Thermokon FTA54+ RH/temp sensor

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
UNI: Firmware0I161
UNI: Device Location1I161
UNI: Offset temperature5I160.01K
UNI: Offset rel. humidity6I160.01%
USE: Offset temperature100I160.1K
USE: Offset rel. humidity101I160.1%rH
USE: Unit system400I161
USE: Firmware version503I161
UNI: Relative humidity585I160.1%
UNI: Temperature587I160.01°C
UNI: Temperature588I160.01°F

link settings as documented (unverified): RTU/ASCII; default 9600 8E1; unit ID 1; When using ASCII mode, parity must be set to EVEN or ODD. 'No Parity' (no) is not available in ASCII mode. Register addressing mode (UNI or USE) is selectable via DIP switch 2.6.

⚠ The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsremovable plug-in terminal, max. 14AWG
A/B polarityIn case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device.
connectorremovable plug-in terminal
wiring notesCable entry Flextherm M20, for wire max. Ø=0.18..0.35 in., removable
protocol notesRegister compatibility to USE (Valid from firmware version 1.4, Jan. 2020). Via dipswitch 2.6 it is possible to change between the previous register addressing of the UNI-Modbus board to a USE compatible register assignment.
firmware register0 (Variant 1) or 503 (Variant 2)
identification notesFirmware version is available at register 0 in UNI-Modbus mode or register 503 in USE-Modbus mode.
power15..24 V = (±10%) (or 24 V ~ (±10%))* SELV, max. 0,7 W (24 V =) | 1,8 VA (24 V ~)
environmentAmbient condition -4..+158 °F, short term condensation. IP65 according to EN 60529
accuracyAccuracy temperature ±0,3 K (typ. at 70 °F), Accuracy humidity ±2% between 10..90% rH (typ. at 70 °F)
certificationsCE
doc revision05/21/2026 • A160
firmware applicabilityValid from firmware version 1.4, Jan. 2020
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [9600, 19200, 38400, 57600] and default baud rate 9600 — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: Default Unit ID is 1 — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: ASCII mode requires EVEN or ODD parity, No Parity is not available in ASCII mode — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: Register addressing mode (UNI or USE) is selectable via DIP switch 2.6 — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: Accuracy temperature ±0,3 K (typ. at 70 °F), Accuracy humidity ±2% between 10..90% rH (typ. at 70 °F) — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet (US version)
  • confirmed: Power supply 15..24 V = (±10%) or 24 V ~ (±10%) SELV, max. 0,7 W (24 V =) | 1,8 VA (24 V ~) — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: Ambient condition -4..+158 °F, short term condensation, IP65 according to EN 60529 — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet
  • confirmed: Reversed polarity at one field device causes a supply voltage short-circuit — confirmed by Thermokon FTA54+ Basic RS485 Modbus Datasheet

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.