Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| hour_meter | 50512 | U32BE | 0.01 | 1/100 h |
| phase_to_phase_voltage_u12 | 50514 | U32BE | 0.01 | V/100 |
| phase_to_phase_voltage_u23 | 50516 | U32BE | 0.01 | V/100 |
| phase_to_phase_voltage_u31 | 50518 | U32BE | 0.01 | V/100 |
| simple_voltage_v1 | 50520 | U32BE | 0.01 | V/100 |
| simple_voltage_v2 | 50522 | U32BE | 0.01 | V/100 |
| simple_voltage_v3 | 50524 | U32BE | 0.01 | V/100 |
| frequency | 50526 | U32BE | 0.01 | Hz/100 |
| current_i1 | 50528 | U32BE | 0.001 | mA |
| current_i2 | 50530 | U32BE | 0.001 | mA |
| current_i3 | 50532 | U32BE | 0.001 | mA |
| neutral_current | 50534 | U32BE | 0.001 | mA |
| active_power | 50536 | U32BE | 0.01 | kW/100 (Signed) |
| reactive_power | 50538 | U32BE | 0.01 | kvar/100 (Signed) |
| apparent_power | 50540 | U32BE | 0.01 | kVA/100 |
| power_factor | 50542 | U32BE | 0.001 | 0.001 (Signed) |
| active_power_phase_1 | 50544 | U32BE | 0.01 | kW/100 (Signed) |
| active_power_phase_2 | 50546 | U32BE | 0.01 | kW/100 (Signed) |
| active_power_phase_3 | 50548 | U32BE | 0.01 | kW/100 (Signed) |
| reactive_power_phase_1 | 50550 | U32BE | 0.01 | kvar/100 (Signed) |
| reactive_power_phase_2 | 50552 | U32BE | 0.01 | kvar/100 (Signed) |
| reactive_power_phase_3 | 50554 | U32BE | 0.01 | kvar/100 (Signed) |
| apparent_power_phase_1 | 50556 | U32BE | 0.01 | kVA/100 |
| apparent_power_phase_2 | 50558 | U32BE | 0.01 | kVA/100 |
| apparent_power_phase_3 | 50560 | U32BE | 0.01 | kVA/100 |
| power_factor_phase_1 | 50562 | U32BE | 0.001 | 0.001 (Signed) |
| power_factor_phase_2 | 50564 | U32BE | 0.001 | 0.001 (Signed) |
| power_factor_phase_3 | 50566 | U32BE | 0.001 | 0.001 (Signed) |
| partial_positive_active_energy | 50780 | U32BE | 1 | kWh |
| partial_positive_reactive_energy | 50782 | U32BE | 1 | kvarh |
| module_temperature | 51457 | U16 | 1 | |
| thd_u12 | 51536 | U16 | 0.1 | |
| thd_u23 | 51537 | U16 | 0.1 | |
| thd_u31 | 51538 | U16 | 0.1 | |
| thd_v1 | 51539 | U16 | 0.1 | |
| thd_v2 | 51540 | U16 | 0.1 | |
| thd_v3 | 51541 | U16 | 0.1 | |
| thd_i1 | 51542 | U16 | 0.1 | |
| thd_i2 | 51543 | U16 | 0.1 | |
| thd_i3 | 51544 | U16 | 0.1 | |
| thd_in | 51545 | U16 | 0.1 |
| terminals | Diris A10 RS-485 Port: NC, +, - (terminals 13, 15, 17). Diris A20 RS-485 Optional Module: +, -, 0. |
| termination | Diris A10: 120 ohm resistor supplied as loose component to connect between + and - terminals at last slave. Diris A20: Set the 2 DIP switches on the last module on the bus to ON. |
| shield/ground | Only link the shield to the end on one end to guarantee the same potential of the shield. There is no other required earthing. |
| power | Diris A20: 110 / 240 VAC, 120 / 250 VDC. Diris A10: 110-277 VAC. |
| environment | 50 or 60 Hz distribution system. Max voltage across voltage-input terminals (V1, V2, V3, VN) 520VAC phase-to-phase or 300VAC phase-to-neutral. Max current of 6A on current-input terminals (I1, I2, I3). |
⚠ field check could not confirm this document matches this device — treat with caution.
⚠ disputed: default_baud: 38400 — disputed by LabVIEW Modbus RTU RS-485 Communication Setup guide which states the default baud rate is 9600 bps [3.2.4]
⚠ disputed: default_unit_id: 1 — disputed by Polar Monitoring guide which states the default communication address is 5
⚠ disputed: physical terminals, termination, and power specifications — disputed by official manuals because the stated specifications are explicitly for DIRIS A10 and DIRIS A20 models, whereas the DIRIS A40/A41 has different specifications (e.g., auxiliary power supply of 110 to 400 VAC / 120 to 350 VDC)
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.