Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Parameter access level | 0 | U16 | 1 | |
| Initialization | 3 | U16 | 1 | |
| Keyboard parameter copy | 4 | U16 | 1 | |
| User password | 5 | U16 | 1 | |
| LCD keyboard language selection | 6 | U16 | 1 | |
| Free parameter 1 | 7 | U16 | 1 | |
| Free parameter 2 | 8 | U16 | 1 | |
| Motor 1 control mode | 256 | U16 | 1 | |
| Run command channel | 257 | U16 | 1 | |
| Frequency reference source channel A | 258 | U16 | 1 | |
| Frequency reference source channel A gain | 259 | U16 | 1 | |
| Frequency reference source channel B | 260 | U16 | 1 | |
| Frequency reference source channel B gain | 261 | U16 | 1 | |
| Frequency channel B reference source | 262 | U16 | 1 | |
| Frequency reference source selection | 263 | U16 | 1 | |
| Run command bundled given frequency | 264 | U16 | 1 | |
| Keyboard digital given frequency | 265 | U16 | 1 | |
| Maximum frequency | 266 | U16 | 1 | |
| Upper frequency source selection | 267 | U16 | 1 | |
| Upper limit frequency digital setting | 268 | U16 | 1 | |
| Lower limit frequency | 269 | U16 | 1 | |
| Acceleration/deceleration time reference frequency | 276 | U16 | 1 | |
| Acceleration time unit | 277 | U16 | 1 | |
| Acceleration time 1 | 278 | U16 | 1 | |
| Deceleration time 1 | 279 | U16 | 1 | |
| Acceleration time 2 | 280 | U16 | 1 | |
| Deceleration time 2 | 281 | U16 | 1 | |
| Acceleration time 3 | 282 | U16 | 1 | |
| Deceleration time 3 | 283 | U16 | 1 | |
| Acceleration time 4 | 284 | U16 | 1 | |
| Deceleration time 4 | 285 | U16 | 1 | |
| S curve acceleration and deceleration selection | 286 | U16 | 1 | |
| Acceleration start S curve time | 287 | U16 | 1 | |
| Accelerated end S curve time | 288 | U16 | 1 | |
| Deceleration start S curve time | 289 | U16 | 1 | |
| Deceleration end S curve time | 290 | U16 | 1 | |
| Acceleration time 1 and acceleration time 2 switching freque | 291 | U16 | 1 | |
| Carrier frequency | 296 | U16 | 1 | |
| PWM control mode | 297 | U16 | 1 | |
| Reserved | 298 | U16 | 1 | |
| Dead zone compensation gain | 299 | U16 | 1 | |
| Motor type | 512 | U16 | 1 | |
| Pole number | 513 | U16 | 1 | |
| Motor rated power | 514 | U16 | 1 | |
| Motor rated frequency | 515 | U16 | 1 | |
| Motor rated speed | 516 | U16 | 1 | |
| Motor rated voltage | 517 | U16 | 1 | |
| Motor rated current | 518 | U16 | 1 | |
| Motor parameter auto-tuning selection | 519 | U16 | 1 | |
| Asynchronous motor no-load current | 522 | U16 | 1 | |
| Asynchronous motor stator resistance | 523 | U16 | 1 | |
| Asynchronous motor rotor resistance | 524 | U16 | 1 | |
| Asynchronous motor stator leakage inductance | 525 | U16 | 1 | |
| Asynchronous motor stator inductance | 526 | U16 | 1 | |
| Stator resistance standard value | 527 | U16 | 1 | |
| Rotor resistance standard value | 528 | U16 | 1 | |
| Stator leakage inductance | 529 | U16 | 1 | |
| Stator inductance value | 530 | U16 | 1 | |
| F02.11~F02.14 decimal point selection | 531 | U16 | 1 | |
| Motor online learning function selection | 562 | U16 | 1 | |
| ASR speed rigidity level | 768 | U16 | 1 | |
| ASR speed rigid mode | 769 | U16 | 1 | |
| ASR (speed loop) proportional gain 1 | 770 | U16 | 1 | |
| ASR (speed loop) integration time 1 | 771 | U16 | 1 | |
| ASR filtering time 1 | 772 | U16 | 1 | |
| ASR switching frequency 1 | 773 | U16 | 1 | |
| ASR (speed loop) proportional gain 2 | 774 | U16 | 1 | |
| ASR (speed loop) integration time 2 | 775 | U16 | 1 | |
| ASR filtering time 2 | 776 | U16 | 1 | |
| ASR switching frequency 2 | 777 | U16 | 1 | |
| Current loop D-axis proportional gain | 778 | U16 | 1 | |
| Current loop D-axis integral gain | 779 | U16 | 1 | |
| Current loop Q-axis proportional gain | 780 | U16 | 1 | |
| Current loop Q-axis integral gain | 781 | U16 | 1 | |
| Electric state torque limit | 782 | U16 | 1 | |
| Power generation torque limit | 783 | U16 | 1 | |
| Regenerative torque limit at low speed | 786 | U16 | 1 | |
| Torque limit action frequency amplitude at low speed | 787 | U16 | 1 | |
| Asynchronous motor slip compensation | 788 | U16 | 1 | |
| Starting torque initial value | 789 | U16 | 1 | |
| Weak magnetic feedforward coefficient | 798 | U16 | 1 | |
| Weak magnetic control gain | 799 | U16 | 1 | |
| Weak magnetic current upper limit | 800 | U16 | 1 | |
| Weak magnetic voltage coefficient | 801 | U16 | 1 | |
| Output power limit | 802 | U16 | 1 | |
| Overexcitation braking gain | 803 | U16 | 1 | |
| Overexcitation braking limit | 804 | U16 | 1 | |
| Energy efficient operation | 805 | U16 | 1 | |
| Energy-saving operation excitation lower limit | 806 | U16 | 1 | |
| Energy-saving operating filter coefficient | 807 | U16 | 1 | |
| Torque control selection | 808 | U16 | 1 | |
| Torque command given | 809 | U16 | 1 | |
| Torque keyboard digital setting | 810 | U16 | 1 | |
| Torque input lower limit | 811 | U16 | 1 | |
| Lower limit corresponding setting | 812 | U16 | 1 | |
| Torque input upper limit | 813 | U16 | 1 | |
| Upper limit corresponding setting | 814 | U16 | 1 | |
| Torque filtering time | 815 | U16 | 1 | |
| Torque command upper limit | 820 | U16 | 1 | |
| Torque command lower limit | 821 | U16 | 1 | |
| Torque control forward speed limit selection | 822 | U16 | 1 | |
| Torque control reverse speed limit selection | 823 | U16 | 1 | |
| Torque control forward speed maximum speed limit | 824 | U16 | 1 | |
| Torque control anyway maximum speed limit | 825 | U16 | 1 | |
| Given torque gain switching frequency | 826 | U16 | 1 | |
| Given torque gain | 827 | U16 | 1 | |
| Linear VF curve selection | 1024 | U16 | 1 | |
| Torque boost | 1025 | U16 | 1 | |
| Torque boost cutoff frequency | 1026 | U16 | 1 | |
| Slip compensation gain | 1027 | U16 | 1 | |
| Slip compensation limit | 1028 | U16 | 1 | |
| Slip compensation filter time | 1029 | U16 | 1 | |
| Oscillation suppression gain | 1030 | U16 | 1 | |
| Oscillation suppression filter time | 1031 | U16 | 1 | |
| Output voltage percentage | 1032 | U16 | 1 | |
| Self-setting voltage V1 | 1034 | U16 | 1 | |
| Self-set frequency F1 | 1035 | U16 | 1 | |
| Self-setting voltage V2 | 1036 | U16 | 1 | |
| Self-set frequency F2 | 1037 | U16 | 1 | |
| Self-setting voltage V3 | 1038 | U16 | 1 | |
| Self-set frequency F3 | 1039 | U16 | 1 | |
| Self-setting voltage V4 | 1040 | U16 | 1 | |
| Self-set frequency F4 | 1041 | U16 | 1 | |
| Self-setting voltage V5 | 1042 | U16 | 1 | |
| Self-set frequency F5 | 1043 | U16 | 1 | |
| Automatic energy saving control | 1054 | U16 | 1 | |
| Energy saving step frequency lower limit | 1055 | U16 | 1 | |
| Energy-saving step-down voltage lower limit | 1056 | U16 | 1 | |
| Energy-saving step-down voltage regulation rate | 1057 | U16 | 1 | |
| Energy-saving voltage and voltage recovery rate | 1058 | U16 | 1 | |
| Terminal X1 function selection | 1280 | U16 | 1 | |
| Terminal X2 function selection | 1281 | U16 | 1 | |
| Terminal X3 function selection | 1282 | U16 | 1 | |
| Terminal X4 function selection | 1283 | U16 | 1 | |
| X1 effective detection delay | 1290 | U16 | 1 | |
| X1 invalid detection delay | 1291 | U16 | 1 | |
| X2 effective detection delay | 1292 | U16 | 1 | |
| X2 invalid detection delay | 1293 | U16 | 1 | |
| X3 effective detection delay | 1294 | U16 | 1 | |
| X3 invalid detection delay | 1295 | U16 | 1 | |
| X4 effective detection delay | 1296 | U16 | 1 | |
| X4 invalid detection delay | 1297 | U16 | 1 | |
| Terminal control mode | 1300 | U16 | 1 | |
| Terminal start protection | 1301 | U16 | 1 | |
| X1 ~ X4 terminal characteristics selection | 1302 | U16 | 1 | |
| Terminal UP/DW control selection | 1305 | U16 | 1 | |
| Terminal UP/DW controls frequency increase and decrease rate | 1306 | U16 | 1 | |
| Terminal emergency stop deceleration time | 1307 | U16 | 1 | |
| Reserved | 1310 | U16 | 1 | |
| PUL input minimum frequency | 1311 | U16 | 1 | |
| PUL minimum frequency corresponding setting | 1312 | U16 | 1 | |
| PUL input maximum frequency | 1313 | U16 | 1 | |
| PUL maximum frequency corresponding setting | 1314 | U16 | 1 | |
| PUL filter time | 1315 | U16 | 1 | |
| PUL cutoff frequency | 1316 | U16 | 1 | |
| AI input signal type selection method | 1320 | U16 | 1 | |
| Analog input curve selection | 1323 | U16 | 1 | |
| AI lower limit | 1330 | U16 | 1 | |
| AI lower limit corresponding setting | 1331 | U16 | 1 | |
| AI upper limit | 1332 | U16 | 1 | |
| AI upper limit corresponding setting | 1333 | U16 | 1 | |
| AI filter time | 1334 | U16 | 1 | |
| Curve 1 lower limit | 1340 | U16 | 1 | |
| Curve 1 lower limit corresponding setting | 1341 | U16 | 1 | |
| Curve 1 inflection point 1 input voltage | 1342 | U16 | 1 | |
| Curve 1 inflection point 1 corresponding setting | 1343 | U16 | 1 | |
| Curve 1 inflection point 2 input voltage | 1344 | U16 | 1 | |
| Curve 1 inflection point 2 corresponding setting | 1345 | U16 | 1 | |
| Curve 1 upper limit | 1346 | U16 | 1 | |
| Curve 1 upper limit corresponding setting | 1347 | U16 | 1 | |
| Curve 2 lower limit | 1350 | U16 | 1 | |
| Curve 2 lower limit corresponding setting | 1351 | U16 | 1 | |
| Curve 2 inflection point 1 input voltage | 1352 | U16 | 1 | |
| Curve 2 inflection point 1 corresponding setting | 1353 | U16 | 1 | |
| Curve 2 inflection point 2 input voltage | 1354 | U16 | 1 | |
| Curve 2 inflection point 2 corresponding setting | 1355 | U16 | 1 | |
| Curve 2 upper limit | 1356 | U16 | 1 | |
| Curve 2 upper limit corresponding setting | 1357 | U16 | 1 | |
| AI port to do digital input terminal feature selection | 1360 | U16 | 1 | |
| AI terminal function selection (as X) | 1361 | U16 | 1 | |
| AI high level setting | 1362 | U16 | 1 | |
| AI low level setting | 1363 | U16 | 1 | |
| AO output mode selection | 1536 | U16 | 1 | |
| AO output selection | 1537 | U16 | 1 | |
| AO output gain | 1538 | U16 | 1 | |
| AO output bias | 1539 | U16 | 1 | |
| AO output filtering | 1540 | U16 | 1 | |
| Output terminal polarity selection | 1556 | U16 | 1 | |
| Output terminal Y | 1557 | U16 | 1 | |
| Relay 1 output (TA-TB-TC) | 1558 | U16 | 1 | |
| Y output ON delay time | 1561 | U16 | 1 | |
| Relay 1 output ON delay time | 1562 | U16 | 1 | |
| Y output OFF delay time | 1565 | U16 | 1 | |
| Relay 1 output OFF delay time | 1566 | U16 | 1 | |
| Frequency detection value 1 | 1576 | U16 | 1 | |
| Frequency detection amplitude 1 | 1577 | U16 | 1 | |
| Frequency detection value 2 | 1578 | U16 | 1 | |
| Frequency detection range 2 | 1579 | U16 | 1 | |
| The given frequency reaches the detection range | 1580 | U16 | 1 | |
| Comparator 1 monitor selection | 1586 | U16 | 1 | |
| Comparator 1 upper limit | 1587 | U16 | 1 | |
| Comparator 1 lower limit | 1588 | U16 | 1 | |
| Comparator 1 bias | 1589 | U16 | 1 | |
| Action selection when sending CP1 | 1590 | U16 | 1 | |
| Comparator 2 monitor selection | 1591 | U16 | 1 | |
| Comparator 2 upper limit | 1592 | U16 | 1 | |
| Comparator 2 lower limit | 1593 | U16 | 1 | |
| Comparator 2 bias | 1594 | U16 | 1 | |
| Action selection when sending CP2 | 1595 | U16 | 1 | |
| Virtual vX1 terminal function selection | 1596 | U16 | 1 | |
| Virtual vX2 terminal function selection | 1597 | U16 | 1 | |
| Virtual vX3 terminal function selection | 1598 | U16 | 1 | |
| Virtual vX4 terminal function selection | 1599 | U16 | 1 | |
| vX terminal valid status source | 1600 | U16 | 1 | |
| Virtual vX terminal function code setting valid status | 1601 | U16 | 1 | |
| Virtual vY1 output selection | 1602 | U16 | 1 | |
| Virtual vY2 output selection | 1603 | U16 | 1 | |
| Virtual vY3 output selection | 1604 | U16 | 1 | |
| Virtual vY4 output selection | 1605 | U16 | 1 | |
| vY1 output ON delay time | 1606 | U16 | 1 | |
| vY2 output ON delay time | 1607 | U16 | 1 | |
| vY3 output ON delay time | 1608 | U16 | 1 | |
| vY4 output ON delay time | 1609 | U16 | 1 | |
| vY1 output OFF delay time | 1610 | U16 | 1 | |
| vY2 output OFF delay time | 1611 | U16 | 1 | |
| vY3 output OFF delay time | 1612 | U16 | 1 | |
| vY4 output OFF delay time | 1613 | U16 | 1 | |
| Start mode | 1792 | U16 | 1 | |
| Start pre-excitation time | 1793 | U16 | 1 | |
| Starting frequency | 1794 | U16 | 1 | |
| Start protection selection | 1795 | U16 | 1 | |
| Direction of rotation | 1797 | U16 | 1 | |
| Power failure restart action selection | 1798 | U16 | 1 | |
| Power failure restart waiting time | 1799 | U16 | 1 | |
| Stop mode | 1802 | U16 | 1 | |
| Shutdown detection frequency | 1803 | U16 | 1 | |
| Stop and restart limit time | 1804 | U16 | 1 | |
| Insufficient lower limit frequency action selection | 1807 | U16 | 1 | |
| Zero speed torque retention factor | 1808 | U16 | 1 | |
| Zero speed torque holding time | 1809 | U16 | 1 | |
| Positive reversal dead time | 1810 | U16 | 1 | |
| Braking current before starting | 1812 | U16 | 1 | |
| Braking time before starting | 1813 | U16 | 1 | |
| DC braking start frequency | 1814 | U16 | 1 | |
| DC braking current | 1815 | U16 | 1 | |
| DC braking time during shutdown | 1816 | U16 | 1 | |
| Speed tracking mode | 1817 | U16 | 1 | |
| Speed tracking speed | 1818 | U16 | 1 | |
| Speed tracking stop delay | 1819 | U16 | 1 | |
| Speed tracking current | 1820 | U16 | 1 | |
| Jog running frequency setting | 1822 | U16 | 1 | |
| Jog acceleration time | 1823 | U16 | 1 | |
| Jog deceleration time | 1824 | U16 | 1 | |
| Jog S curve selection | 1825 | U16 | 1 | |
| Jog stop mode selection | 1826 | U16 | 1 | |
| Maintain frequency at startup | 1832 | U16 | 1 | |
| Maintain frequency time at startup | 1833 | U16 | 1 | |
| Maintain frequency during shutdown | 1834 | U16 | 1 | |
| Maintain frequency time during shutdown | 1835 | U16 | 1 | |
| Jump frequency 1 | 1836 | U16 | 1 | |
| Jump frequency amplitude | 1837 | U16 | 1 | |
| Jump frequency 2 | 1838 | U16 | 1 | |
| Jump frequency amplitude | 1839 | U16 | 1 | |
| Counter input source | 2048 | U16 | 1 | |
| Count input crossover | 2049 | U16 | 1 | |
| Counter maximum | 2050 | U16 | 1 | |
| Counter setting | 2051 | U16 | 1 | |
| Pulse number per meter | 2052 | U16 | 1 | |
| Set length | 2053 | U16 | 1 | |
| Actual length | 2054 | U16 | 1 | |
| Timer time unit | 2055 | U16 | 1 | |
| Timer setting | 2056 | U16 | 1 | |
| Swing frequency control | 2078 | U16 | 1 | |
| Swing frequency amplitude control | 2079 | U16 | 1 | |
| Swing frequency preset frequency | 2080 | U16 | 1 | |
| Swing frequency preset frequency waiting time | 2081 | U16 | 1 | |
| Swing frequency amplitude | 2082 | U16 | 1 | |
| Kick frequency | 2083 | U16 | 1 | |
| Triangle wave rise time | 2084 | U16 | 1 | |
| Triangle wave fall time | 2085 | U16 | 1 | |
| Overcurrent suppression | 2560 | U16 | 1 | |
| Overcurrent suppression point | 2561 | U16 | 1 | |
| Overcurrent suppression gain | 2562 | U16 | 1 | |
| Current protection setting 1 | 2563 | U16 | 1 | |
| Current protection setting 2 | 2564 | U16 | 1 | |
| Operation Pause Delay | 2570 | U16 | 1 | |
| Bus overvoltage suppression | 2571 | U16 | 1 | |
| Bus overvoltage suppression point | 2572 | U16 | 1 | |
| Bus overvoltage suppression gain | 2573 | U16 | 1 | |
| Energy brake enable | 2574 | U16 | 1 | |
| Energy consumption braking action voltage | 2575 | U16 | 1 | |
| Bus undervoltage suppression | 2576 | U16 | 1 | |
| Bus undervoltage suppression point | 2577 | U16 | 1 | |
| Bus undervoltage suppression gain | 2578 | U16 | 1 | |
| Bus undervoltage protection point | 2579 | U16 | 1 | |
| Input and output phase loss protection options | 2580 | U16 | 1 | |
| Input phase loss threshold | 2581 | U16 | 1 | |
| Ground short circuit protection option | 2582 | U16 | 1 | |
| Fan ON/OFF control selection | 2583 | U16 | 1 | |
| Fan control delay time | 2584 | U16 | 1 | |
| AC Drive overheating oH1 detection level | 2585 | U16 | 1 | |
| Motor overload protection curve coefficient | 2590 | U16 | 1 | |
| Selection of AC Drive overload characteristics at low speed | 2591 | U16 | 1 | |
| Load warning checkout setting | 2592 | U16 | 1 | |
| Load warning detection level 1 | 2593 | U16 | 1 | |
| Load warning detection time 1 | 2594 | U16 | 1 | |
| Load warning detection level 2 | 2595 | U16 | 1 | |
| Load warning detection time 2 | 2596 | U16 | 1 | |
| Too large peed deviation protection action | 2600 | U16 | 1 | |
| Speed deviation excessive detection threshold | 2601 | U16 | 1 | |
| Speed deviation too large detection time | 2602 | U16 | 1 | |
| Speed protection action | 2603 | U16 | 1 | |
| Rapid detection threshold | 2604 | U16 | 1 | |
| Rapid speed detection time | 2605 | U16 | 1 | |
| Failure self-recovery | 2610 | U16 | 1 | |
| Failure self-recovery interval | 2611 | U16 | 1 | |
| Numbers of failures recovered | 2612 | U16 | 1 | |
| Key lock selection | 2816 | U16 | 1 | |
| Key lock password | 2817 | U16 | 1 | |
| Keyboard multi-function key selection | 2818 | U16 | 1 | |
| Keyboard STOP button settings | 2819 | U16 | 1 | |
| Status interface up and down keys (knob) function selection | 2820 | U16 | 1 | |
| Up and down keys to quickly change the parameter code settin | 2821 | U16 | 1 | |
| Keyboard command key selection | 2822 | U16 | 1 | |
| Status interface left shift, right shift key function select | 2826 | U16 | 1 | |
| Parameter 1 showed up on first line of the keyboard | 2827 | U16 | 1 | |
| Parameter 2 showed up on first line of the keyboard | 2828 | U16 | 1 | |
| Parameter 3 showed up on first line of the keyboard | 2829 | U16 | 1 | |
| Parameter 4 showed up on first line of the keyboard | 2830 | U16 | 1 | |
| Parameter 1 showed up on second line of the keyboard | 2831 | U16 | 1 | |
| Parameter 2 showed up on second line of the keyboard | 2832 | U16 | 1 | |
| Parameter 3 showed up on second line of the keyboard | 2833 | U16 | 1 | |
| Parameter 4 showed up on second line of the keyboard | 2834 | U16 | 1 | |
| Keyboard display item settings | 2836 | U16 | 1 | |
| Speed display factor | 2837 | U16 | 1 | |
| Power display factor | 2838 | U16 | 1 | |
| Monitoring parameter group display selection | 2839 | U16 | 1 | |
| Reserved | 2840 | U16 | 1 | |
| Display selection when the motor is self-tuning | 2841 | U16 | 1 | |
| AC10 serial port function selection | 2846 | U16 | 1 | |
| Keyboard potentiometer lower limit voltage | 2847 | U16 | 1 | |
| Keyboard potentiometer lower limit corresponding value | 2848 | U16 | 1 | |
| Keyboard potentiometer upper limit voltage | 2849 | U16 | 1 | |
| Keyboard potentiometer upper limit corresponding value | 2850 | U16 | 1 | |
| External keyboard potentiometer control | 2851 | U16 | 1 | |
| Master-slave choice | 3072 | U16 | 1 | |
| Modbus communication address | 3073 | U16 | 1 | |
| Communication baud rate selection | 3074 | U16 | 1 | |
| Modbus data format | 3075 | U16 | 1 | |
| Modbus transmission response processing | 3076 | U16 | 1 | |
| Modbus communication response delay | 3077 | U16 | 1 | |
| Modbus communication timeout failure time | 3078 | U16 | 1 | |
| Communication disconnection processing | 3079 | U16 | 1 | |
| Receive data (address 0x3000) zero bias | 3080 | U16 | 1 | |
| Receive data (address 0x3000) gain | 3081 | U16 | 1 | |
| Host cyclically send parameter selection | 3082 | U16 | 1 | |
| Frequency given custom address setting | 3083 | U16 | 1 | |
| Command given custom address settings | 3084 | U16 | 1 | |
| Command given as forward run command value | 3085 | U16 | 1 | |
| Command given as reverse run command value | 3086 | U16 | 1 | |
| Command given as stop command value | 3087 | U16 | 1 | |
| Command given as reset command value | 3088 | U16 | 1 | |
| PID controller given signal source | 3328 | U16 | 1 | |
| Keyboard digital PID given / feedback | 3329 | U16 | 1 | |
| PID given change time | 3330 | U16 | 1 | |
| PID controller feedback signal source | 3331 | U16 | 1 | |
| Feedback signal low pass filtering time | 3332 | U16 | 1 | |
| Feedback signal gain | 3333 | U16 | 1 | |
| Feedback signal range | 3334 | U16 | 1 | |
| PID control selection | 3335 | U16 | 1 | |
| PID preset output | 3336 | U16 | 1 | |
| PID preset output running time | 3337 | U16 | 1 | |
| PID control deviation limit | 3338 | U16 | 1 | |
| Proportional gain P1 | 3339 | U16 | 1 | |
| Integration time I1 | 3340 | U16 | 1 | |
| Differential gain D1 | 3341 | U16 | 1 | |
| Proportional gain P2 | 3342 | U16 | 1 | |
| Integration time I2 | 3343 | U16 | 1 | |
| Differential gain D2 | 3344 | U16 | 1 | |
| PID parameter switching condition | 3345 | U16 | 1 | |
| Switching deviation low value | 3346 | U16 | 1 | |
| Switching deviation high value | 3347 | U16 | 1 | |
| Reserved | 3348 | U16 | 1 | |
| Differential limiting | 3349 | U16 | 1 | |
| PID output upper limit | 3350 | U16 | 1 | |
| PID output lower limit | 3351 | U16 | 1 | |
| PID output filtering time | 3352 | U16 | 1 | |
| Feedback disconnection action selection | 3353 | U16 | 1 | |
| Feedback disconnection detection time | 3354 | U16 | 1 | |
| Wire break alarm upper limit | 3355 | U16 | 1 | |
| Wire break alarm lower limit | 3356 | U16 | 1 | |
| Sleep selection | 3357 | U16 | 1 | |
| Sleep frequency | 3358 | U16 | 1 | |
| Sleep delay | 3359 | U16 | 1 | |
| Wake up deviation | 3360 | U16 | 1 | |
| Wake-up delay | 3361 | U16 | 1 | |
| PLC multi-speed 1 | 3584 | U16 | 1 | |
| PLC multi-speed 2 | 3585 | U16 | 1 | |
| PLC multi-speed 3 | 3586 | U16 | 1 | |
| PLC multi-speed 4 | 3587 | U16 | 1 | |
| PLC multi-speed 5 | 3588 | U16 | 1 | |
| PLC multi-speed 6 | 3589 | U16 | 1 | |
| PLC multi-speed 7 | 3590 | U16 | 1 | |
| PLC multi-speed 8 | 3591 | U16 | 1 | |
| PLC multi-speed 9 | 3592 | U16 | 1 | |
| PLC multi-speed 10 | 3593 | U16 | 1 | |
| PLC multi-speed 11 | 3594 | U16 | 1 | |
| PLC multi-speed 12 | 3595 | U16 | 1 | |
| PLC multi-speed 13 | 3596 | U16 | 1 | |
| PLC multi-speed 14 | 3597 | U16 | 1 | |
| PLC multi-speed 15 | 3598 | U16 | 1 | |
| PLC operation mode selection | 3599 | U16 | 1 | |
| PLC first stage running time | 3600 | U16 | 1 | |
| PLC second stage running time | 3601 | U16 | 1 | |
| PLC third stage running time | 3602 | U16 | 1 | |
| PLC fourth stage running time | 3603 | U16 | 1 | |
| PLC fifth stage running time | 3604 | U16 | 1 | |
| PLC sixth stage running time | 3605 | U16 | 1 | |
| PLC seventh stage running time | 3606 | U16 | 1 | |
| PLC eighth stage running time | 3607 | U16 | 1 | |
| PLC ninth stage running time | 3608 | U16 | 1 | |
| PLC tenth stage running time | 3609 | U16 | 1 | |
| PLC eleventh stage running time | 3610 | U16 | 1 | |
| PLC twelveth stage running time | 3611 | U16 | 1 | |
| PLC thirteenth stage running time | 3612 | U16 | 1 | |
| PLC fourteenth stage running time | 3613 | U16 | 1 | |
| PLC fifteenth stage running time | 3614 | U16 | 1 | |
| PLC first direction and acceleration and deceleration time | 3615 | U16 | 1 | |
| PLC second direction and acceleration and deceleration time | 3616 | U16 | 1 | |
| PLC third direction and acceleration and deceleration time | 3617 | U16 | 1 | |
| PLC fourth direction and acceleration and deceleration time | 3618 | U16 | 1 | |
| PLC fifth direction and acceleration and deceleration time | 3619 | U16 | 1 | |
| PLC sixth direction and acceleration and deceleration time | 3620 | U16 | 1 | |
| PLC seventh direction and acceleration and deceleration time | 3621 | U16 | 1 | |
| PLC eighth direction and acceleration and deceleration time | 3622 | U16 | 1 | |
| PLC ninth direction and acceleration and deceleration time | 3623 | U16 | 1 | |
| PLC tenth direction and acceleration and deceleration time | 3624 | U16 | 1 | |
| PLC eleventh direction and acceleration and deceleration tim | 3625 | U16 | 1 | |
| PLC twelveth direction and acceleration and deceleration tim | 3626 | U16 | 1 | |
| PLC thirteenth direction and acceleration and deceleration t | 3627 | U16 | 1 | |
| PLC fourteenth direction and acceleration and deceleration t | 3628 | U16 | 1 | |
| PLC fifteenth direction and acceleration and deceleration ti | 3629 | U16 | 1 | |
| Given frequency | 8448 | U16 | 1 | |
| Output frequency | 8449 | U16 | 1 | |
| Output current | 8450 | U16 | 1 | |
| Input voltage | 8451 | U16 | 1 | V |
| The output voltage | 8452 | U16 | 1 | V |
| Mechanical speed | 8453 | I16 | 1 | |
| Given torque | 8454 | I16 | 1 | % |
| Output torque | 8455 | I16 | 1 | % |
| PID given | 8456 | U16 | 1 | % |
| PID feedback | 8457 | U16 | 1 | % |
| Output Power | 8458 | U16 | 1 | |
| bus voltage | 8459 | U16 | 1 | V |
| Module temperature 1 | 8460 | I16 | 1 | °C |
| Module temperature 2 | 8461 | I16 | 1 | °C |
| Input terminal X is on | 8462 | U16 | 1 | |
| Output terminal Y is on | 8463 | U16 | 1 | |
| Analog AI input value | 8464 | U16 | 1 | V |
| Reserved | 8465 | U16 | 1 | |
| Keyboard potentiometer input value | 8466 | U16 | 1 | |
| Pulse signal PUL input value | 8467 | U16 | 1 | |
| Analog output AO | 8468 | U16 | 1 | |
| Reserved | 8469 | U16 | 1 | |
| Counter count value | 8470 | U16 | 1 | |
| Power-on running time | 8471 | U16 | 1 | |
| Accumulated running time of the machine | 8472 | U16 | 1 | |
| AC Drive power level | 8473 | U16 | 1 | |
| AC Drive rated voltage | 8474 | U16 | 1 | |
| AC Drive rated current | 8475 | U16 | 1 | |
| Software version | 8476 | U16 | 1 | |
| PG feedback frequency | 8477 | U16 | 1 | |
| Timer timing | 8478 | U16 | 1 | |
| PID output value | 8479 | U16 | 1 | |
| AC Drive software subversion | 8480 | U16 | 1 | |
| Encoder feedback angle | 8481 | U16 | 1 | |
| Z pulse cumulative error | 8482 | U16 | 1 | |
| Z pulse count | 8483 | U16 | 1 | |
| Failure warning code | 8484 | U16 | 1 | |
| Cumulative power consumption (low level) | 8485 | U16 | 1 | |
| Cumulative power consumption (high) | 8486 | U16 | 1 | |
| Power factor angle | 8487 | U16 | 1 | |
| Fault type diagnostic information | 8704 | U16 | 1 | |
| Troubleshooting information | 8705 | U16 | 1 | |
| Fault operating frequency | 8706 | U16 | 1 | |
| Fault output voltage | 8707 | U16 | 1 | |
| Fault output current | 8708 | U16 | 1 | |
| Fault bus voltage | 8709 | U16 | 1 | |
| Faulty module temperature | 8710 | U16 | 1 | |
| Faulty AC Drive status | 8711 | U16 | 1 | |
| Fault input terminal status | 8712 | U16 | 1 | |
| Fault output terminal status | 8713 | U16 | 1 | |
| Previous failure type | 8714 | U16 | 1 | |
| Previous troubleshooting information | 8715 | U16 | 1 | |
| The first fault operation frequency | 8716 | U16 | 1 | |
| Last fault output voltage | 8717 | U16 | 1 | |
| Last fault output current | 8718 | U16 | 1 | |
| The first fault bus voltage | 8719 | U16 | 1 | |
| The first fault module temperature | 8720 | U16 | 1 | |
| The first faulty AC Drive status | 8721 | U16 | 1 | |
| The first fault input terminal status | 8722 | U16 | 1 | |
| The first fault output terminal status | 8723 | U16 | 1 | |
| First 2 fault types | 8724 | U16 | 1 | |
| The first 2 troubleshooting information | 8725 | U16 | 1 | |
| Top 3 fault types | 8726 | U16 | 1 | |
| The first 3 troubleshooting information | 8727 | U16 | 1 | |
| Communication Given Frequency | 12288 | U16 | 0.01 | Hz |
| Communication Command Setting | 12289 | U16 | 1 | |
| State of AC Drive | 12290 | U16 | 1 | |
| AC Drive Fault Code | 12291 | U16 | 1 | |
| Communication Given Upper Frequency | 12292 | U16 | 0.01 | Hz |
| Communication Torque Setting | 12293 | U16 | 0.1 | % |
| The FWD Max Frequency limit in Torque Control | 12294 | U16 | 0.1 | % |
| The REV Max Frequency limit in Torque Control | 12295 | U16 | 0.1 | % |
| Communication Given PID Setting | 12296 | U16 | 0.1 | % |
| Communication Given PID Feedback | 12297 | U16 | 0.1 | % |
| Fault and warning code reading | 12304 | U16 | 1 | |
| Output terminal state | 12312 | U16 | 1 | |
| AO output | 12313 | U16 | 1 |
| terminals | A+, B- |
| termination | 120Ω termination resistor selectable via switch S3 |
| wiring notes | RS485 differential communication |
| response timeout | 1000 ms |
| inter-frame delay | 0 ms |
| protocol notes | Interval over 1.5 byte before ending clears half-baked info. Interval under 3.5 byte time is considered continuation of former frame. Writing to 0x00XX writes to RAM, writing to 0x10XX writes to EEPROM. |
| power | S2: Single-phase 220V, T2: Three-phase 220V, T3: Three-phase 380V |
| environment | -10 ~ +50°C (derating above 40°C, max 60°C), 5% to 95% RH (no condensation), altitude < 1000m, vibration 5.9 m/s2 (0.6 g) |
| certifications | IEC61800-2 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.