Schneider Conext RL string inverter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Product Model Designation1U161
Serial Number20U161
Software Part Number for Processor A130U161
Software Part Number for Processor B150U161
Software Part Number for Processor C170U161
Energy since Commissioning2050U32BE0.1kWh
Energy Today2052U32BE0.1kWh
Energy Today (1 day earlier)2054U32BE0.1kWh
Energy Today (2 days earlier)2056U32BE0.1kWh
Energy Today (3 days earlier)2058U32BE0.1kWh
Energy Today (4 days earlier)2060U32BE0.1kWh
Energy Today (5 days earlier)2062U32BE0.1kWh
Energy Today (6 days earlier)2064U32BE0.1kWh
Operating Hours2078U32BE1h
Operational Mode State5888U161
Temperature 1, NTC on control board5889I160.1C
Temperature 2, Boost module 15890I160.1C
Temperature 3, Boost module 25891I160.1C
Temperature 4, Inverter module5892I160.1C
Apparent Power6129I160.1kVA
Reactive Power6132I160.1kVAr
Grid voltage6136I160.1Vrms
Phase A current6139I160.1Arms
PV1 voltage6143I160.1V
PV1 Current6144I160.1A
PV1 Power6145I160.1kW
Grid Frequency6146U160.1Hz
DC Voltage6157U160.1V
Real Power6171I160.1kW
Fault Code6184U161
PV2 Voltage6185I160.1V
PV2 Current6186I160.1A
PV2 Power6191I160.1kW
Power Ramp Up Recover Time63981U160.01s
Cos(φ) Lock-in Voltage63982U160.1V
Cos(φ) Lock-out Voltage63983U160.1V
KVAr(U) Lock-in Power%63984U161%
KVAr(U) Lock-out Power%63985U161%
User Phase Angle *63995I161deg
User Active Power Reference64025U160.1kW
User Reactive Power Reference64027I160.1kVAr
LVRT low voltage threshold (H) (Voltage1)64037U161%
LVRT fast low voltage threshold (L) (V-Drop)64038U161%
Reactive Power Mode Select64096U161
Fixed_Cos(φ)64097I160.01
Cos(φ)with Power Upper limit64098I160.01
Cos(φ)with Power Lower limit64099I160.01
Cos(φ)with % power Lower limit64100U161%
Cos(φ)with % power Upper limit64101U161%
Fixed kVAr %64102I161%
kVAr(U) as % of VA Upper limit64103I161%
kVAr(U) as % of VA Lower limit64104I161%
kVAr(U) Vmin64105U160.1V
kVAr(U) Vmax64106U160.1V
kVar(U) Uac_Lower limit64107U160.1V
kVar(U) Uac_Upper limit64108U160.1V
kVar(U) Hysteresis64109U160.1V
Response Time64110U160.01s
Mode registers64111U161
Actual /rated power64112U161
Start frequency64113U160.01Hz
Stop frequency64114U161
Recover frequency64115U160.01Hz
Gradient64116U160.1%
Recovery Time64117U161s
Active Power vs frequency Mode64118U161
K factor64119U160.1
Dead Band -Vh64120U161%
Dead band -VL64121U161%
Time164122U160.01s
Time264123U160.01s
Time364124U160.01s
Statism64125U160.1%
User Active Power management Mode64240U161
User Active Power Management Percentage64241U161%
Multifunction relay64245U161
Fault1/Error1 code64246U161
Fault2/Error2 code64247U161
Fault3/Erro3 code64248U161
Power production64249U161
Output power64250U160.1kW
Duration64251U161min
Minimum Duration64252U161min
Temperature 164253I160.1C
Temperature 264254I160.1C

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,08,16,43; Supports only the Modbus/RTU protocol. Slave address (Inverter ID) can be configured between 1 and 254.

⚠ HAZARD OF FIRE, ARC FLASH, OR ELECTRIC SHOCK FROM MULTIPLE SOURCES — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRJ-45
terminationDIP switch on communication interface board
connectorRJ-45
shield/groundPin 8 Modbus ground
wiring notesStandard Ethernet (straight-through) patch cable may be used. Ethernet cross-over cables must not be used.
broadcastsupported
protocol notesBroadcasts are valid only with Function 16 and are triggered by setting the slave address to zero (0).
model register0x0001
serial register0x0014
identification notesFunction code 43 (Read Device Identifier) is supported.
FC 43 device IDsupported
doc revisionRevision A
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Supports only the Modbus/RTU protocol. Slave address (Inverter ID) can be configured between 1 and 254. — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)
  • confirmed: RJ-45 connector pinout: Pin 4 DATA+, Pin 5 DATA-, Pin 8 Modbus ground — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)
  • confirmed: DIP switch on communication interface board for termination — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)
  • confirmed: Broadcasts are valid only with Function 16 and are triggered by setting the slave address to zero (0) — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)
  • confirmed: Product Model Designation at 0x0001 and Serial Number at 0x0014 — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)
  • confirmed: Register map addresses (e.g., energy_since_commissioning @ 2050 (0x0802), energy_today @ 2052 (0x0804), operational_mode_state @ 5888 (0x1700), pv1_current @ 6144 (0x1800)) — confirmed by Schneider Conext RL Modbus Application Note (976-2110-01-01 Revision A)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.