Schneider Sepam series 20 relay (needs ACE949/959 interface)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Binary time (year)2U161year
Binary time (months + days)3U161
Binary time (hours + minutes)4U161
Binary time (milliseconds)5U161ms
Manufacturer identification6U161
Equipment7U161
Marking + equipment type8U161
Modbus version9U161
Application version10U32BE1
Sepam check-word12U161
Synthesis zone13U161
Command14U161
Extension address15U161
Exchange word64U161
Exchange word112U161
Sepam check-word256U161
TS1-TS16257U161
TS17-TS32258U161
TS33-TS48259U161
TS49-TS64260U161
Logic inputs261U161
I1 phase current (gain x 1) (S2x/T2x/M2x)262U160.1A
I2 phase current (gain x 1) (S2x/T2x/M2x)263U160.1A
I3 phase current (gain x 1) (S2x/T2x/M2x)264U160.1A
I0 residual current (gain x 1) (S2x/T2x/M2x)265U160.1A
Im1 average phase current (x 1) (S2x/T2x/M2x)266U160.1A
Im2 average phase current (x 1) (S2x/T2x/M2x)267U160.1A
Im3 average phase current (x 1) (S2x/T2x/M2x)268U160.1A
I1 phase current (gain x 10) (S2x/T2x/M2x)269U161A
I2 phase current (gain x 10) (S2x/T2x/M2x)270U161A
I3 phase current (gain x 10) (S2x/T2x/M2x)271U161A
I0 residual current (gain x 10) (S2x/T2x/M2x)272U161A
IM1 average phase current (x10) (S2x/T2x/M2x)273U161A
IM2 average phase current (x10) (S2x/T2x/M2x)274U161A
IM3 average phase current (x10) (S2x/T2x/M2x)275U161A
IM1 peak demand phase current (S2x/T2x/M2x)276U161A
IM2 peak demand phase current (S2x/T2x/M2x)277U161A
IM3 peak demand phase current (S2x/T2x/M2x)278U161A
Itrip1 tripping current280U1610A
Itrip2 tripping current281U1610A
Itrip3 tripping current282U1610A
Itrip0 tripping current283U161A
Cumulative breaking current284U161(kA)2
Number of operations285U161
Operating time286U161ms
Charging time287U161sec
Running hours counter289U161hr
Thermal capacity used290U161%
Operating time before overload tripping291U161min
Waiting time after overload tripping292U161min
Unbalance ratio293U161% Ib
Starting time / overload294U160.1sec
Starting current overload295U161A
Start inhibit time delay296U161min
Number of starts allowed297U161
Temperature 1298I161°C
Temperature 2299I161°C
Temperature 3300I161°C
Temperature 4301I161°C
Temperature 5302I161°C
Temperature 6303I161°C
Temperature 7304I161°C
Temperature 8305I161°C
TC1-TC16496U161
STC1-STC16497U161
Control of analog output498I161
Time delay500U160.1sec

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; FC 01,02,03,04,05,06,07,08,11,15,16,43; Modbus RTU protocol supported via ACE949-2, ACE959, ACE969TP-2, or ACE969FO-2 interfaces.

bench facts as documented (unverified)
terminalsScrew-type terminal blocks (CCA620) or ring lug connectors (CCA622)
A/B polarityA/B/A'/B'
terminationJumper for RS 485 network line-end impedance matching with load resistor (Rc = 150 Ohm)
connectorRJ45 socket to connect the interface to the base unit with a CCA612 cord
isolationGalvanic isolation between RS 232 and RS 485 interfaces: 1000 Vrms, 50 Hz, 1 min
shield/groundConnection of the earthing terminal by tinned copper braid with cross-section >= 6 mm2 or cable >= 2.5 mm2
response timeout15 ms
inter-frame delay3 ms
broadcastsupported
protocol notesResponse time Tr is less than 15 ms, including a 3-character silence (~3 ms at 9600 bauds).
identification notesSupports Modbus function 43 sub-function 14 for reading device identification (VendorName, ProductCode, MajorMinorRevision, VendorURL, ProductName, ModelName, UserAppName).
FC 43 device IDsupported
power24 to 250 V DC or 110 to 240 V AC
environmentOperating temperature: -25°C to +70°C
certificationsCE, UL 508/UL 60950, cUL, AS/NZS 60950
field reports — community-sourced, unverified (checked 2026-06-11)
  • Integrators frequently encounter RS-485 polarity confusion when wiring the ACE949-2 interface to third-party Modbus masters, as the L+ and L- terminal designations may require swapping depending on the master's polarity convention. [source]
  • confirmed: comms.baud_rates [4800, 9600, 19200, 38400] and default_baud 19200 — confirmed by Schneider Electric Modbus communication manual
  • confirmed: facts.identification.fc43_device_id — confirmed by Sepam Series 20 User's Manual describing Modbus function 43 sub-function 14 support
  • confirmed: register map addresses (e.g., sepam_check_word @ 256, ts1_to_ts16 @ 257) — confirmed by Sepam Series 20 Modbus register documentation mapping 0x0100 (256) and 0x0101 (257)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.