device library

Schneider Electric ION9000 meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
voltage_a_b_v3020F32BE1V
current_a_a3000F32BE1
active_power_a_w3054F32BE1kW
active_energy_delivered_into_load_kwh2700F32BE1kWh
frequency_hz3110F32BE1Hz
digital_input_status_validity_base_unit2400U161
thd_v1_10m_mean40028F32BE1
year_year1837U161
com1_baud_rate54392U161
digital_output_status_validity_base_unit2402U161
setpoint_status_validity2420U161

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.