device library

Sentera FCTH temp/RH sensor

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Device slave address0U161
Temperature reading0I160.1°C
Modbus baud rate1U161
Temperature output value1U160.1%
Modbus parity2U161
Temperature alert flag2U161
Device type3U161
Temperature range limit flag3U161
HW version4U161
Temperature sensor state4U161
FW version5U161
Modbus safety timeout7U161minutes
Modbus network resistor termination (NBT)8U161
Modbus registers reset9U161
Relative humidity level9U160.1% rH
Minimum temperature range10U160.1°C
Relative humidity output value10U160.1%
Maximum temperature range11U160.1°C
Relative humidity alert flag11U161
Minimum temperature alert12U160.1°C
Relative humidity range limit flag12U161
Maximum temperature alert13U160.1°C
Humidity sensor state13U161
Dew point level14I160.1°C
Minimum relative humidity range18U160.1% rH
Maximum relative humidity range19U160.1% rH
Minimum relative humidity alert20U160.1% rH
Maximum relative humidity alert21U160.1% rH
Active light level34U161lux
Standby light level35U161lux
Actual output value38U160.1%
Output control mode39U161
Output 1 mode40U161
Ambient light intensity40U161lux
Output 1 enable / disable41U161
Active / Standby41U161
Output 1 overwrite value42U160.1%
Ambient light sensor state42U161
Internal voltage source selection Output 143U161
Output 1 min. value44U160.1%
Output 1 max. value45U160.1%
Temperature sensor selection (ON / OFF)46U161
Relative humidity sensor selection (ON / OFF)56U161
LED indication78U161
LED brightness79U1610%

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; FC 03,04,06,16

bench facts as documented (unverified)
terminationSoftware-selectable Modbus network resistor termination (NBT)
model registerHR4
firmware registerHR6
doc revisionMBRM-FCTH-EN-000 - 27 / 04 / 2021
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms.baud_rates: [4800, 9600, 19200, 38400, 57600, 115200, 230400] — confirmed by MBRM-FCTH-EN-000 Holding Register 2 options [2.3]
  • confirmed: comms.default_baud: 19200 — confirmed by MBRM-FCTH-EN-000 Holding Register 2 default value of 2 (19,200 bps) [5.3]
  • confirmed: comms.default_unit_id: 1 — confirmed by MBRM-FCTH-EN-000 Holding Register 1 default value of 1 [5.3]
  • confirmed: comms.parity: E and stop_bits: 1 — confirmed by MBRM-FCTH-EN-000 Holding Register 3 default value of 1 (8E1) [2.3]
  • confirmed: comms.function_codes: [3, 4, 6, 16] — confirmed by MBRM-FCTH-EN-000 notes on reading/writing registers [3.1, 4.3]
  • confirmed: facts.doc_revision: 'MBRM-FCTH-EN-000 - 27 / 04 / 2021' — confirmed by document header [1.1]
  • confirmed: facts.identification: {'firmware_register': 'HR6', 'model_register': 'HR4'} — confirmed by MBRM-FCTH-EN-000 Holding Register 4 (Device type) and Holding Register 6 (Firmware version) [5.3, 6.1]
  • confirmed: facts.physical.termination: 'Software-selectable Modbus network resistor termination (NBT)' — confirmed by MBRM-FCTH-EN-000 Holding Register 9 [3.4]

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.