Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| RH | 0 | F32LE | 1 | % |
| T | 2 | F32LE | 1 | °C |
| Td | 6 | F32LE | 1 | °C |
| Td/f | 8 | F32LE | 1 | °C |
| a | 14 | F32LE | 1 | g/m³ |
| x | 16 | F32LE | 1 | g/kg |
| Tw | 18 | F32LE | 1 | °C |
| H2O | 20 | F32LE | 1 | ppmV |
| pw | 22 | F32LE | 1 | hPa |
| pws | 24 | F32LE | 1 | hPa |
| H | 26 | F32LE | 1 | kJ/kg |
| ΔT | 30 | F32LE | 1 | °C |
| H2O | 64 | F32LE | 1 | ppmW |
| RH | 256 | I16 | 0.01 | % |
| T | 257 | I16 | 0.01 | °C |
| Td | 259 | I16 | 0.01 | °C |
| Td/f | 260 | I16 | 0.01 | °C |
| a | 263 | I16 | 0.01 | g/m³ |
| x | 264 | I16 | 0.01 | g/kg |
| Tw | 265 | I16 | 0.01 | °C |
| H2O | 266 | I16 | 1 | ppmV |
| pw | 267 | I16 | 0.1 | hPa |
| pws | 268 | I16 | 0.1 | hPa |
| H | 269 | I16 | 0.01 | kJ/kg |
| ΔT | 271 | I16 | 0.01 | °C |
| H2O | 288 | I16 | 1 | ppmW |
| Fault status | 512 | U16 | 1 | |
| Online status | 513 | U16 | 1 | |
| Error code (bits 15...0) | 515 | U16 | 1 | |
| Error code (bits 31...16) | 516 | U16 | 1 | |
| Pressure setting default value | 768 | F32LE | 1 | hPa |
| Pressure setting temporary value | 770 | F32LE | 1 | hPa |
| Chemical purge interval | 772 | F32LE | 1 | min |
| Molecular weight for ppmw calculation | 774 | F32LE | 1 | g/mol |
| Pressure setting default value | 1024 | I16 | 1 | hPa |
| Pressure setting temporary value | 1025 | I16 | 1 | hPa |
| Chemical purge interval | 1026 | I16 | 1 | min |
| Molecular weight for ppmw calculation | 1027 | I16 | 0.001 | g/mol |
| Standard filtering on/off | 1280 | U16 | 1 | |
| Extended filtering on/off | 1281 | U16 | 1 | |
| Automatic chemical purge on/off | 1282 | U16 | 1 | |
| Start-up chemical purge on/off | 1283 | U16 | 1 | |
| Chemical purge in progress | 1284 | U16 | 1 | |
| Sensor heating on/off | 1286 | U16 | 1 |
| terminals | Screw Terminal Block on Motherboard |
| connector | RJ45 for LAN, RP-SMA for WLAN, optional 8-pin M12 male |
| isolation | RS-485 interface is isolated to 300VDC |
| shield/ground | Grounding screen of electrical cable and grounding connector inside housing |
| broadcast | supported |
| protocol notes | Modbus TCP can process reliably only one Modbus transaction at a time. Reduce the polling rate of the client to avoid nested transactions. |
| identification notes | Supports Device Identification Objects: VendorName (0x00), ProductCode (0x01), MajorMinorVersion (0x02), VendorUrl (0x03), ProductName (0x04), SerialNumber (0x80), CalibrationDate (0x81), CalibrationText (0x82) |
| FC 43 device ID | supported |
| power | 10 ... 35 VDC, 24 VAC (optional power supply module: 100 ... 240 VAC, 50/60 Hz) |
| environment | Operating temperature range for humidity measurement: -70 ... +180 °C, for transmitter body electronics: -40 ... +60 °C (with display: 0 ... +60 °C) |
| accuracy | Accuracy of analog outputs at 20 °C: ± 0.05 % full scale |
| certifications | EN61326-1, UL file number E249387 |
| doc revision | M210566EN-K |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.