device library

sungrow-sh-series-hybrid-inverter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Protocol No4949U32LE1
Protocol ver4951U32LE1
Certification version number of ARM software4953U161
Certification version number of DSP software4968U161
SN4989U161
Device type code4999U161
Nominal output power5000U160.1kW
Output type5001U161
Daily Output Energy5002U160.1kWh
Total Output Energy5003U32LE0.1kWh
System clock: Second5004U161
Inside Temperature5007I160.1°C
MPPT 1 Voltage5010U160.1V
MPPT 1 Current5011U160.1A
MPPT 2 Voltage5012U160.1V
MPPT 2 Current5013U160.1A
MPPT 3 Voltage5014U160.1V
MPPT 3 Current5015U160.1A
Total DC power5016U32LE1W
A-B line voltage/phase A voltage5018U160.1V
B-C line voltage/phase B voltage5019U160.1V
C-A line voltage/phase voltage5020U160.1V
Reactive power5032I32LE1var
Power factor5034I160.001
Grid frequency5035U160.1Hz
Battery power - Wide range5213I32LE1W
Grid Frequency - High precision5241U160.01Hz
Meter Phase A Active Power5602I32LE1W
Meter Phase B Active Power5604I32LE1W
Meter Phase C Active Power5606I32LE1W
Export limit min5621U1610W
Export limit max5622U1610W
BDC rated power5627U16100W
Battery Current5630I160.1A
Max. Charging Current (BMS)5634U161A
Max. Discharging Current (BMS)5635U161A
Battery Capacity- High precision5638U160.01kWh
Phase A Backup Current5719I160.1A
Phase B Backup Current5720I160.1A
Phase C Backup Current5721I160.1A
Phase A Backup Power5722I161W
Phase B Backup Power5723I161W
Phase C Backup Power5724I161W
Total Backup Power5725U32LE1W
Phase A Backup Voltage5730U160.1V
Phase B Backup Voltage5731U160.1V
Phase C Backup Voltage5732U160.1V
Backup Frequency5733U160.01Hz
PV Power of today6099U161W
Daily PV energy yields6195U160.1kWh
Monthly PV energy yields6226U160.1kWh
Yearly PV energy yields6249U32LE0.1kWh
Direct power consumption of today from PV6289U161W
Daily direct energy consumption from PV6385U160.1kWh
Monthly direct energy consumption from PV6416U160.1kWh
Yearly direct energy consumption from PV6428U32LE0.1kWh
Export power from PV of today6468U161W
Daily export energy from PV6564U160.1kWh
Monthly export energy from PV6595U160.1kWh
Yearly export energy from PV6607U32LE0.1kWh
Battery charge power of today6647U161W
Daily battery charge energy from PV6743U160.1kWh
Monthly battery charge energy from PV6774U160.1kWh
Yearly battery charge energy from PV6786U32LE0.1kWh
Running state12999U161
Power Flow Status13000U161
Daily PV Generation13001U160.1kWh
Total PV Generation13002U32LE0.1kWh
Load 1 timing period 1: Start minute13003U161min
Daily export power from PV13004U160.1kWh
Total export energy from PV13005U32LE0.1kWh
Load 1 timing period 2: Start hour13006U161h
Load power13007I32LE1W
Load 1 timing period 2: End hour13008U161h
Export power13009I32LE1W
Load 1 ON/OFF mode13010U161
Daily battery charge energy from PV13011U160.1kWh
Total battery charge energy from PV13012U32LE0.1kWh
Load 1 power optimized mode: End hour13013U161h
Load 1 power optimized mode: End minute13014U161min
Optimized power of load 113015U161W
Daily direct energy consumption13016U160.1kWh
Total direct energy consumption13017U32LE0.1kWh
Battery voltage13019U160.1V
Battery current13020U160.1A
Battery power13021U161W
Battery level13022U160.1%
Battery state of healthy13023U160.1%
Battery temperature13024I160.1°C
Daily battery discharge energy13025U160.1kWh
Total battery discharge energy13026U32LE0.1kWh
Self-consumption of today13028U160.1%
Phase A current13030I160.1A
Phase B current13031I160.1A
Phase C current13032I160.1A
Total active power13033I32LE1W
Daily Import Energy13035U160.1kWh
Total Import Energy13036U32LE0.1kWh
Battery Capacity13038U160.1
Daily Charge Energy13039U160.1kWh
Total Charge Energy13040U32LE0.1kWh
DRM State13042U161
Daily export energy13044U160.1kWh
Total export energy13045U32LE0.1kWh
Inverter alarm13049U32LE1
Charge/discharge command13050U161
Grid-side fault13051U32LE1
System fault 113053U32LE1
System fault 213055U32LE1
DC-side fault13057U32LE1
Min. SOC13058U160.1%
Permanent fault13059U32LE1
BDC-side fault13061U32LE1
BDC-side permanent fault13063U32LE1
Battery fault13065U32LE1
Battery alarm13067U32LE1
BMS alarm13069U32LE1
BMS protection13071U32LE1
BMS fault 113073U32LE1
Off-grid option13074U161
BMS fault 213075U32LE1
BMS alarm 213077U32LE1
External EMS heartbeat13079U161s
Meter Comm. Detection13085U161
Export Power Limitation13086U161
Reserved SOC for backup13099U161%
Feed-in Limitation – Wide range31221U160.01kW
Charge Cutoff Voltage –Wide range33041U160.1V
Max. Charging Power33046U160.01kW
Max. Discharging Power33047U160.01kW
Charging/Discharging Power –Wide range33147U160.01kW
Forced Charging33207U161
Forced Charging Valid Time33208U161
Forced Charging Start Time 1 (h)33209U161h
Forced Charging Start Time 1 (min)33210U161min
Forced Charging End Time 1 (h)33211U161h
Forced Charging End Time 1 (min)33212U161min
Forced Charging Target SOC133213U161%
Forced Charging Start Time 2 (h)33214U161h
Forced Charging Start Time 2 (min)33215U161min
Forced Charging End Time 2 (h)33216U161h
Forced Charging End Time 2 (min)33217U161min
Forced Charging Target SOC 233218U161%
Load Rated Power33273U160.01kW

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.