device library

Schneider Electric PM200 meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
scale_factor_v_voltage4105I161V
scale_factor_i_current4104I161
scale_factor_w_power4106I161kW
scale_factor_e_energy4107I161kWh
service_frequency4124I161Hz
thermal_demand_interval4116I161kW
error_bitmap4111I161
serial_number7001U161
modbus_address7004I161
power_block_demand_interval4117I161kW
power_block_demand_number_of_subintervals4118I161kW
signed_real_energy_consumption999F32BE1kWh

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.