Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
system_ph_n_voltage_v36866U32BE1V
frequency_mhz36870U32BE1Hz
status58272U161
system_thd_v37149U161
modbus_table_version50005U161
system_ph_ph_voltage_v36868U32BE1V
ph_n_voltage_v1_v36872U32BE1V
ph_n_voltage_v2_v36874U32BE1V
ph_n_voltage_v3_v36876U32BE1V
ph_n_voltage_vn_v36878U32BE1V
ph_ph_voltage_u12_v36880U32BE1V

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.