Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Command mode selection | 3 | U16 | 1 | |
| Frequency setting mode selection 1 | 4 | U16 | 1 | |
| Setting of acceleration / deceleration time unit | 1305 | U16 | 1 | |
| Integrating wattmeter display unit selection | 1865 | U16 | 1 | |
| MODBUS continuous address | 2096 | U16 | 1 | |
| Number of motor pole pair for communication | 2134 | U16 | 1 | |
| Communication function reset | 2201 | U16 | 1 | |
| Device Name 1 | 49281 | U16 | 1 | |
| Device Name 2 | 49282 | U16 | 1 | |
| Device Name 3 | 49283 | U16 | 1 | |
| Device Name 4 | 49284 | U16 | 1 | |
| Device Name 5 | 49285 | U16 | 1 | |
| Device Name 6 | 49286 | U16 | 1 | |
| Device Name 7 | 49287 | U16 | 1 | |
| Device Name 8 | 49288 | U16 | 1 | |
| Device Name 9 | 49289 | U16 | 1 | |
| Device Name 10 | 49290 | U16 | 1 | |
| Device Name 11 | 49291 | U16 | 1 | |
| Device Name 12 | 49292 | U16 | 1 | |
| Device Name 13 | 49293 | U16 | 1 | |
| Device Name 14 | 49294 | U16 | 1 | |
| Device Name 15 | 49295 | U16 | 1 | |
| Device Name 16 | 49296 | U16 | 1 | |
| Emb Eth. Communication error detection delay | 50694 | U16 | 0.1 | sec |
| Emb Eth. Communication error operation | 50695 | U16 | 1 | |
| Emb Eth. Preset speed at communication error | 50696 | U16 | 1 | |
| Emb Eth. Communication error detection | 50697 | U16 | 1 | |
| Emb Eth. IP setting mode | 50698 | U16 | 1 | |
| Emb Eth. IP address setting value 1 | 50699 | U16 | 1 | |
| Emb Eth. IP address setting value 2 | 50700 | U16 | 1 | |
| Emb Eth. IP address setting value 3 | 50701 | U16 | 1 | |
| Emb Eth. IP address setting value 4 | 50702 | U16 | 1 | |
| Emb Eth. Subnet mask setting value 1 | 50703 | U16 | 1 | |
| Emb Eth. Subnet mask setting value 2 | 50704 | U16 | 1 | |
| Emb Eth. Subnet mask setting value 3 | 50705 | U16 | 1 | |
| Emb Eth. Subnet mask setting value 4 | 50706 | U16 | 1 | |
| Emb Eth. Default gateway setting value 1 | 50707 | U16 | 1 | |
| Emb Eth. Default gateway setting value 2 | 50708 | U16 | 1 | |
| Emb Eth. Default gateway setting value 3 | 50709 | U16 | 1 | |
| Emb Eth. Default gateway setting value 4 | 50710 | U16 | 1 | |
| Emb Eth. MAC address monitor 1 | 50723 | U16 | 1 | |
| Emb Eth. MAC address monitor 2 | 50724 | U16 | 1 | |
| Emb Eth. MAC address monitor 3 | 50725 | U16 | 1 | |
| Emb Eth. MAC address monitor 4 | 50726 | U16 | 1 | |
| Emb Eth. MAC address monitor 5 | 50727 | U16 | 1 | |
| Emb Eth. MAC address monitor 6 | 50728 | U16 | 1 | |
| Emb Eth. IP address monitor 1 | 50729 | U16 | 1 | |
| Emb Eth. IP address monitor 2 | 50730 | U16 | 1 | |
| Emb Eth. IP address monitor 3 | 50731 | U16 | 1 | |
| Emb Eth. IP address monitor 4 | 50732 | U16 | 1 | |
| Emb Eth. Subnet mask monitor 1 | 50733 | U16 | 1 | |
| Emb Eth. Subnet mask monitor 2 | 50734 | U16 | 1 | |
| Emb Eth. Subnet mask monitor 3 | 50735 | U16 | 1 | |
| Emb Eth. Subnet mask monitor 4 | 50736 | U16 | 1 | |
| Emb Eth. Default gateway monitor 1 | 50737 | U16 | 1 | |
| Emb Eth. Default gateway monitor 2 | 50738 | U16 | 1 | |
| Emb Eth. Default gateway monitor 3 | 50739 | U16 | 1 | |
| Emb Eth. Default gateway monitor 4 | 50740 | U16 | 1 | |
| Emb Eth. Scanner input select 1 | 50753 | U16 | 1 | |
| Emb Eth. Scanner input select 2 | 50754 | U16 | 1 | |
| Emb Eth. Scanner input select 3 | 50755 | U16 | 1 | |
| Emb Eth. Scanner input select 4 | 50756 | U16 | 1 | |
| Emb Eth. Scanner input select 5 | 50757 | U16 | 1 | |
| Emb Eth. Scanner input select 6 | 50758 | U16 | 1 | |
| Emb Eth. Scanner input select 7 | 50759 | U16 | 1 | |
| Emb Eth. Scanner input select 8 | 50760 | U16 | 1 | |
| Emb Eth. Scanner output select 1 | 50769 | U16 | 1 | |
| Emb Eth. Scanner output select 2 | 50770 | U16 | 1 | |
| Emb Eth. Scanner output select 3 | 50771 | U16 | 1 | |
| Emb Eth. Scanner output select 4 | 50772 | U16 | 1 | |
| Emb Eth. Scanner output select 5 | 50773 | U16 | 1 | |
| Emb Eth. Scanner output select 6 | 50774 | U16 | 1 | |
| Emb Eth. Scanner output select 7 | 50775 | U16 | 1 | |
| Emb Eth. Scanner output select 8 | 50776 | U16 | 1 | |
| Emb Eth. I/O scan timeout detection time | 50790 | U16 | 0.1 | s |
| Emb Eth. Web server | 50792 | U16 | 1 | |
| Emb Eth. Web server reset | 50793 | U16 | 1 | |
| Emb Eth. Unit ID | 50794 | U16 | 1 | |
| Emb Eth. Command monitor | 50838 | U16 | 1 | |
| Emb Eth. Frequency command monitor | 50839 | U16 | 1 | |
| Emb Eth. Error monitor | 50840 | U16 | 1 | |
| Emb Eth. External error monitor | 50841 | U16 | 1 | |
| Communication command1 from embedded ethernet | 64054 | U16 | 1 | |
| Frequency command from embedded ethernet | 64055 | U16 | 0.01 | Hz |
| Communication command 2 from embedded ethernet | 64056 | U16 | 1 | |
| Torque command setting from embedded ethernet | 64064 | U16 | 0.01 | % |
| Terminal output data | 64080 | U16 | 1 | |
| Alarm code | 64657 | U16 | 1 | |
| Output frequency | 64768 | U16 | 0.01 | Hz |
| Inverter status 1 | 64769 | U16 | 1 | |
| Output current | 64771 | U16 | 0.01 | % |
| Input voltage (DC detection) | 64772 | U16 | 0.01 | % (V) |
| Output voltage | 64773 | U16 | 0.01 | % (V) |
| Input terminal status | 64774 | U16 | 1 | |
| Output terminal status | 64775 | U16 | 1 | |
| Speed feedback frequency (real time) | 64790 | I16 | 0.01 | Hz |
| Torque | 64792 | I16 | 0.01 | % (Nm) |
| Torque current | 64796 | U16 | 1 | |
| PID feedback value | 64802 | U16 | 0.01 | Hz |
| Motor overload factor | 64803 | U16 | 1 | |
| Inverter overload factor | 64804 | U16 | 1 | |
| Braking resistor overload factor | 64805 | U16 | 1 | |
| Motor load factor | 64806 | U16 | 1 | |
| Inverter load factor | 64807 | U16 | 1 | |
| Input power | 64809 | U16 | 0.01 | kW |
| Cumulative run time for monitor | 65044 | U16 | 1 | hour |
| Terminal RR input value | 65077 | U16 | 0.01 | % |
| Terminal RX input value | 65078 | I16 | 0.01 | % |
| Terminal II input value | 65079 | U16 | 0.01 | % |
| FM output monitor | 65088 | U16 | 1 | |
| AM output monitor | 65089 | U16 | 1 |
| connector | Dual RJ45 shielded connector |
| wiring notes | Supports Daisy chain topology and Star topology. Auto MDI-X and LLDP are supported. |
| max registers/read | 63 |
| protocol notes | Writing via function codes 06 and 16 writes to EEPROM, which has a lifespan of approximately 100,000 writes. Writing via function code 23 (I/O scanning) writes to RAM. |
| identification notes | Supports Read Device Identification (0x2B) for Basic and Regular Device ID. |
| FC 43 device ID | supported |
| doc revision | E6582125② |
⚠ disputed: output_power @ 64810 — disputed by Embedded Ethernet Function Manual E6582125, which states output_power is at 0xFD30 (64816). 64810 (0xFD2A) is an invalid/unused address.
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.