Utility Relay AC-PRO-II trip unit

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
alarm_status_code_07040U161
alarm_code_17041U161
current_phase_a7042U161A
current_phase_b7043U161A
current_phase_c7044U161A
current_neutral7045U161A
current_gf7046U161A
voltage_a_n7047U161V
voltage_b_n7048U161V
voltage_c_n7049U161V
voltage_a_b7050U161V
voltage_b_c7051U161V
voltage_c_a7052U161V
power_kw_phase_a7053U161kW
power_kw_phase_b7054U161kW
power_kw_phase_c7055U161kW
power_kva_phase_a7056U161kVA
power_kva_phase_b7057U161kVA
power_kva_phase_c7058U161kVA
power_kw_total7059U161kW
power_kva_total7060U161kVA
power_factor_total7061U161%
energy_kva_hrs7062U32BE1kVAh
energy_kw_hrs7064U32BE1kWh
kw_signs_lead_lag_pf7066U161
energy_kw_hrs_alt7067U32BE1kWh
frequency7069U161Hz
negative_sequence_overvoltage7070U161%
status7071U161
special_current_phase_a7072U161A
special_current_phase_b7073U161A
special_current_phase_c7074U161A
special_neutral_current7075U161A
special_gf_current7076U161A
breaker_cycle_count7090U161
last_kwd7901U161kW
last_kvad7902U161kVA
peak_kwd7903U161kW
peak_kvad7904U161kVA
demand_period7905U161s

link settings as documented (unverified): RTU

bench facts as documented (unverified)
terminals+24 VDC Aux Power, Sluggish Breaker Limit Switch, GF Defeat, Programmable Relay Output, Breaker Harness (Neutral, Phase C, Phase B, Phase A Actuator)
terminationRS485 End of Line Termination switch (ON/OFF)
connectorQuick-Trip Connector, USB, RS485
serial register7022-7026
firmware register7027-7028
power+24 VDC
certificationsUL, CE
doc revision4.0
firmware applicabilityv4.0.65
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Modbus RTU framing — confirmed by AC-PRO-II Instruction Manual
  • confirmed: Firmware applicability v4.0.65 and Document Revision 4.0 — confirmed by AC-PRO-II Communications Modbus Register Map rev 4.0
  • confirmed: Serial number registers 7022-7026 and Firmware version registers 7027-7028 — confirmed by AC-PRO-II Communications Modbus Register Map rev 4.0
  • confirmed: RS485 End of Line Termination switch (ON/OFF) — confirmed by AC-PRO-II Quick Start Manual
  • confirmed: Register map addresses (e.g., alarm_status_code_0 @ 7040, current_phase_a @ 7042, last_kwd @ 7901) — confirmed by AC-PRO-II Communications Modbus Register Map rev 4.0

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.