Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Product Model Designation | 1 | U16 | 1 | |
| Serial Number | 20 | U16 | 1 | |
| Software Part Number for Processor A | 130 | U16 | 1 | |
| Software Part Number for Processor B | 150 | U16 | 1 | |
| Software Part Number for Processor C | 170 | U16 | 1 | |
| Energy Since Commissioning | 2050 | U32BE | 0.1 | kWh |
| Energy Today | 2052 | U32BE | 0.1 | kWh |
| Energy Today (1 day earlier) | 2054 | U32BE | 0.1 | kWh |
| Energy Today (2 days earlier) | 2056 | U32BE | 0.1 | kWh |
| Energy Today (3 days earlier) | 2058 | U32BE | 0.1 | kWh |
| Energy Today (4 days earlier) | 2060 | U32BE | 0.1 | kWh |
| Energy Today (5 days earlier) | 2062 | U32BE | 0.1 | kWh |
| Energy Today (6 days earlier) | 2064 | U32BE | 0.1 | kWh |
| Operating Hours | 2078 | U32BE | 1 | h |
| Operational Mode State | 5888 | U16 | 1 | |
| Temperature 1, NTC on control board | 5889 | I16 | 0.1 | C |
| Temperature 2, Boost module 1 | 5890 | I16 | 0.1 | C |
| Temperature 3, Boost module 2 | 5891 | I16 | 0.1 | C |
| Temperature 4, Inverter module | 5892 | I16 | 0.1 | C |
| Apparent Power | 6129 | U16 | 0.1 | kVA |
| Reactive Power | 6132 | I16 | 0.1 | kVAr |
| Inverter Vab | 6136 | I16 | 0.1 | Vrms |
| Inverter Vbc | 6137 | I16 | 0.1 | Vrms |
| Inverter Vca | 6138 | I16 | 0.1 | Vrms |
| Phase A Current | 6139 | I16 | 0.1 | Arms |
| Phase B Current | 6140 | I16 | 0.1 | Arms |
| Phase C Current | 6141 | I16 | 0.1 | Arms |
| Real Power (Total) | 6142 | I16 | 0.1 | kW |
| PV1 Voltage | 6143 | I16 | 0.1 | V |
| PV1 Current | 6144 | I16 | 0.1 | A |
| PV1 Power | 6145 | I16 | 0.1 | kW |
| DC Voltage | 6157 | U16 | 0.1 | V |
| Phase A Frequency | 6168 | U16 | 0.1 | Hz |
| Phase B Frequency | 6169 | U16 | 0.1 | Hz |
| Phase C Frequency | 6170 | U16 | 0.1 | Hz |
| Phase A Real Power | 6171 | I16 | 0.1 | kW |
| Phase B Real Power | 6172 | I16 | 0.1 | kW |
| Phase C Real Power | 6173 | I16 | 0.1 | kW |
| Fault Code | 6184 | U16 | 1 | |
| PV2 Voltage | 6185 | I16 | 0.1 | V |
| PV2 Current | 6186 | I16 | 0.1 | A |
| PV2 Power | 6191 | I16 | 0.1 | kW |
| Number of Event Log Records | 18177 | U16 | 1 | |
| Log Request Index | 18179 | U16 | 1 | |
| Log Response Index | 18180 | U16 | 1 | |
| Logger-mode | 18181 | U16 | 1 | |
| Logger-state | 18182 | U16 | 1 | |
| Timestamp High | 18208 | U16 | 1 | |
| Timestamp Low | 18209 | U16 | 1 | |
| Timestamp ms | 18210 | U16 | 1 | |
| Event 1 | 18211 | U16 | 1 | |
| Event 2 | 18212 | U16 | 1 | |
| Event 3 | 18213 | U16 | 1 | |
| Event 4 | 18214 | U16 | 1 | |
| Clear Log | 61442 | U16 | 1 | |
| User Phase Angle | 63995 | I16 | 1 | degrees |
| User Active Power Limit | 64025 | U16 | 0.1 | kW |
| User Reactive Power Reference | 64027 | I16 | 0.1 | kVAr |
| Reactive Power Mode Select | 64096 | U16 | 1 | |
| Fixed Cos(phi) | 64097 | I16 | 1 | |
| Cos(phi) with Power Upper limit | 64098 | I16 | 1 | |
| Cos(phi) with Power Lower limit | 64099 | I16 | 1 | |
| Cos(phi) with % power Lower limit | 64100 | U16 | 1 | % |
| Cos(phi) with % power Upper limit | 64101 | U16 | 1 | % |
| Fixed kVAr % | 64102 | I16 | 1 | % |
| kVAr(U) as % Upper limit | 64103 | I16 | 1 | % |
| kVAr(U) as % Lower limit | 64104 | I16 | 1 | % |
| kVAr(U) Vmin | 64105 | U16 | 0.1 | V |
| kVAr(U) Vmax | 64106 | U16 | 0.1 | V |
| kVAr(U) UAC Lower limit | 64107 | U16 | 0.1 | V |
| kVAr(U) UAC Upper limit | 64108 | U16 | 0.1 | V |
| kVAr(U) Hysteresis | 64109 | U16 | 0.1 | V |
| kVAr(U) Response Time | 64110 | U16 | 0.01 | s |
| terminals | RJ-45 and 5-position terminal block |
| connector | RJ-45 and terminal block |
| shield/ground | Chassis ground on terminal block pin 3, Modbus ground on pin 4, Modbus ground on RJ-45 pin 8 |
| wiring notes | Provides an RID (Remote Inverter Disable) input and a dry contact. |
| broadcast | supported |
| protocol notes | Unmapped registers generate an 'Invalid Address' exception (02). Out of range writes return ExceptionCode = 02. |
| model register | 0x0001 |
| serial register | 0x0014 |
| firmware register | 0x0082 |
| identification notes | Function 43 reports Manufacturer Name, Product Identification, and Product Version Number. |
| FC 43 device ID | supported |
| doc revision | Revision A |
| firmware applicability | To access certain registers (0x182F, 0xF9FB, 0xFA19, 0xFA1B, 0xFA60 to 0xFA6E), communication software version must be higher than 1.22. |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.