device library

Trane Ascend/Symbio chiller controller

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Chilled Water Setpoint9F32BE1Degrees Fahrenhe
Active Chilled Water Setpoint10F32BE1Degrees Fahrenhe
Demand Limit Setpoint11F32BE1Percent
Evaporator Entering Water Temperature12F32BE1Degrees Fahrenhe
Evaporator Leaving Water Temperature14F32BE1Degrees Fahrenhe
Calculated Chiller Capacity16F32BE1Tons of Refriger
Active Demand Limit Setpoint18F32BE1Percent
Unit Power Consumption20F32BE1Kilowatts
Outdoor Air Temperature24F32BE1Degrees Fahrenhe
Evaporator Refrigerant Pressure Circuit 126F32BE1Pound Force per
Condenser Refrigerant Pressure Circuit 128F32BE1Pound Force per
Differential Refrigerant Pressure Circuit 130F32BE1Pound Force per
Evaporator Saturated Refrigerant Temperature Circuit 132F32BE1Degrees Fahrenhe
Condenser Saturated Refrigerant Temperature Circuit 134F32BE1Degrees Fahrenhe
Evaporator Refrigerant Pressure Circuit 236F32BE1Pound Force per
Condenser Refrigerant Pressure Circuit 238F32BE1Pound Force per
Differential Refrigerant Pressure Circuit 240F32BE1Pound Force per
Evaporator Saturated Refrigerant Temperature Circuit 242F32BE1Degrees Fahrenhe
Condenser Saturated Refrigerant Temperature Circuit 244F32BE1Degrees Fahrenhe
Refrigerant Discharge Temperature - Compressor 1A46F32BE1Degrees Fahrenhe
Oil Pressure - Compressor 1A48F32BE1Pound Force per
Refrigerant Discharge Temperature - Compressor 2A50F32BE1Degrees Fahrenhe
Oil Pressure - Compressor 2A52F32BE1Pound Force per
Air Flow Percentage Circuit 154F32BE1Percent
Air Flow Percentage Circuit 256F32BE1Percent
Starts - Compressor 1A58F32BE1No Units
Run Time - Compressor 1A60F32BE1Hours
Compressor 1A Speed Status62F32BE1Percent
Motor Winding Temperature 1 Circuit 164F32BE1Degrees Fahrenhe
Motor Winding Temperature 2 Circuit 166F32BE1Degrees Fahrenhe
Drive Motor Current U RLA Compressor 1A68F32BE1Percent
Drive Motor Current V RLA Compressor 1A70F32BE1Percent
Drive Motor Current W RLA Compressor 1A72F32BE1Percent
Drive Motor Average Current RLA Compressor 1A74F32BE1Percent
Drive Motor Current U Compressor 1A76F32BE1Amps
Drive Motor Current V Compressor 1A78F32BE1Amps
Drive Motor Current W Compressor 1A80F32BE1Amps
Drive Motor Voltage UV Circuit 182F32BE1Volts
Drive Motor Voltage VW Circuit 184F32BE1Volts
Drive Motor Voltage WU Circuit 186F32BE1Volts
Drive Motor Average Voltage Circuit 188F32BE1Volts
Drive DC Bus Voltage Circuit 190F32BE1Volts
Drive Output Power Circuit 192F32BE1Kilowatts
Drive Input Power Circuit 194F32BE1Kilowatts
Drive Line Average Voltage Circuit 196F32BE1Volts
Drive Average Line Current Circuit 198F32BE1Amps
Drive Line Frequency Circuit 1100F32BE1feet per second
AFD Frequency Circuit 1102F32BE1feet per second
AFD Transistor Temperature Circuit 1104F32BE1Degrees Fahrenhe
Drive Inverter Base Temperature Circuit 1106F32BE1Degrees Fahrenhe
Drive Rectifier Base Temperature Circuit 1108F32BE1Degrees Fahrenhe
Starts - Compressor 2A110F32BE1No Units
Run Time - Compressor 2A112F32BE1No Units
Compressor 2A Speed Status114F32BE1Percent
Motor Winding Temperature 1 Circuit 2116F32BE1Degrees Fahrenhe
Motor Winding Temperature 2 Circuit 2118F32BE1Degrees Fahrenhe
Drive Motor Current U RLA Compressor 2A120F32BE1Percent
Drive Motor Current V RLA Compressor 2A122F32BE1Percent
Drive Motor Current W RLA Compressor 2A124F32BE1Percent
Drive Motor Average Current RLA Compressor 2A126F32BE1Percent
Drive Motor Current U Compressor 2A128F32BE1Amps
Drive Motor Current V Compressor 2A130F32BE1Amps
Drive Motor Current W Compressor 2A132F32BE1Amps
Drive Motor Voltage UV Circuit 2134F32BE1Volts
Drive Motor Voltage VW Circuit 2136F32BE1Volts
Drive Motor Voltage WU Circuit 2138F32BE1Volts
Drive Motor Average Voltage Circuit 2140F32BE1Volts
Drive DC Bus Voltage Circuit 2142F32BE1Volts
Drive Output Power Circuit 2144F32BE1Kilowatts
Drive Input Power Circuit 2146F32BE1Kilowatts
Drive Line Average Voltage Circuit 2148F32BE1Volts
Drive Average Line Current Circuit 2150F32BE1Amps
Drive Line Frequency Circuit 2152F32BE1feet per second
AFD Frequency Circuit 2154F32BE1feet per second
AFD Transistor Temperature Circuit 2156F32BE1Degrees Fahrenhe
Drive Inverter Base Temperature Circuit 2158F32BE1Degrees Fahrenhe
Drive Rectifier Base Temperature Circuit 2160F32BE1Degrees Fahrenhe
Number Of Circuits162F32BE1No Units
Number Of Compressors Circuit 1164F32BE1No Units
Number Of Compressors Circuit 2166F32BE1No Units
Free Cooling Capacity168F32BE1Percent
Free Cooling Entering Water Temperature170F32BE1Degrees Fahrenhe
Energy Consumption Lifetime172F32BE1Kilowatts hour
Energy Consumption174F32BE1Kilowatts hour
Unit Source ID176F32BE1No Units
Chiller Design Capacity178F32BE1Tons of Refriger
Active Cool/Heat Setpoint Temperature180F32BE1Degrees Fahrenhe
Actual Running Capacity182F32BE1Percent
Running Mode2009U161
Operating Mode2010U161
Chiller Setpoint Source2011U161
Refrigerant Type2012U161
Cooling Type2013U161
Manufacture Location2014U161
Model Information [GEN2]2015U161
Run Enable3009I161
Local Setpoint Control3010I161
Limit Mode Relay Status3011I161
Chiller Running State3012I161
Maximum Capacity Relay3013I161
Evaporator Water Pump Command3014I161
Evaporator Water Flow Status3015I161
Manual Override Exists3016I161
Emergency Stop3017I161
Diagnostic Present3018I161
Diagnostic Shutdown Present3019I161
Diagnostic: Manual Reset Required3020I161
Diagnostic: Local Manual Reset Required3021I161
Diagnostic Present: Information3022I161
Diagnostic Present: Warning3023I161
Diagnostic Present: Critical3024I161
Diagnostic Present: Service Required3025I161
Running Status Cprsr1A3026I161
Running Status Cprsr2A3027I161
Free Cooling Active3028I161
External Auto Stop3029I161
Front Panel Auto/Stop3030I161
Noise Reduction Request Active3031I161

link settings as documented (unverified): RTU/TCP; default 19200 8E1; The valid range of Modbus RTU server addresses is 001–247. Rotary address 000 disables Modbus RTU communications.

bench facts as documented (unverified)
terminalsP1 Link (+ and - terminals)
A/B polarityObserve wire polarity when connecting to the + and - terminals. The + terminals and the - terminals are internally connected.
connectorRJ-45 for Modbus TCP on Ethernet port 1
wiring notesP1 Link is used for RS-485 daisy chain.
protocol notesThe Symbio 800 controller does not support the optional Wi-Fi module with Modbus TCP communications.
powerPower for the controller is provided and connected from within the chiller control panel.
doc revisionBAS-SVP045B-EN
field reports — community-sourced, unverified (checked 2026-06-11)
  • Modbus communication errors can occur on Symbio 800 controllers due to harness damage, water intrusion in plug connections, or electromagnetic interference if the Modbus cable is not separated from the control power transformer as it exits the top of the control box. [source]
  • confirmed: comms.default_baud: 19200 — confirmed by Trane Integration Guide BAS-SVP045B-EN, which lists the default baud rate as 19200 bps [2.3.1].
  • confirmed: comms.framing: ['RTU', 'TCP'] — confirmed by Trane Integration Guide BAS-SVP045B-EN, which details configuration for both Modbus RTU and Modbus TCP.
  • confirmed: comms.notes: The valid range of Modbus RTU server addresses is 001–247. Rotary address 000 disables Modbus RTU communications. — confirmed by Trane Integration Guide BAS-SVP045B-EN, which states that the valid range is 001-247 and setting the rotary address to 000 disables Modbus RTU communications.
  • confirmed: comms.parity: E — confirmed by Trane Integration Guide BAS-SVP045B-EN, which lists the default parity as Even.
  • confirmed: comms.stop_bits: 1 — confirmed by Trane Integration Guide BAS-SVP045B-EN, which lists the default stop bits as 1.
  • confirmed: facts.doc_revision: BAS-SVP045B-EN — confirmed by the official Trane document title 'BACnet® and Modbus Integration to Ascend™ Air-Cooled Chiller Model ACR with Symbio™ 800 Controls'.
  • confirmed: facts.physical.connector: RJ-45 for Modbus TCP on Ethernet port 1 — confirmed by Trane Integration Guide BAS-SVP045B-EN, which instructs to connect an Ethernet cable with RJ-45 connectors to Ethernet port 1.
  • confirmed: facts.physical.notes: P1 Link is used for RS-485 daisy chain. — confirmed by Trane Integration Guide BAS-SVP045B-EN, which states P1 Link is used for RS-485 daisy chain connection to a primary controller.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.