device library

Schneider Conext Grid-Tie inverter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Device Name0U161
FGA Number10U161
Unique ID Number20U161
Firmware Version30U161
Modbus Address40U161
Device Number41U161
System Instance42U161
Hardware Serial Number43U161
Configuration Status53U161
Configuration Refresh Counter54U32BE1
Device State64U161
Inverter Enabled65U161
Device Present66U161
Active Faults Flag67U161
Active Fault Count68U161
Fault Bitmap 069U161
Configuration Errors70U32BE1
PV Input Voltage72U32BE0.001V
PV Input Current74U32BE0.001A
PV Input Power76U32BE1W
Grid AC Voltage78U32BE0.001V
Grid AC Current80U32BE0.001A
Grid AC Frequency82U160.01Hz
Inverter Status83U161
Grid AC Power84U32BE1W
AC Power to Load86U32BE1W
AC Power to Grid88U32BE1W
Energy From PV This Hour96U32BE0.001kWh
PV Input Active This Hour98U32BE1s
Energy From PV Today100U32BE0.001kWh
PV Input Active Today102U32BE1s
Energy From PV This Week104U32BE0.001kWh
PV Input Active Week106U32BE1s
Energy From PV This Month108U32BE0.001kWh
PV Input Active Month110U32BE1s
Energy From PV This Year112U32BE0.001kWh
PV Input Active Year114U32BE1s
Energy From PV Lifetime116U32BE0.001kWh
PV Input Active Lifetime118U32BE1s
Grid Output Energy This Hour120U32BE0.001kWh
Grid Output Active This Hour122U32BE1s
Grid Output Energy Today124U32BE0.001kWh
Grid Output Active Today126U32BE1s
Grid Output Energy This Week128U32BE0.001kWh
Grid Output Active This Week130U32BE1s
Grid Output Energy This Month132U32BE0.001kWh
Grid Output Active This Month134U32BE1s
Grid Output Energy This Year136U32BE0.001kWh
Grid Output Active This Year138U32BE1s
Grid Output Energy Lifetime140U32BE0.001kWh
Grid Output Active Lifetime142U32BE1s
AC To Load Energy This Hour144U32BE0.001kWh
AC To Load Active This Hour146U32BE1s
AC To Load Energy Today148U32BE0.001kWh
AC To Load Active Today150U32BE1s
AC To Load Energy This Week152U32BE0.001kWh
AC To Load Active This Week154U32BE1s
AC To Load Energy This Month156U32BE0.001kWh
AC To Load Active This Month158U32BE1s
AC To Load Energy This Year160U32BE0.001kWh
AC To Load Active This Year162U32BE1s
AC To Load Energy Lifetime164U32BE0.001kWh
AC To Load Active Lifetime166U32BE1s
AC To Grid Energy This Hour168U32BE0.001kWh
AC To Grid Active This Hour170U32BE1s
AC To Grid Energy Today172U32BE0.001kWh
AC To Grid Active Today174U32BE1s
AC To Grid Energy This Week176U32BE0.001kWh
AC To Grid Active This Week178U32BE1s
AC To Grid Energy This Month180U32BE0.001kWh
AC To Grid Active This Month182U32BE1s
AC To Grid Energy This Year184U32BE0.001kWh
AC To Grid Active This Year186U32BE1s
AC To Grid Energy Lifetime188U32BE0.001kWh
AC To Grid Active Lifetime190U32BE1s
Reset192U161
Operating Mode193U161
Clear194U161
Identify Enable195U161
Refresh Configuration Data196U161
DC Input Association197U161
AC Output Association198U161

link settings as documented (unverified): Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. To confirm that a Modbus Register is correctly written, you should read it back and compare it with the expected value.

⚠ UNINTENDED OPERATION: The use of this product with Modbus communications requires expertise in the design, operation, and programming of the device. LOSS OF CONTROL: Do not assign the same address to two Modbus devices. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
protocol notesModbus does not provide an error response when data written to a Modbus Register is out of range or invalid.
model register0x0000
serial register0x002B
firmware register0x001E
identification notesUnique ID Number is located at register 0x0014
doc revisionRevision A.4

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.