hz
Phase C Frequency6170U160.1Hz
Phase A Real Power6171I160.1kW
Phase B Real Power6172I160.1kW
Phase C Real Power6173I160.1kW
Phase A Reactive Power6174I160.1kVAr
Phase B Reactive Power6175I160.1kVAr
Phase C Reactive Power6176I160.1kVAr
Phase A Apparent Power6177U160.1kVA
Phase B Apparent Power6178U160.1kVA
Phase C Apparent Power6179U160.1kVA
Event Code6182U161
System State6183U161
Alarm Code6184U161
Day Log Rate16393U161Min
First Daytime Hour16394U161Hours
Night Log Rate16395U161Min
First Nighttime Hour16396U161Hours
Grid Voltage 12 Gain Calibration16476U161000
Grid Voltage 23 Gain Calibration16477U161000
Grid Voltage 31 Gain Calibration16478U161000
Grid Voltage 12 Offset Calibration16479I160.1V
Grid Voltage 23 Offset Calibration16480I160.1V
Grid Voltage 31 Offset Calibration16481I160.1V
Gain kVAr Inductive16482U160.1V2/kVAr*Hz
Gain kVAr Capacitive16483U160.1V2/kVAr*Hz
Disconnect Profile16526U161
P-analog Filter Time16527U160.01s
Q-analog Filter Time16528U160.01s
I1 Gain Cal16529U160.001s
I2 Gain Cal16530U160.001s
I3 Gain Cal16531U160.001s
I1 Offset Cal16532U160.1s
I2 Offset Cal16533U160.1s
I3 Offset Cal16534U160.1s
Analog Error Suppressed16535U161
Modbus User P Readout16536U160.1kW
Modbus User Q Readout16537U160.1kVAr
Analog P Signal Readout16538U160.1mA
Analog Q Signal Readout16539U160.1mA
AI Disconn LF Threshold16563U160.01Hz
AI Disconn LF Delay16564U160.01s
AI LF Disconn Function16565U161
P(f), Slew Rate Type16571U161
Oscillography Item 1 (Vab)17990I160.1V
Oscillography Item 2 (Vbc)17991I160.1V
Oscillography Item 3 (Vca)17992I160.1V
Oscillography Item 4 (Ia)17993I160.1A
Oscillography Item 5 (Ib)17994I160.1A
Oscillography Item 6 (Ic)17995I160.1A
Oscillography Item 7 (Vpv)17996I160.1V
Oscillography Item 8 (Ipv)17997I160.1A
Oscillography Item 9 (Ignd)17998I160.1A
Oscillography Item 10 (Vdc)17999I160.1V
Oscillography Item 11 (App-Info1)18000U161
Oscillography Item 12 (App-Info2)18001U161
Oscillography Item 13 (App-Info3)18002U161
Oscillography Item 14 (App-Info4)18003U161
Oscillography Item 15; reserved18004U161
Oscillography Item 16; reserved18005U161
Oscillography Item 17; reserved18006U161
Number of Data Log Records18176U161
Number of Event Log Records18177U161
Number of Fault Log Records18178U161
Log Request Index18179U161
Log Response Index18180U161
Logger mode18181U161
Logger state18182U161
Timestamp High18208U161
Timestamp Low18209U161
Timestamp ms18210U161ms
Event 118211U161
Event 218212U161
Event 318213U161
Event 418214U161
Timestamp High18240U161
Timestamp Low18241U161
Timestamp ms18242U161ms
Fault18243U161
Timestamp High18449U161
Timestamp Low18450U161
kWh Energy High18451U160.1kWh
kWh Energy Low18452U160.1kWh
Grid AC voltage phase A to phase B, RMS18453I160.1V
Grid AC voltage phase B to phase C, RMS18454I160.1V
Grid AC voltage phase C to phase A, RMS18455I160.1V
Inverter AC Current Phase A, RMS18456I160.1A
Inverter AC Current Phase B, RMS18457I160.1A
Inverter AC Current Phase C, RMS18458I160.1A
Grid frequency18459I160.1Hz
Real power18460I161kW
Reactive power18461I161kVAr
DC bus voltage18462I160.1V
PV voltage18463I160.1V
PV current18464I160.1A
PV Power18465I160.1A
Ground Current18466I160.1A
Normalized thermal numbers18467U161%
App-Info118468U161
App-Info218469U161
App-Info318470U161
App-Info418471U161
DC Voltage Reference18472I160.1V
Power reference18473I161kW
Reactive power reference18474I161kVAr
Power board temperature by slave 118475I160.1°C
Heatsink temperature (average) by slave 218476I160.1°C
Highest priority event code18477U161
Power Point Shifting Flag18478U160.1V
Modbus Unit ID32771U161#
Baud Rate32784U161
Parameter Control Station57568U161
Commit Modbus Settings57569U161
Remote Disable/Enable61438U161
Clear Service Mode61439U161
Rated Input (PV) Current63489U161A
Maximum Input (PV) Voltage63490U161VDC
Max Tracking Volt63491U161V
Min Tracking Volt63492U161V
Max PV OC Voltage63493U161VDC
Max STC PV-SC Current63494U161ADC
Rated Apparent Power63495U160.1kVA
Rated Power at Unity PF63496I160.1kW
Min Input (PV) Voltage63497U161VDC
Nominal L-to-L Voltage63498U161Vrms
Nominal Line Current63499U161Arms
Rated Reactive Power63500I160.1kVAr
P(f) Control Function63990U161
Reconn HV Threshold63994U161%
User Phase Angle Ref63995I161Deg
PV noP Disconn Delay64002U161sec
Disconn HV Delay64005U161ms
Disconn LV Delay64006U161ms
Disconn HF Delay64007U161ms
Disconn LF Delay64008U160.01sec
Grid Reconnection Delay64009U161sec
PV Reconn Delay64010U161sec
Disconn HV Threshold64011U161%
Disconn LV Threshold64012U161%
User PV Voltage Ref64013U161V
PV OC Start Voltage64014U161V
Disconn HF Threshold64015U160.01Hz
Disconn LF Threshold64016U160.01Hz
MPPT Occurrence Factor64018U161
Perturb Voltage Step64019U160.1V
LP PV Voltage Reference64021U161V
LP Threshold64022U161%
PV noP Disconn Threshold64023U160.1%
User Active Power Limit64025I160.1kW
Active Anti-Islanding Function64026U161
User Reactive Power Reference64027I160.1kVAr
PV noP Disconn Delay Factor64028U161
User Apparent Power Limit64029U160.1kVA
User Phase Current Limit64030U161%
Utility Region64031U161
Language64032U161
Time (UTC)64033I32BE1sec
Voltage Support Function64036U161
P(f) Control, Reset Freq High64040U160.01Hz
P(f) Control, Corner Freq64041U160.1Hz
LP Transition Delay64047U161sec
Sweep Enable64048U161
Sweep Occurrence64049U161sec
Sweep Duration64050U160.1sec
MPPT Type64051U161
P(f) Control, Slope64052U161%/Hz
Power Ref. Ramp Time64053U161ms
System L-to-L Voltage64054U161Vrms
Disconn very HV Threshold64055U161%
Disconn very HV Delay64057U161ms
Disconn very LV Threshold64058U161%
Disconn very LV Delay64060U161ms
Disconn very LF Threshold64061U160.01Hz
Disconn very LF Delay64063U161ms
Disconn very HF Threshold64064U160.01Hz
Disconn very HF Delay64066U161ms
Reconn LF Threshold64067U160.01Hz
Reconn HF Threshold64068U160.01Hz
Reconn LV Threshold64069U161%
Reconn Power Ramp Time64070U161sec
Service Code64071U161
Power Reference Selection64072U161
Voltage Support Factor64073U160.1
Access Code64074U161
MPPT Offset Factor64075U161
MPPT Offset Maximum64076U161W
MPPT Offset Minimum64077U161W
MPPT Sampling Interval64078U161ms
MPPT Reset Factor64079U160.01
MPPT Sweep Trigger64080U161
Sweep Start Voltage64081U161V
Sweep Stop Voltage64082U161V
Sweep Range Voltage64083U161V
P(f) Control, Reset Time64088U161sec
V-Support Low Threshold64089U161%
V-Support High Threshold64090U161%
DC Cap Surge Accum64264U161Min
Voltage Envelope Threshold64272U161%
Voltage Envelope Delay64273U161Samples
DC Switch Open Count64305U161
AC Switch Open Count64306U161
GFD Reconn Delay64330U161min
GFD Max Daily Count64331U161count
Vac-Regulation64344U161
Q(V), V2s64345U161%
Q(V), V1s64346U161%
Q(V), V1i64347U161%
Q(V), V2i64348U161%
Phi(P), Pb64350U161%
Phi(P), PFc64351U160.01
Phi(P), Vlock in64352U161%
Phi(P), Vlock out64353U161%
Power Ramp Rate64354U160.1%/min
Min. Power Ramp Step64355U160.1kW
Reconnect Start Delay64356U161sec
Reconnect Power Ramp Type64357U161
Q(V), P Lock in64358U161%
Q(V), P Lock out64359U161%
P Lock in Delay64360U160.01sec
P Lock out Delay64361U160.01sec
OVSPD, Voltage Threshold64362U161%
OVSPD, Power Limit64363U161%
OVSPD, Ramp Down Rate64364U160.1%/min
OVSPD, Ramp Up Rate64365U160.1%/min
P(f)2, A Frequency64366U160.01Hz
P(f)2, B Frequency64367U160.01Hz
P(f)2, C Frequency64368U160.01Hz
P(f)2, D Frequency64369U160.01Hz
P(f)2, A Power64370U160.1%
P(f)2, B Power64371U160.1%
P(f)2, C Power64372U160.1%
P(f)2, D Power64373U160.1%
P(f)2, P Snapshot64374U161
P(f)2, F Lock in64375U160.01Hz
P(f)2, F Lock out64376U160.01Hz
P(f)2, F Lock in Delay64377U161ms
P(f)2, F Lock out Delay64378U161ms
Max DC Operating Voltage64404U161V
PV OC Recovery Delay64405U161min
P(f) Control, Reset Freq Low64406U160.01Hz
P(f) Control, Reset Delay64407U161sec
CQ Mode64413U161
Software Reset64414U161
Device Active Status64415U161
Countdown64419U161
Max Daily Online Cycling64466U161
Fan Speed64474U160.1V
Q(V) Qmax AVR64480I161%

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 247; FC 03,08,16,43; If the Vigilohm IM400 device is installed, do not configure the devices in the Conext Core XC Series for 57600 baud. The IM400 only supports up to 38400 baud.

⚠ LOSS OF CONTROL: The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
wiring notesRS-485 serial communication standard.
sentinel values0xFFFF for invalid registers
protocol notesWhen an invalid register is read from, the inverter responds with 0xFFFF in the data field but it does not return an error code. When written to, it responds with an Invalid Address exception.
model register0x1-0x9
serial register0x14-0x1D
firmware registerFC43
identification notesFC43 returns Vendor Name, Product Code, and Application Firmware Revision.
FC 43 device IDsupported
doc revisionRevision A
firmware applicabilityv1.07 and later, v1.09 and later, v3.00 and later, v3.01 and later, v3.02 and later, v5.00 and later
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms.baud_rates — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.default_baud — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.default_unit_id — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.framing — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.function_codes — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.notes — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.parity — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)
  • confirmed: comms.stop_bits — confirmed by Conext Core XC Using Modbus Application Note (AP-XC-095)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.