SRNE MPPT inverter-charger

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
System information (max voltage / rated charging current)10U161
System information (rated discharging current / product type)11U161
Product model12U161
Software version20U32BE1
Hardware version22U32BE1
Product serial number24U32BE1
Device address26U161
Battery capacity SOC256U161%
Battery voltage257U160.1V
Charging current258U160.01A
Controller and Battery temperature259U161℃
Load dc voltage260U160.1V
Load dc current261U160.01A
Load dc power262U161W
Solar panel voltage263U160.1V
Solar panel current264U160.01A
Charging power265U161W
Load On/Off command266U161
Battery's min. voltage of the current day267U160.1V
Battery's max. voltage of the current day268U160.1V
Max. charging current of the current day269U160.01A
Max. discharging current of the current day270U160.01A
Max. charging power of the current day271U161W
Max. discharging power of the current day272U161W
Charging amp-hrs of the current day273U161AH
Discharging amp-hrs of the current day274U161AH
Power generation of the current day275U161W
Power consumption of the day276U161W
Total number of operating days277U161days
Total number of battery over-discharges278U161
Total number of battery full-charges279U161
Total charging amp-hrs of the battery280U32BE1AH
Total discharging amp-hrs of the battery282U32BE1AH
Cumulative power generation284U32BE1W
Cumulative power consumption286U32BE1W
Load status and Charging state288U161
Controller failure, alarm information 16 high bits289U161
Controller failure, alarm information 16 low bits290U161
Set charging current limit57345U160.01A
Nominal battery capacity57346U161AH
System voltage setting and recognized voltage57347U161
Battery type57348U161
Over-voltage threshold57349U160.1V
Charging voltage limit57350U160.1V
Equalizing charging voltage57351U160.1V
Boost charging voltage/overcharge voltage57352U160.1V
Floating charging voltage/overcharge recovery voltage57353U160.1V
Boost charging recovery voltage57354U160.1V
Over-discharge recovery voltage57355U160.1V
Under-voltage warning level57356U160.1V
Over-discharge voltage57357U160.1V
Discharging limit voltage57358U160.1V
end-of-charge SOC and end-of-discharge SOC57359U161
Over-discharge time delay57360U161S
Equalizing charging time57361U161Min
Boost charging time57362U161Min
Equalizing charging interval57363U161day
Temperature compensation factor57364U161mV/℃/2V
Load working modes57373U161
Light control delay57374U161Min
Light control voltage57375U161V
Special power control57377U161
Historical data record (FLASH)61440U161

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,06,16,120,121; Address FFH can be used to bypass the local device address with data return for stand-alone devices. Address 00H is a broadcast address.

bench facts as documented (unverified)
terminalsRJ12 (6-pin) for RS232, 4-pin terminal block for RS485-1, 8-pin terminal block for RS485-2, 4-pin terminal block for TTL
A/B polarityRS485-1: D- (Yellow), D+ (Red); RS485-2: D+ (pin 2), D- (pin 3)
connectorRJ12, Terminal block
shield/groundPower supply grounding/signal grounding
inter-frame delay10 ms
broadcastsupported
protocol notesPDU address segments (0000 to 0009)/(000A to 001A)/(0100 to 0122)/(E001 to E02D)/(F000 to F3FF) are not allowed to cross access and modification in the same command.
powerRS232: pins 5,6 positive, pins 3,4 ground. RS485-1: 12V pin 1, GND pin 2. RS485-2: Power positive pin 1, ground pin 4. TTL: GND pin 1, 12.8V pin 4.
doc revisionV3.9 (2020-4-21)
field reports — community-sourced, unverified (checked 2026-06-11)
  • Users report that changing settings (writing to registers) on SRNE hybrid inverters via Modbus requires writing a password (default '111111') to register E203 (or E202) first, which must be done once after every reboot of the inverter. Otherwise, write commands fail or are ignored. [source]
  • Modbus communication can be slow and unstable, with register writes taking up to 10 minutes or failing if multiple write registers are spammed without a delay (adding a delay between actions is recommended). [source]
  • confirmed: comms defaults (9600 baud, RTU, N, 8, 1) — confirmed by SRNE Inverter Modbus Protocol Guide and community integrations
  • confirmed: PDU address segments (0000 to 0009)/(000A to 001A)/(0100 to 0122)/(E001 to E02D)/(F000 to F3FF) are not allowed to cross access — confirmed by SRNE Modbus Protocol V3.8/V3.9 documentation
  • confirmed: Address FFH can be used to bypass local device address — confirmed by SRNE Modbus Protocol V3.8/V3.9 documentation
  • confirmed: Register battery_soc @ 256 (0x0100) and battery_voltage @ 257 (0x0101) — confirmed by SRNE Modbus Protocol V3.8/V3.9 documentation and community ESPHome integrations

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.