Siemens SENTRON PAC2200 meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
voltage_ul1_n1F32BE1V
current_l113F32BE1A
apparent_power_l119F32BE1kW
frequency55F32BE1Hz
device_diagnostics_and_device_status205U32BE1
active_tariff211U32BE1
voltage_ul2_n3F32BE1V
voltage_ul3_n5F32BE1V
voltage_ul1_l27F32BE1V
voltage_ul2_l39F32BE1V
voltage_ul3_l111F32BE1V