coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
sv11I161
at_auto_reset3U161
out1_proportional_band4I161
out2_proportional_band5I161
integral_time6I161
derivative_time7I161
out1_proportional_cycle8I161
out2_proportional_cycle9I161
a1_value11I161
a2_value12I161
hb_heater_burnout_alarm_value15I161
la_loop_break_alarm_time16I161
la_loop_break_alarm_span17I161
set_value_lock18U161
sv_high_limit19I161
sv_low_limit20I161
sensor_correction_value21I161
overlap_dead_band22I161
scaling_high_limit24I161
scaling_low_limit25I161
decimal_point_place26U161
pv_filter_time_constant27I161
out1_high_limit28I161
out1_low_limit29I161
out1_on_off_hysteresis30I161
out2_action_mode31U161
out2_high_limit32I161
out2_low_limit33I161
out2_on_off_hysteresis34I161
a1_type35U161
a2_type36U161
a1_hysteresis37I161
a2_hysteresis38I161
a1_action_delay_time41I161
a2_action_delay_time42I161
control_output_off55U161
auto_manual_control56U161
manual_control_mv57I161
a1_energized_de_energized64U161
a2_energized_de_energized65U161
input_type68U161
direct_reverse_action69U161
at_bias71I161
arw_anti_reset_windup72I161
Key Lock111U161
Key operation change flag clearing112U161
PV reading128I161
OUT1 MV reading129I161
OUT2 MV reading130I161
Status flag reading133U161

link settings as documented (unverified): RTU/ASCII; default 9600 8E1; unit ID 0; FC 03,06; Instrument number setting range is 0 to 95. Parity and stop bits are selectable.

⚠ Turn the power supply to the instrument off before wiring or checking it. Working on or touching the terminal with the power switched on may result in severe injury or death due to electric shock. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals13 YA(-), 14 YB(+), 15 SG
A/B polarityYA(-), YB(+)
terminationDo not connect the terminator to the communication line because each JCx-33A has built-in pull-up and pull-down resistors instead of a terminator.
shield/groundConnect only one end of the shielded wire to the FG terminal so that current cannot flow to the shielded wire.
wiring notesRecommended cable: OTSC-VB 2PX0.5SQ or equivalent (twisted pair cable).
max registers/read1
inter-frame delay1000 ms
broadcastsupported
protocol notesUp to 1,000,000 entries can be stored in memory. Frequent transmission is not recommended.
doc revisionNo.JC3CE11 2013.01

⚠ disputed: inter_frame_delay_ms: 1000 — disputed by Shinko JCS/JCM/JCR/JCD-33A (C5) manual No.JC3CE11, which specifies standard Modbus RTU timing (data interval of 3.5 characters or less)

field reports — community-sourced, unverified (checked 2026-06-11)
  • The controller only supports reading 1 register per Modbus request (the number of data is fixed to 0001H). Attempting to read multiple registers in a single request will fail or return invalid data. [source]
  • confirmed: comms defaults (baud 9600, parity E, stop bits 1, unit ID 0) — confirmed by Shinko JCS/JCM/JCR/JCD-33A (C5) manual No.JC3CE11
  • confirmed: physical terminals (13 YA(-), 14 YB(+), 15 SG) and polarity — confirmed by Shinko JCS/JCM/JCR/JCD-33A (C5) manual No.JC3CE11
  • confirmed: register map addresses (sv1 @ 1, out1_proportional_band @ 4, control_output_off @ 55) — confirmed by Shinko JCS/JCM/JCR/JCD-33A (C5) manual No.JC3CE11
  • confirmed: memory write limit of 1,000,000 entries — confirmed by Shinko JCS/JCM/JCR/JCD-33A (C5) manual No.JC3CE11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.