Sontex Supercal 531 heat meter (needs Modbus EIA-485 module)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
energy_unit100U161
energy_totalizer_heating102F32BE1Wh|kWh|MWh|MJ|GJ|BTU
energy_totalizer_tariff_1104F32BE1Wh|kWh|MWh|MJ|GJ|BTU
energy_totalizer_tariff_2106F32BE1Wh|kWh|MWh|MJ|GJ|BTU
volume_unit300U161
volume302F32BE1m3|USGallon
volume_tariff_1304F32BE1m3|USGallon
volume_tariff_2306F32BE1m3|USGallon
power_unit700U161
power702F32BE1W|kW
flow_unit710U161
flow712F32BE1m3/h
temperature_unit720U161
high_temperature722F32BE1°C
low_temperature724F32BE1°C
delta_temperature_unit730U161
delta_temperature732F32BE1K

link settings as documented (unverified): RTU/ASCII; default 19200 8E1; unit ID 1; The device address, the serial transmission mode (RTU or ASCII) and the parity can be changed over the optical interface by the Prog531 and Prog449 configuration software or via Modbus command. If no parity is set, the number of stop bits is set to 2 automatically.

⚠ Avoid electrostatic discharges during installation or handling. Modbus devices powered from a common AC source could be damaged if a mix of half-wave and full-wave rectified devices exist. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals2x3 screw terminals (D1/D0/Common terminals for the RS-485 connection) and +12 VDC / 0 VDC
A/B polarityD0, D1
terminationThrough DIP switch S1 (120 Ω + 1nF) or with an external resistor
connectorPlug-screw terminal
isolationMains switching power supply module Model 0531A030 is completely electrically isolated. Model 0690A013 is built with a full-wave rectifier.
shield/groundConnect the shield to earth at only one point.
wiring notesDimensions 66 x 30 mm. Mounted in one of the two module slots on the mother board of the Supercal integrator.
broadcastsupported
protocol notesAfter programming new parameters, it's obligatory to open/separate the upper part with the lower of the integrator to perform a hardware reset.
model register30001
serial register40023
firmware register30003
identification notesFabrication number MET at 30001-30002, Custom ID (OEM serial number) at 40023-40024, Firmware version at 30003.
powerInternal power supply: Mains switching power supply of 531 / 449 integrator (0531A030, 230 VAC or 0690A013, 24 VAC). External power supply: 12 VDC / 150 mA.
environmentOperating temperature: 5° to 55°C. Storage temperature: -10° to 55°C (dry environment).
accuracyHigh accuracy e.g. energy, volume, power, flow, and temperature data.
doc revision0531P217 Installation Modbus Module EN 29-08-2018
firmware applicabilitySupercal 531 / Superstatic 449 firmware release FW 3.7 or higher (FW ≥ V3.7)

⚠ disputed: energy_unit @ 100 — disputed by Sontex register map which places Energy Unit at 30101 (or 0-based 100 within the 30000 block, but physically mapped as 30101)

⚠ disputed: energy_totalizer_heating @ 102 — disputed by Sontex register map which places Energy totalizer heating at 30103-30104

⚠ disputed: energy_totalizer_tariff_1 @ 104 — disputed by Sontex register map which places Energy totalizer Tariff 1 at 30105-30106

⚠ disputed: energy_totalizer_tariff_2 @ 106 — disputed by Sontex register map which places Energy totalizer Tariff 2 at 30107-30108

⚠ disputed: volume_unit @ 300 — disputed by Sontex register map which places Volume Unit at 30301

⚠ disputed: volume @ 302 — disputed by Sontex register map which places Volume at 30303-30304

⚠ disputed: volume_tariff_1 @ 304 — disputed by Sontex register map which places Volume Tariff 1 at 30305-30306

⚠ disputed: volume_tariff_2 @ 306 — disputed by Sontex register map which places Volume Tariff 2 at 30307-30308

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults — confirmed by Sontex Modbus EIA-485 module manual (0531P217) which states default unit ID is 1, default transmission mode is RTU, and if no parity is set, stop bits automatically default to 2
  • confirmed: physical terminals and isolation — confirmed by Sontex installation instructions detailing 2x3 screw terminals (D1/D0/Common), DIP switch S1 for termination (120 Ω + 1nF), and mains switching power supply modules 0531A030 (isolated) and 0690A013 (full-wave rectifier)
  • confirmed: firmware applicability — confirmed by Sontex manual stating compatibility with Supercal 531 / Superstatic 449 firmware release FW 3.7 or higher
  • confirmed: identification registers — confirmed by Sontex register map showing Fabrication number MET at 30001-30002, Firmware version at 30003, and Custom ID (OEM serial number) at 40023-40024

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.