device library

schneider-powerlogic-ion6200-meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
serial number0U32LE1
firmware revision2U161
oem identification3U161
meter options4U32LE1
# meter power ups6U161
# peak demand resets7U161
meter on-time8U32LE1
# flash erase cycles10U32LE1
device type12U161
demand interval down counter14U161
Vln a99U161V
Vln b100U161V
Vln c101U161V
Vln avg102U161V
Vll ab103U161V
Vll bc104U161V
Vll ca105U161V
Vll avg106U161V
I a107U161A
I b108U161A
I c109U161A
I avg110U161A
I demand111U161A
I peak demand112U161A
I4113U161A
Frequency114I160.01Hz
PF sign total115I160.01
PF sign a116I160.01
PF sign b117I160.01
PF sign c118I160.01
kW total119I161kW
kVAR total120I161kVAR
kVA total121I161kVA
kW a122I161kW
kW b123I161kW
kW c124I161kW
kVAR a125I161kVAR
kVAR b126I161kVAR
kVAR c127I161kVAR
kVA a128I161kVA
kVA b129I161kVA
kVA c130I161kVA
kW demand131I161kW
kW peak demand132I161kW
kVAR demand133I161kVAR
kVA demand134I161kVA
kVAR peak demand135I161kVAR
kVA peak demand136I161kVA
kWh del137U32LE1kWh
kWh rec139U32LE1kWh
kVARh del141U32LE1kVARh
kVARh rec143U32LE1kVARh
kVAh del+rec145U32LE1kVAh
V1 THD147U160.1%
V2 THD148U160.1%
V3 THD149U160.1%
I1 THD150U160.1%
I2 THD151U160.1%
I3 THD152U160.1%
I a demand153U161A
I b demand154U161A
I c demand155U161A
I a peak demand156U161A
I b peak demand157U161A
I c peak demand158U161A
kWh a del159U32LE1kWh
kWh b del161U32LE1kWh
kWh c del163U32LE1kWh
kWh a rec165U32LE1kWh
kWh b rec167U32LE1kWh
kWh c rec169U32LE1kWh
kVARh a del171U32LE1kVARh
kVARh b del173U32LE1kVARh
kVARh c del175U32LE1kVARh
kVARh a rec177U32LE1kVARh
kVARh b rec179U32LE1kVARh
kVARh c rec181U32LE1kVARh
kVAh a183U32LE1kVAh
kVAh b185U32LE1kVAh
kVAh c187U32LE1kVAh
Expansion, SnapOn 1, 25 regs499U161
Expansion, SnapOn 2, 25 regs699U161
kWh del1137U32BE1kWh
kWh rec1139U32BE1kWh
kVARh del1141U32BE1kVARh
kVARh rec1143U32BE1kVARh
kVAh del+rec1145U32BE1kVAh
kWh a del1159U32BE1kWh
kWh b del1161U32BE1kWh
kWh c del1163U32BE1kWh
kWh a rec1165U32BE1kWh
kWh b rec1167U32BE1kWh
kWh c rec1169U32BE1kWh
kVARh a del1171U32BE1kVARh
kVARh b del1173U32BE1kVARh
kVARh c del1175U32BE1kVARh
kVARh a rec1177U32BE1kVARh
kVARh b rec1179U32BE1kVARh
kVARh c rec1181U32BE1kVARh
kVAh a1183U32BE1kVAh
kVAh b1185U32BE1kVAh
kVAh c1187U32BE1kVAh
Energy Reset2000U161
Peak Power Demand Reset2001U161
Peak Current Demand Reset2002U161
Digital Output #12003U161
Digital Output #22004U161
Configuration via display password3999U161
Volts Mode4000U161
PT Primary4001U161
PT Secondary4002U161
CT Primary4003U161
CT Secondary4004U161
V1 Polarity4005U161
V2 Polarity4006U161
V3 Polarity4007U161
I1 Polarity4008U161
I2 Polarity4009U161
I3 Polarity4010U161
Programmable Voltage Scale (PVS)4011U161
Programmable Current Scale (PIS)4012U161
Programmable Neutral Current Scale (PnS)4013U161
Programmable Power Scale (PPS)4014U161
Demand Sub Interval4015U161minutes
Demand #Sub Intervals4016U161
Kt, Digital Output #14017U160.1
Kt, Digital Output #24018U160.1
Output Mode, Digital Output #14020U161
Output Mode, Digital Output #24021U161
Baud Rate4023U161
Protocol4024U161
Unit ID4025U161
RTS Delay4026U161milliseconds
Display Scroll Time4027U161seconds
Display Refresh Period4028U161seconds
PT Scale4029U161

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.