coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Parameter access level0U161
Initialization3U161
Keyboard parameter copy4U161
User password5U161
LCD keyboard language selection6U161
Free parameter 17U161
Free parameter 28U161
Motor 1 control mode256U161
Run command channel257U161
Frequency reference source channel A258U161
Frequency reference source channel A gain259U161
Frequency reference source channel B260U161
Frequency reference source channel B gain261U161
Frequency channel B reference source262U161
Frequency reference source selection263U161
Run command bundled given frequency264U161
Keyboard digital given frequency265U161
Maximum frequency266U161
Upper frequency source selection267U161
Upper limit frequency digital setting268U161
Lower limit frequency269U161
Acceleration/deceleration time reference frequency276U161
Acceleration time unit277U161
Acceleration time 1278U161
Deceleration time 1279U161
Acceleration time 2280U161
Deceleration time 2281U161
Acceleration time 3282U161
Deceleration time 3283U161
Acceleration time 4284U161
Deceleration time 4285U161
S curve acceleration and deceleration selection286U161
Acceleration start S curve time287U161
Accelerated end S curve time288U161
Deceleration start S curve time289U161
Deceleration end S curve time290U161
Acceleration time 1 and acceleration time 2 switching freque291U161
Carrier frequency296U161
PWM control mode297U161
Reserved298U161
Dead zone compensation gain299U161
Motor type512U161
Pole number513U161
Motor rated power514U161
Motor rated frequency515U161
Motor rated speed516U161
Motor rated voltage517U161
Motor rated current518U161
Motor parameter auto-tuning selection519U161
Asynchronous motor no-load current522U161
Asynchronous motor stator resistance523U161
Asynchronous motor rotor resistance524U161
Asynchronous motor stator leakage inductance525U161
Asynchronous motor stator inductance526U161
Stator resistance standard value527U161
Rotor resistance standard value528U161
Stator leakage inductance529U161
Stator inductance value530U161
F02.11~F02.14 decimal point selection531U161
Motor online learning function selection562U161
ASR speed rigidity level768U161
ASR speed rigid mode769U161
ASR (speed loop) proportional gain 1770U161
ASR (speed loop) integration time 1771U161
ASR filtering time 1772U161
ASR switching frequency 1773U161
ASR (speed loop) proportional gain 2774U161
ASR (speed loop) integration time 2775U161
ASR filtering time 2776U161
ASR switching frequency 2777U161
Current loop D-axis proportional gain778U161
Current loop D-axis integral gain779U161
Current loop Q-axis proportional gain780U161
Current loop Q-axis integral gain781U161
Electric state torque limit782U161
Power generation torque limit783U161
Regenerative torque limit at low speed786U161
Torque limit action frequency amplitude at low speed787U161
Asynchronous motor slip compensation788U161
Starting torque initial value789U161
Weak magnetic feedforward coefficient798U161
Weak magnetic control gain799U161
Weak magnetic current upper limit800U161
Weak magnetic voltage coefficient801U161
Output power limit802U161
Overexcitation braking gain803U161
Overexcitation braking limit804U161
Energy efficient operation805U161
Energy-saving operation excitation lower limit806U161
Energy-saving operating filter coefficient807U161
Torque control selection808U161
Torque command given809U161
Torque keyboard digital setting810U161
Torque input lower limit811U161
Lower limit corresponding setting812U161
Torque input upper limit813U161
Upper limit corresponding setting814U161
Torque filtering time815U161
Torque command upper limit820U161
Torque command lower limit821U161
Torque control forward speed limit selection822U161
Torque control reverse speed limit selection823U161
Torque control forward speed maximum speed limit824U161
Torque control anyway maximum speed limit825U161
Given torque gain switching frequency826U161
Given torque gain827U161
Linear VF curve selection1024U161
Torque boost1025U161
Torque boost cutoff frequency1026U161
Slip compensation gain1027U161
Slip compensation limit1028U161
Slip compensation filter time1029U161
Oscillation suppression gain1030U161
Oscillation suppression filter time1031U161
Output voltage percentage1032U161
Self-setting voltage V11034U161
Self-set frequency F11035U161
Self-setting voltage V21036U161
Self-set frequency F21037U161
Self-setting voltage V31038U161
Self-set frequency F31039U161
Self-setting voltage V41040U161
Self-set frequency F41041U161
Self-setting voltage V51042U161
Self-set frequency F51043U161
Automatic energy saving control1054U161
Energy saving step frequency lower limit1055U161
Energy-saving step-down voltage lower limit1056U161
Energy-saving step-down voltage regulation rate1057U161
Energy-saving voltage and voltage recovery rate1058U161
Terminal X1 function selection1280U161
Terminal X2 function selection1281U161
Terminal X3 function selection1282U161
Terminal X4 function selection1283U161
X1 effective detection delay1290U161
X1 invalid detection delay1291U161
X2 effective detection delay1292U161
X2 invalid detection delay1293U161
X3 effective detection delay1294U161
X3 invalid detection delay1295U161
X4 effective detection delay1296U161
X4 invalid detection delay1297U161
Terminal control mode1300U161
Terminal start protection1301U161
X1 ~ X4 terminal characteristics selection1302U161
Terminal UP/DW control selection1305U161
Terminal UP/DW controls frequency increase and decrease rate1306U161
Terminal emergency stop deceleration time1307U161
Reserved1310U161
PUL input minimum frequency1311U161
PUL minimum frequency corresponding setting1312U161
PUL input maximum frequency1313U161
PUL maximum frequency corresponding setting1314U161
PUL filter time1315U161
PUL cutoff frequency1316U161
AI input signal type selection method1320U161
Analog input curve selection1323U161
AI lower limit1330U161
AI lower limit corresponding setting1331U161
AI upper limit1332U161
AI upper limit corresponding setting1333U161
AI filter time1334U161
Curve 1 lower limit1340U161
Curve 1 lower limit corresponding setting1341U161
Curve 1 inflection point 1 input voltage1342U161
Curve 1 inflection point 1 corresponding setting1343U161
Curve 1 inflection point 2 input voltage1344U161
Curve 1 inflection point 2 corresponding setting1345U161
Curve 1 upper limit1346U161
Curve 1 upper limit corresponding setting1347U161
Curve 2 lower limit1350U161
Curve 2 lower limit corresponding setting1351U161
Curve 2 inflection point 1 input voltage1352U161
Curve 2 inflection point 1 corresponding setting1353U161
Curve 2 inflection point 2 input voltage1354U161
Curve 2 inflection point 2 corresponding setting1355U161
Curve 2 upper limit1356U161
Curve 2 upper limit corresponding setting1357U161
AI port to do digital input terminal feature selection1360U161
AI terminal function selection (as X)1361U161
AI high level setting1362U161
AI low level setting1363U161
AO output mode selection1536U161
AO output selection1537U161
AO output gain1538U161
AO output bias1539U161
AO output filtering1540U161
Output terminal polarity selection1556U161
Output terminal Y1557U161
Relay 1 output (TA-TB-TC)1558U161
Y output ON delay time1561U161
Relay 1 output ON delay time1562U161
Y output OFF delay time1565U161
Relay 1 output OFF delay time1566U161
Frequency detection value 11576U161
Frequency detection amplitude 11577U161
Frequency detection value 21578U161
Frequency detection range 21579U161
The given frequency reaches the detection range1580U161
Comparator 1 monitor selection1586U161
Comparator 1 upper limit1587U161
Comparator 1 lower limit1588U161
Comparator 1 bias1589U161
Action selection when sending CP11590U161
Comparator 2 monitor selection1591U161
Comparator 2 upper limit1592U161
Comparator 2 lower limit1593U161
Comparator 2 bias1594U161
Action selection when sending CP21595U161
Virtual vX1 terminal function selection1596U161
Virtual vX2 terminal function selection1597U161
Virtual vX3 terminal function selection1598U161
Virtual vX4 terminal function selection1599U161
vX terminal valid status source1600U161
Virtual vX terminal function code setting valid status1601U161
Virtual vY1 output selection1602U161
Virtual vY2 output selection1603U161
Virtual vY3 output selection1604U161
Virtual vY4 output selection1605U161
vY1 output ON delay time1606U161
vY2 output ON delay time1607U161
vY3 output ON delay time1608U161
vY4 output ON delay time1609U161
vY1 output OFF delay time1610U161
vY2 output OFF delay time1611U161
vY3 output OFF delay time1612U161
vY4 output OFF delay time1613U161
Start mode1792U161
Start pre-excitation time1793U161
Starting frequency1794U161
Start protection selection1795U161
Direction of rotation1797U161
Power failure restart action selection1798U161
Power failure restart waiting time1799U161
Stop mode1802U161
Shutdown detection frequency1803U161
Stop and restart limit time1804U161
Insufficient lower limit frequency action selection1807U161
Zero speed torque retention factor1808U161
Zero speed torque holding time1809U161
Positive reversal dead time1810U161
Braking current before starting1812U161
Braking time before starting1813U161
DC braking start frequency1814U161
DC braking current1815U161
DC braking time during shutdown1816U161
Speed tracking mode1817U161
Speed tracking speed1818U161
Speed tracking stop delay1819U161
Speed tracking current1820U161
Jog running frequency setting1822U161
Jog acceleration time1823U161
Jog deceleration time1824U161
Jog S curve selection1825U161
Jog stop mode selection1826U161
Maintain frequency at startup1832U161
Maintain frequency time at startup1833U161
Maintain frequency during shutdown1834U161
Maintain frequency time during shutdown1835U161
Jump frequency 11836U161
Jump frequency amplitude1837U161
Jump frequency 21838U161
Jump frequency amplitude1839U161
Counter input source2048U161
Count input crossover2049U161
Counter maximum2050U161
Counter setting2051U161
Pulse number per meter2052U161
Set length2053U161
Actual length2054U161
Timer time unit2055U161
Timer setting2056U161
Swing frequency control2078U161
Swing frequency amplitude control2079U161
Swing frequency preset frequency2080U161
Swing frequency preset frequency waiting time2081U161
Swing frequency amplitude2082U161
Kick frequency2083U161
Triangle wave rise time2084U161
Triangle wave fall time2085U161
Overcurrent suppression2560U161
Overcurrent suppression point2561U161
Overcurrent suppression gain2562U161
Current protection setting 12563U161
Current protection setting 22564U161
Operation Pause Delay2570U161
Bus overvoltage suppression2571U161
Bus overvoltage suppression point2572U161
Bus overvoltage suppression gain2573U161
Energy brake enable2574U161
Energy consumption braking action voltage2575U161
Bus undervoltage suppression2576U161
Bus undervoltage suppression point2577U161
Bus undervoltage suppression gain2578U161
Bus undervoltage protection point2579U161
Input and output phase loss protection options2580U161
Input phase loss threshold2581U161
Ground short circuit protection option2582U161
Fan ON/OFF control selection2583U161
Fan control delay time2584U161
AC Drive overheating oH1 detection level2585U161
Motor overload protection curve coefficient2590U161
Selection of AC Drive overload characteristics at low speed2591U161
Load warning checkout setting2592U161
Load warning detection level 12593U161
Load warning detection time 12594U161
Load warning detection level 22595U161
Load warning detection time 22596U161
Too large peed deviation protection action2600U161
Speed deviation excessive detection threshold2601U161
Speed deviation too large detection time2602U161
Speed protection action2603U161
Rapid detection threshold2604U161
Rapid speed detection time2605U161
Failure self-recovery2610U161
Failure self-recovery interval2611U161
Numbers of failures recovered2612U161
Key lock selection2816U161
Key lock password2817U161
Keyboard multi-function key selection2818U161
Keyboard STOP button settings2819U161
Status interface up and down keys (knob) function selection2820U161
Up and down keys to quickly change the parameter code settin2821U161
Keyboard command key selection2822U161
Status interface left shift, right shift key function select2826U161
Parameter 1 showed up on first line of the keyboard2827U161
Parameter 2 showed up on first line of the keyboard2828U161
Parameter 3 showed up on first line of the keyboard2829U161
Parameter 4 showed up on first line of the keyboard2830U161
Parameter 1 showed up on second line of the keyboard2831U161
Parameter 2 showed up on second line of the keyboard2832U161
Parameter 3 showed up on second line of the keyboard2833U161
Parameter 4 showed up on second line of the keyboard2834U161
Keyboard display item settings2836U161
Speed display factor2837U161
Power display factor2838U161
Monitoring parameter group display selection2839U161
Reserved2840U161
Display selection when the motor is self-tuning2841U161
AC10 serial port function selection2846U161
Keyboard potentiometer lower limit voltage2847U161
Keyboard potentiometer lower limit corresponding value2848U161
Keyboard potentiometer upper limit voltage2849U161
Keyboard potentiometer upper limit corresponding value2850U161
External keyboard potentiometer control2851U161
Master-slave choice3072U161
Modbus communication address3073U161
Communication baud rate selection3074U161
Modbus data format3075U161
Modbus transmission response processing3076U161
Modbus communication response delay3077U161
Modbus communication timeout failure time3078U161
Communication disconnection processing3079U161
Receive data (address 0x3000) zero bias3080U161
Receive data (address 0x3000) gain3081U161
Host cyclically send parameter selection3082U161
Frequency given custom address setting3083U161
Command given custom address settings3084U161
Command given as forward run command value3085U161
Command given as reverse run command value3086U161
Command given as stop command value3087U161
Command given as reset command value3088U161
PID controller given signal source3328U161
Keyboard digital PID given / feedback3329U161
PID given change time3330U161
PID controller feedback signal source3331U161
Feedback signal low pass filtering time3332U161
Feedback signal gain3333U161
Feedback signal range3334U161
PID control selection3335U161
PID preset output3336U161
PID preset output running time3337U161
PID control deviation limit3338U161
Proportional gain P13339U161
Integration time I13340U161
Differential gain D13341U161
Proportional gain P23342U161
Integration time I23343U161
Differential gain D23344U161
PID parameter switching condition3345U161
Switching deviation low value3346U161
Switching deviation high value3347U161
Reserved3348U161
Differential limiting3349U161
PID output upper limit3350U161
PID output lower limit3351U161
PID output filtering time3352U161
Feedback disconnection action selection3353U161
Feedback disconnection detection time3354U161
Wire break alarm upper limit3355U161
Wire break alarm lower limit3356U161
Sleep selection3357U161
Sleep frequency3358U161
Sleep delay3359U161
Wake up deviation3360U161
Wake-up delay3361U161
PLC multi-speed 13584U161
PLC multi-speed 23585U161
PLC multi-speed 33586U161
PLC multi-speed 43587U161
PLC multi-speed 53588U161
PLC multi-speed 63589U161
PLC multi-speed 73590U161
PLC multi-speed 83591U161
PLC multi-speed 93592U161
PLC multi-speed 103593U161
PLC multi-speed 113594U161
PLC multi-speed 123595U161
PLC multi-speed 133596U161
PLC multi-speed 143597U161
PLC multi-speed 153598U161
PLC operation mode selection3599U161
PLC first stage running time3600U161
PLC second stage running time3601U161
PLC third stage running time3602U161
PLC fourth stage running time3603U161
PLC fifth stage running time3604U161
PLC sixth stage running time3605U161
PLC seventh stage running time3606U161
PLC eighth stage running time3607U161
PLC ninth stage running time3608U161
PLC tenth stage running time3609U161
PLC eleventh stage running time3610U161
PLC twelveth stage running time3611U161
PLC thirteenth stage running time3612U161
PLC fourteenth stage running time3613U161
PLC fifteenth stage running time3614U161
PLC first direction and acceleration and deceleration time3615U161
PLC second direction and acceleration and deceleration time3616U161
PLC third direction and acceleration and deceleration time3617U161
PLC fourth direction and acceleration and deceleration time3618U161
PLC fifth direction and acceleration and deceleration time3619U161
PLC sixth direction and acceleration and deceleration time3620U161
PLC seventh direction and acceleration and deceleration time3621U161
PLC eighth direction and acceleration and deceleration time3622U161
PLC ninth direction and acceleration and deceleration time3623U161
PLC tenth direction and acceleration and deceleration time3624U161
PLC eleventh direction and acceleration and deceleration tim3625U161
PLC twelveth direction and acceleration and deceleration tim3626U161
PLC thirteenth direction and acceleration and deceleration t3627U161
PLC fourteenth direction and acceleration and deceleration t3628U161
PLC fifteenth direction and acceleration and deceleration ti3629U161
Given frequency8448U161
Output frequency8449U161
Output current8450U161
Input voltage8451U161V
The output voltage8452U161V
Mechanical speed8453I161
Given torque8454I161%
Output torque8455I161%
PID given8456U161%
PID feedback8457U161%
Output Power8458U161
bus voltage8459U161V
Module temperature 18460I161°C
Module temperature 28461I161°C
Input terminal X is on8462U161
Output terminal Y is on8463U161
Analog AI input value8464U161V
Reserved8465U161
Keyboard potentiometer input value8466U161
Pulse signal PUL input value8467U161
Analog output AO8468U161
Reserved8469U161
Counter count value8470U161
Power-on running time8471U161
Accumulated running time of the machine8472U161
AC Drive power level8473U161
AC Drive rated voltage8474U161
AC Drive rated current8475U161
Software version8476U161
PG feedback frequency8477U161
Timer timing8478U161
PID output value8479U161
AC Drive software subversion8480U161
Encoder feedback angle8481U161
Z pulse cumulative error8482U161
Z pulse count8483U161
Failure warning code8484U161
Cumulative power consumption (low level)8485U161
Cumulative power consumption (high)8486U161
Power factor angle8487U161
Fault type diagnostic information8704U161
Troubleshooting information8705U161
Fault operating frequency8706U161
Fault output voltage8707U161
Fault output current8708U161
Fault bus voltage8709U161
Faulty module temperature8710U161
Faulty AC Drive status8711U161
Fault input terminal status8712U161
Fault output terminal status8713U161
Previous failure type8714U161
Previous troubleshooting information8715U161
The first fault operation frequency8716U161
Last fault output voltage8717U161
Last fault output current8718U161
The first fault bus voltage8719U161
The first fault module temperature8720U161
The first faulty AC Drive status8721U161
The first fault input terminal status8722U161
The first fault output terminal status8723U161
First 2 fault types8724U161
The first 2 troubleshooting information8725U161
Top 3 fault types8726U161
The first 3 troubleshooting information8727U161
Communication Given Frequency12288U160.01Hz
Communication Command Setting12289U161
State of AC Drive12290U161
AC Drive Fault Code12291U161
Communication Given Upper Frequency12292U160.01Hz
Communication Torque Setting12293U160.1%
The FWD Max Frequency limit in Torque Control12294U160.1%
The REV Max Frequency limit in Torque Control12295U160.1%
Communication Given PID Setting12296U160.1%
Communication Given PID Feedback12297U160.1%
Fault and warning code reading12304U161
Output terminal state12312U161
AO output12313U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,06; When F11.30 selects the external keyboard, the MODBUS bus (master/slave) cannot be used.

bench facts as documented (unverified)
terminalsA+, B-
termination120Ω termination resistor selectable via switch S3
wiring notesRS485 differential communication
response timeout1000 ms
inter-frame delay0 ms
protocol notesInterval over 1.5 byte before ending clears half-baked info. Interval under 3.5 byte time is considered continuation of former frame. Writing to 0x00XX writes to RAM, writing to 0x10XX writes to EEPROM.
powerS2: Single-phase 220V, T2: Three-phase 220V, T3: Three-phase 380V
environment-10 ~ +50°C (derating above 40°C, max 60°C), 5% to 95% RH (no condensation), altitude < 1000m, vibration 5.9 m/s2 (0.6 g)
certificationsIEC61800-2
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400, 57600], default baud 9600, default unit ID 1, framing RTU, parity N, stop bits 1 — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: When F11.30 selects the external keyboard, the MODBUS bus (master/slave) cannot be used — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: RS485 differential communication terminals A+, B- and 120Ω termination resistor selectable via switch S3 — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: Power models S2 (Single-phase 220V), T2 (Three-phase 220V), and T3 (Three-phase 380V) — confirmed by VEICHI AC10 Series Frequency Inverter Catalog and Quick Start Guide
  • confirmed: Register addresses 12288 (0x3000) for given frequency, 12289 (0x3001) for command setting, 12290 (0x3002) for state of AC drive, and 12291 (0x3003) for fault code — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: Register addresses 8448 (0x2100) for given frequency, 8449 (0x2101) for output frequency, 8450 (0x2102) for output current, and 8451 (0x2103) for input voltage — confirmed by VEICHI AC10 Series Frequency Inverter Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.