Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Parameter access level | 0 | U16 | 1 | |
| Use selection | 1 | U16 | 1 | |
| Reserved | 2 | U16 | 1 | |
| Initialization | 3 | U16 | 1 | |
| Keyboard parameter copy | 4 | U16 | 1 | |
| Reserved | 5 | U16 | 1 | |
| Reserved | 6 | U16 | 1 | |
| Free parameter 1 | 7 | U16 | 1 | |
| Free parameter 2 | 8 | U16 | 1 | |
| Common parameter address setting | 10 | U16 | 1 | |
| Motor control mode | 256 | U16 | 1 | |
| Run command channel | 257 | U16 | 1 | |
| Frequency given source channel A | 258 | U16 | 1 | |
| Gain of frequency given source channel A | 259 | U16 | 1 | |
| Frequency given source channel B | 260 | U16 | 1 | |
| Gain of frequency given source channel B | 261 | U16 | 1 | |
| Frequency channel B reference source | 262 | U16 | 1 | |
| Frequency given source selection | 263 | U16 | 1 | |
| Frequency given with run command binding | 264 | U16 | 1 | |
| Keyboard digital given frequency | 265 | U16 | 1 | |
| Maximum frequency | 266 | U16 | 1 | |
| Upper frequency limit source selection | 267 | U16 | 1 | |
| Upper frequency limit digital setting | 268 | U16 | 1 | |
| Lower frequency limit | 269 | U16 | 1 | |
| Frequency command resolution | 270 | U16 | 1 | |
| Reference frequency for acceleration/deceleration time | 276 | U16 | 1 | |
| Unit of acceleration/deceleration time | 277 | U16 | 1 | |
| Acceleration time 1 | 278 | U16 | 1 | |
| Deceleration time 1 | 279 | U16 | 1 | |
| Acceleration time 2 | 280 | U16 | 1 | |
| Deceleration time 2 | 281 | U16 | 1 | |
| Acceleration time 3 | 282 | U16 | 1 | |
| Deceleration time 3 | 283 | U16 | 1 | |
| Acceleration time 4 | 284 | U16 | 1 | |
| Deceleration time 4 | 285 | U16 | 1 | |
| S-curve acceleration/deceleration selection | 286 | U16 | 1 | |
| S-curve acceleration start time | 287 | U16 | 1 | |
| S-curve acceleration end time | 288 | U16 | 1 | |
| S-curve deceleration start time | 289 | U16 | 1 | |
| S-curve deceleration end time | 290 | U16 | 1 | |
| Frequency of switching between acceleration time 1 and accel | 291 | U16 | 1 | |
| Carrier frequency | 296 | U16 | 1 | |
| PWM control mode | 297 | U16 | 1 | |
| Dead-time compensation gain | 299 | U16 | 1 | |
| PWM random depth | 302 | U16 | 1 | |
| Motor type | 512 | U16 | 1 | |
| Number of motor poles | 513 | U16 | 1 | |
| Rated motor power | 514 | U16 | 1 | |
| Rated motor frequency | 515 | U16 | 1 | |
| Rated motor speed | 516 | U16 | 1 | |
| Rated motor voltage | 517 | U16 | 1 | |
| Rated motor current | 518 | U16 | 1 | |
| Selection of motor parameter auto-tuning | 519 | U16 | 1 | |
| No-load current of asynchronous motor | 522 | U16 | 1 | |
| Stator resistance of asynchronous motor | 523 | U16 | 1 | |
| Rotor resistance of asynchronous motor | 524 | U16 | 1 | |
| Stator leakage inductance of asynchronous motor | 525 | U16 | 1 | |
| Stator inductance of asynchronous motor | 526 | U16 | 1 | |
| Stator resistance per-unit value | 527 | U16 | 1 | |
| Rotor resistance per-unit value | 528 | U16 | 1 | |
| Stator leakage inductance per-unit value | 529 | U16 | 1 | |
| Stator inductance per-unit value | 530 | U16 | 1 | |
| Decimal place selection for F02.11 - F02.14 | 531 | U16 | 1 | |
| Stator resistance of synchronous motor | 532 | U16 | 1 | |
| d-axis inductance of synchronous motor | 533 | U16 | 1 | |
| q-axis inductance of synchronous motor | 534 | U16 | 1 | |
| Back-EMF of synchronous motor | 535 | U16 | 1 | |
| Mounting angle of synchronous motor encoder | 536 | U16 | 1 | |
| Stator resistance per-unit value of synchronous motor | 537 | U16 | 1 | |
| d-axis inductance per-unit value of synchronous motor | 538 | U16 | 1 | |
| q-axis inductance per-unit value of synchronous motor | 539 | U16 | 1 | |
| Pulse width coefficient of synchronous motor | 540 | U16 | 1 | |
| Decimal place selection for F02.20 - F02.22 | 541 | U16 | 1 | |
| Types of speed feedback encoder | 542 | U16 | 1 | |
| Encoder direction | 543 | U16 | 1 | |
| ABZ encoder Z pulse detection selection | 544 | U16 | 1 | |
| Number of ABZ encoder pulse | 545 | U16 | 1 | |
| Number of resolver poles | 546 | U16 | 1 | |
| Encoder transmission ratio numerator | 547 | U16 | 1 | |
| Encoder transmission ratio denominator | 548 | U16 | 1 | |
| Encoder speed measurement filter time | 549 | U16 | 1 | |
| Encoder disconnection detection time | 550 | U16 | 1 | |
| Allowable deviation of Z pulse | 559 | U16 | 1 | |
| Tuning current value of Z pulse | 560 | U16 | 1 | |
| Encoder debug register | 561 | U16 | 1 | |
| Stator resistance start tuning function selection | 562 | U16 | 1 | |
| Stator resistance start tuning coefficient 1 | 563 | U16 | 1 | |
| Stator resistance start tuning coefficient 2 | 564 | U16 | 1 | |
| Stator resistance start tuning coefficient 3 | 565 | U16 | 1 | |
| Magnetic pole search of synchronous motor | 572 | U16 | 1 | |
| Pole search current set point | 573 | U16 | 1 | |
| ASR speed rigidity class | 768 | U16 | 1 | |
| ASR speed rigidity mode | 769 | U16 | 1 | |
| ASR (speed loop) proportional gain 1 | 770 | U16 | 1 | |
| ASR (speed loop) integral time 1 | 771 | U16 | 1 | |
| ASR filter time 1 | 772 | U16 | 1 | |
| ASR switching frequency 1 | 773 | U16 | 1 | |
| ASR (speed loop) proportional gain 2 | 774 | U16 | 1 | |
| ASR (speed loop) integral time 2 | 775 | U16 | 1 | |
| ASR filter time 2 | 776 | U16 | 1 | |
| ASR switching frequency 2 | 777 | U16 | 1 | |
| Current loop D-axis proportional gain | 778 | U16 | 1 | |
| Current loop D-axis integral gain | 779 | U16 | 1 | |
| Current loop Q-axis proportional gain | 780 | U16 | 1 | |
| Current loop Q-axis integral gain | 781 | U16 | 1 | |
| Reserved | 782 | U16 | 1 | |
| Torque limit in drive state | 783 | U16 | 1 | |
| Torque limit in power generation state | 784 | U16 | 1 | |
| Regenerative torque limit at low speed | 785 | U16 | 1 | |
| Frequency amplitude for torque limit action at low speed | 786 | U16 | 1 | |
| Torque limit selection | 787 | U16 | 1 | |
| Low frequency pull-in current of synchronous motor | 788 | U16 | 1 | |
| High frequency pull-in current of synchronous motor | 789 | U16 | 1 | |
| Pull-in current frequency of synchronous motor | 790 | U16 | 1 | |
| Slip compensation | 791 | U16 | 1 | |
| Initial value of starting torque | 792 | U16 | 1 | |
| Flux weakening feedforward coefficient | 798 | U16 | 1 | |
| Flux weakening control gain | 799 | U16 | 1 | |
| Flux weakening current upper limit | 800 | U16 | 1 | |
| Flux weakening voltage coefficient | 801 | U16 | 1 | |
| Shaft output power limit | 802 | U16 | 1 | |
| Over-excitation brake gain | 803 | U16 | 1 | |
| Over-excitation brake limit | 804 | U16 | 1 | |
| Energy-saving running | 805 | U16 | 1 | |
| Lower excitation limit in energy-saving running | 806 | U16 | 1 | |
| Filter coefficient of energy-saving running | 807 | U16 | 1 | |
| Torque control selection | 808 | U16 | 1 | |
| Torque command setting | 809 | U16 | 1 | |
| Torque given by keyboard digital | 810 | U16 | 1 | |
| Torque input lower limit | 811 | U16 | 1 | |
| Corresponding setting of lower torque limit | 812 | U16 | 1 | |
| Torque input upper limit | 813 | U16 | 1 | |
| Upper torque limit setting | 814 | U16 | 1 | |
| Torque filter time | 815 | U16 | 1 | |
| Speed limit selection | 816 | U16 | 1 | |
| Torque command upper limit | 820 | U16 | 1 | |
| Torque command lower limit | 821 | U16 | 1 | |
| Selection of torque control forward speed limit | 822 | U16 | 1 | |
| Selection of torque control reverse speed limit | 823 | U16 | 1 | |
| Forward speed limit number/gain setting | 824 | U16 | 1 | |
| Reverse speed limit number/gain setting | 825 | U16 | 1 | |
| Torque gain switching frequency setting | 826 | U16 | 1 | |
| Torque gain setting | 827 | U16 | 1 | |
| High-frequency injection selection | 828 | U16 | 1 | |
| High-frequency injection voltage | 829 | U16 | 1 | |
| High-frequency injection cutoff frequency | 830 | U16 | 1 | |
| Position compensation control | 838 | U16 | 1 | |
| Compensation gain | 839 | U16 | 1 | |
| Compensation range limiting | 840 | U16 | 1 | |
| Compensation range | 841 | U16 | 1 | |
| MTPA gain of synchronous motor | 848 | U16 | 1 | |
| MTPA filter time of synchronous motor | 849 | U16 | 1 | |
| Linear V/F curve selection | 1024 | U16 | 1 | |
| Torque boost | 1025 | U16 | 1 | |
| Torque boost cutoff frequency | 1026 | U16 | 1 | |
| Slip compensation gain | 1027 | U16 | 1 | |
| Slip compensation range limiting | 1028 | U16 | 1 | |
| Slip compensation filter time | 1029 | U16 | 1 | |
| Oscillation suppression gain | 1030 | U16 | 1 | |
| Oscillation suppression filter time | 1031 | U16 | 1 | |
| Output voltage percentage | 1032 | U16 | 1 | |
| Self-setting voltage 1 | 1034 | U16 | 1 | |
| Self-setting frequency 1 | 1035 | U16 | 1 | |
| Self-setting voltage 2 | 1036 | U16 | 1 | |
| Self-setting frequency 2 | 1037 | U16 | 1 | |
| Self-setting voltage 3 | 1038 | U16 | 1 | |
| Self-setting frequency 3 | 1039 | U16 | 1 | |
| Self-setting voltage 4 | 1040 | U16 | 1 | |
| Self-setting frequency 4 | 1041 | U16 | 1 | |
| Self-setting voltage 5 | 1042 | U16 | 1 | |
| Self-setting frequency 5 | 1043 | U16 | 1 | |
| V/F separation voltage setting | 1044 | U16 | 1 | |
| V/F separation output voltage number setting | 1045 | U16 | 1 | |
| V/F separation voltage acceleration time | 1046 | U16 | 1 | |
| V/F separation voltage deceleration time | 1047 | U16 | 1 | |
| V/F separation stop mode | 1048 | U16 | 1 | |
| V/F separation voltage digital setting | 1049 | U16 | 1 | |
| Automatic energy-saving control | 1054 | U16 | 1 | |
| Frequency lower limit of the energy-saving voltage drop | 1055 | U16 | 1 | |
| Voltage lower limit of the energy-saving voltage drop | 1056 | U16 | 1 | |
| Voltage regulation rate of the energy-saving voltage drop | 1057 | U16 | 1 | |
| Energy-saving voltage recovery rate | 1058 | U16 | 1 | |
| Over-excitation coefficient | 1059 | U16 | 1 | |
| Function selection of terminal X1 | 1280 | U16 | 1 | |
| Function selection of terminal X2 | 1281 | U16 | 1 | |
| Function selection of terminal X3 | 1282 | U16 | 1 | |
| Function selection of terminal X4 | 1283 | U16 | 1 | |
| Function selection of terminal X5 | 1284 | U16 | 1 | |
| Function selection of terminal X6 | 1285 | U16 | 1 | |
| Function selection of terminal X7 | 1286 | U16 | 1 | |
| Function selection of terminal X8 | 1287 | U16 | 1 | |
| Function selection of terminal X9 | 1288 | U16 | 1 | |
| Function selection of terminal X10 | 1289 | U16 | 1 | |
| X1 activation detection delay | 1290 | U16 | 1 | |
| X1 deactivation detection delay | 1291 | U16 | 1 | |
| X2 activation detection delay | 1292 | U16 | 1 | |
| X2 deactivation detection delay | 1293 | U16 | 1 | |
| X3 activation detection delay | 1294 | U16 | 1 | |
| X3 deactivation detection delay | 1295 | U16 | 1 | |
| X4 activation detection delay | 1296 | U16 | 1 | |
| X4 deactivation detection delay | 1297 | U16 | 1 | |
| X5 activation detection delay | 1298 | U16 | 1 | |
| X5 deactivation detection delay | 1299 | U16 | 1 | |
| Terminal control running mode | 1300 | U16 | 1 | |
| Terminal X1-X4 characteristic selection | 1302 | U16 | 1 | |
| Terminal X5-X8 characteristic selection | 1303 | U16 | 1 | |
| Terminal X9-X10 characteristic selection | 1304 | U16 | 1 | |
| Terminal's frequency adjustment mode | 1305 | U16 | 1 | |
| Acceleration/deceleration rate of the terminal UP/DW control | 1306 | U16 | 1 | |
| Deceleration time of emergency stop by terminal | 1307 | U16 | 1 | |
| PUL port signal source | 1310 | U16 | 1 | |
| Minimum frequency of PUL input | 1311 | U16 | 1 | |
| PUL minimum frequency corresponding setting | 1312 | U16 | 1 | |
| Maximum frequency of PUL input | 1313 | U16 | 1 | |
| PUL maximum frequency corresponding setting | 1314 | U16 | 1 | |
| PUL filter time | 1315 | U16 | 1 | |
| PUL cutoff frequency | 1316 | U16 | 1 | |
| AI1 input signal type | 1321 | U16 | 1 | |
| AI2 input signal type | 1322 | U16 | 1 | |
| Analog value input curve selection | 1323 | U16 | 1 | |
| AI1 lower limit | 1330 | U16 | 1 | |
| AI1 lower limit corresponding setting | 1331 | U16 | 1 | |
| AI1 upper limit | 1332 | U16 | 1 | |
| AI1 upper limit corresponding setting | 1333 | U16 | 1 | |
| AI1 filter time | 1334 | U16 | 1 | |
| AI2 lower limit | 1335 | U16 | 1 | |
| AI2 lower limit corresponding setting | 1336 | U16 | 1 | |
| AI2 upper limit | 1337 | U16 | 1 | |
| AI2 upper limit corresponding setting | 1338 | U16 | 1 | |
| AI2 filter time | 1339 | U16 | 1 | |
| Curve 1 lower limit | 1340 | U16 | 1 | |
| Curve 1 lower limit corresponding setting | 1341 | U16 | 1 | |
| Input voltage of inflexion point 1 of curve 1 | 1342 | U16 | 1 | |
| Corresponding setting of inflection point 1 of curve 1 | 1343 | U16 | 1 | |
| Input voltage of inflexion point 2 of curve 1 | 1344 | U16 | 1 | |
| Corresponding setting of inflection point 2 of curve 1 | 1345 | U16 | 1 | |
| Curve 1 upper limit | 1346 | U16 | 1 | |
| Curve 1 upper limit corresponding setting | 1347 | U16 | 1 | |
| Curve 2 lower limit | 1350 | U16 | 1 | |
| Curve 2 lower limit corresponding setting | 1351 | U16 | 1 | |
| Input voltage of inflexion point 1 of curve 2 | 1352 | U16 | 1 | |
| Corresponding setting of inflection point 1 of curve 2 | 1353 | U16 | 1 | |
| Input voltage of inflexion point 2 of curve 2 | 1354 | U16 | 1 | |
| Corresponding setting of inflection point 2 of curve 2 | 1355 | U16 | 1 | |
| Curve 2 upper limit | 1356 | U16 | 1 | |
| Curve 2 upper limit corresponding setting | 1357 | U16 | 1 | |
| Characteristic selection of AI as digital input terminals | 1360 | U16 | 1 | |
| Function selection of AI1 terminal (as X) | 1361 | U16 | 1 | |
| High level setting for AI1 | 1362 | U16 | 1 | |
| Low level setting for AI1 | 1363 | U16 | 1 | |
| Function selection of AI2 terminal (as X) | 1364 | U16 | 1 | |
| High level setting for AI2 | 1365 | U16 | 1 | |
| Low level setting for AI2 | 1366 | U16 | 1 | |
| AO mode selection | 1536 | U16 | 1 | |
| AO quantity selection | 1537 | U16 | 1 | |
| AO gain | 1538 | U16 | 1 | |
| AO bias | 1539 | U16 | 1 | |
| AO filter | 1540 | U16 | 1 | |
| Setting AO as the FM output lower limit | 1541 | U16 | 1 | |
| Setting AO as the FM output upper limit | 1542 | U16 | 1 | |
| Expanded AO mode selection | 1546 | U16 | 1 | |
| Expanded AO quantity selection | 1547 | U16 | 1 | |
| Expanded AO gain | 1548 | U16 | 1 | |
| Expanded AO analog output bias | 1549 | U16 | 1 | |
| Expanded AO filtering | 1550 | U16 | 1 | |
| Output terminal polarity selection | 1556 | U16 | 1 | |
| Output terminal Y | 1557 | U16 | 1 | |
| Relay 1 output (TA-TB-TC) | 1558 | U16 | 1 | |
| Extended output terminal Y1 | 1559 | U16 | 1 | |
| Extended relay 2 output (TA-TB-TC) | 1560 | U16 | 1 | |
| Delay when Y outputs ON | 1561 | U16 | 1 | |
| Delay when relay 1 outputs ON | 1562 | U16 | 1 | |
| Delay when extended Y outputs ON | 1563 | U16 | 1 | |
| Delay when extended relay 2 outputs ON | 1564 | U16 | 1 | |
| Delay when Y outputs OFF | 1565 | U16 | 1 | |
| Delay when relay 1 outputs OFF | 1566 | U16 | 1 | |
| Delay when extended Y outputs OFF | 1567 | U16 | 1 | |
| Delay when extended relay 2 outputs OFF | 1568 | U16 | 1 | |
| Frequency detection value 1 | 1576 | U16 | 1 | |
| Frequency detection range 1 | 1577 | U16 | 1 | |
| Frequency detection value 2 | 1578 | U16 | 1 | |
| Frequency detection range 2 | 1579 | U16 | 1 | |
| Detection range for the given frequency reached | 1580 | U16 | 1 | |
| Comparator 1 monitor selection | 1586 | U16 | 1 | |
| Comparator 1 upper limit | 1587 | U16 | 1 | |
| Comparator 1 lower limit | 1588 | U16 | 1 | |
| Comparator 1 bias | 1589 | U16 | 1 | |
| Comparator 1 action selection | 1590 | U16 | 1 | |
| Comparator 2 monitor selection | 1591 | U16 | 1 | |
| Comparator 2 upper limit | 1592 | U16 | 1 | |
| Comparator 2 lower limit | 1593 | U16 | 1 | |
| Comparator 2 bias | 1594 | U16 | 1 | |
| Comparator 2 action selection | 1595 | U16 | 1 | |
| Function selection of virtual terminal vX1 | 1596 | U16 | 1 | |
| Function selection of virtual terminal vX2 | 1597 | U16 | 1 | |
| Function selection of virtual terminal vX3 | 1598 | U16 | 1 | |
| Function selection of virtual terminal vX4 | 1599 | U16 | 1 | |
| Activation state source of terminal vX | 1600 | U16 | 1 | |
| Activation state of function code setting for virtual termin | 1601 | U16 | 1 | |
| Virtual vY1 output selection | 1602 | U16 | 1 | |
| Virtual vY2 output selection | 1603 | U16 | 1 | |
| Virtual vY3 output selection | 1604 | U16 | 1 | |
| Virtual vY4 output selection | 1605 | U16 | 1 | |
| Delay when vY1 outputs ON | 1606 | U16 | 1 | |
| Delay when vY2 outputs ON | 1607 | U16 | 1 | |
| Delay when vY3 outputs ON | 1608 | U16 | 1 | |
| Delay when vY4 outputs ON | 1609 | U16 | 1 | |
| vY1 output OFF delay time | 1610 | U16 | 1 | |
| vY2 output OFF delay time | 1611 | U16 | 1 | |
| vY3 output OFF delay time | 1612 | U16 | 1 | |
| vY4 output OFF delay time | 1613 | U16 | 1 | |
| Start mode | 1792 | U16 | 1 | |
| Start pre-excitation time | 1793 | U16 | 1 | |
| Start frequency | 1794 | U16 | 1 | |
| Start protection selection | 1795 | U16 | 1 | |
| Rotation direction selection | 1797 | U16 | 1 | |
| Selection of restart action upon power failure | 1798 | U16 | 1 | |
| Waiting time for restart after power failure | 1799 | U16 | 1 | |
| Stop mode | 1802 | U16 | 1 | |
| Stop detection frequency | 1803 | U16 | 1 | |
| Minimum time between stop and restart | 1804 | U16 | 1 | |
| Selection of action below lower frequency limit | 1807 | U16 | 1 | |
| Zero-speed torque retention current | 1808 | U16 | 1 | |
| Zero-speed torque retention time | 1809 | U16 | 1 | |
| Forward and reverse rotation dead time | 1810 | U16 | 1 | |
| Start DC braking current | 1812 | U16 | 1 | |
| DC braking time on startup | 1813 | U16 | 1 | |
| DC braking start frequency | 1814 | U16 | 1 | |
| Stop DC braking current | 1815 | U16 | 1 | |
| Stop DC braking time | 1816 | U16 | 1 | |
| Speed tracking mode | 1817 | U16 | 1 | |
| Speed tracking time | 1818 | U16 | 1 | |
| Speed tracking stop delay | 1819 | U16 | 1 | |
| Speed tracking current | 1820 | U16 | 1 | |
| Jogging frequency setting | 1822 | U16 | 1 | |
| Jogging acceleration time | 1823 | U16 | 1 | |
| Jogging deceleration time | 1824 | U16 | 1 | |
| Jogging S-curve selection | 1825 | U16 | 1 | |
| Jogging stop mode selection | 1826 | U16 | 1 | |
| Start retention frequency | 1832 | U16 | 1 | |
| Start frequency retention time | 1833 | U16 | 1 | |
| Stop retention frequency | 1834 | U16 | 1 | |
| Stop frequency retention time | 1835 | U16 | 1 | |
| Hopping frequency 1 | 1836 | U16 | 1 | |
| Hopping frequency amplitude 1 | 1837 | U16 | 1 | |
| Hopping frequency 2 | 1838 | U16 | 1 | |
| Hopping frequency amplitude 2 | 1839 | U16 | 1 | |
| Counter input source | 2048 | U16 | 1 | |
| Count input frequency division | 2049 | U16 | 1 | |
| Counter maximum value | 2050 | U16 | 1 | |
| Counter setting value | 2051 | U16 | 1 | |
| Number of pulses per meter | 2052 | U16 | 1 | |
| Set length | 2053 | U16 | 1 | |
| Actual length | 2054 | U16 | 1 | |
| Timer time unit | 2055 | U16 | 1 | |
| Timer set point | 2056 | U16 | 1 | |
| Swing frequency control selection | 2078 | U16 | 1 | |
| Swing frequency amplitude control selection | 2079 | U16 | 1 | |
| Preset swing frequency | 2080 | U16 | 1 | |
| Preset swing frequency waiting time | 2081 | U16 | 1 | |
| Swing frequency amplitude | 2082 | U16 | 1 | |
| Jump frequency | 2083 | U16 | 1 | |
| Triangular wave rise time | 2084 | U16 | 1 | |
| Triangular wave drop time | 2085 | U16 | 1 | |
| Device maintenance alarm selection | 2306 | U16 | 1 | |
| Cooling fan maintenance setting | 2307 | U16 | 1 | |
| Main relay maintenance setting | 2308 | U16 | 1 | |
| Over-current suppression function | 2560 | U16 | 1 | |
| Over-current suppression point | 2561 | U16 | 1 | |
| Over-current suppression gain | 2562 | U16 | 1 | |
| Current protection setting 1 | 2563 | U16 | 1 | |
| Current protection setting 2 | 2564 | U16 | 1 | |
| Current imbalance judgment threshold | 2565 | U16 | 1 | |
| Current imbalance filter coefficient | 2566 | U16 | 1 | |
| Bus overvoltage suppression function | 2571 | U16 | 1 | |
| Bus overvoltage suppression point | 2572 | U16 | 1 | |
| Bus overvoltage suppression gain | 2573 | U16 | 1 | |
| Dynamic brake enabling | 2574 | U16 | 1 | |
| Dynamic brake action voltage | 2575 | U16 | 1 | |
| Bus under-voltage suppression function | 2576 | U16 | 1 | |
| Bus under-voltage suppression point | 2577 | U16 | 1 | |
| Bus under-voltage suppression gain | 2578 | U16 | 1 | |
| DC bus under-voltage protection point | 2579 | U16 | 1 | |
| Input and output phase loss protection selection | 2580 | U16 | 1 | |
| Input phase loss threshold | 2581 | U16 | 1 | |
| Grounding short circuit protection selection | 2582 | U16 | 1 | |
| Fan ON/OFF control selection | 2583 | U16 | 1 | |
| Fan control delay time | 2584 | U16 | 1 | |
| AC drive overheat oH1 warning detection level | 2585 | U16 | 1 | |
| Motor overheat protection selection (Extension card) | 2586 | U16 | 1 | |
| Motor overheat alarm level (Extension card) | 2587 | U16 | 1 | |
| Motor overheat warning level (Extension card) | 2588 | U16 | 1 | |
| Load warning detection setting | 2592 | U16 | 1 | |
| Load warning detection level 1 | 2593 | U16 | 1 | |
| Load warning detection time 1 | 2594 | U16 | 1 | |
| Load warning detection level 2 | 2595 | U16 | 1 | |
| Load warning detection time 2 | 2596 | U16 | 1 | |
| Protection against excessive speed deviation | 2600 | U16 | 1 | |
| Excessive speed deviation detection threshold | 2601 | U16 | 1 | |
| Excessive speed deviation detection time | 2602 | U16 | 1 | |
| Speed surge protection | 2603 | U16 | 1 | |
| Speed surge detection threshold | 2604 | U16 | 1 | |
| Speed surge detection time | 2605 | U16 | 1 | |
| Fault self-recovery times setting | 2610 | U16 | 1 | |
| Fault self-recovery interval | 2611 | U16 | 1 | |
| Times of fault recovery | 2612 | U16 | 1 | |
| Motor overload model | 2615 | U16 | 1 | |
| Motor insulation class | 2616 | U16 | 1 | |
| Motor working system | 2617 | U16 | 1 | |
| Motor overload start threshold | 2618 | U16 | 1 | |
| Motor overload current coefficient | 2619 | U16 | 1 | |
| Parameters and button lock selection | 2816 | U16 | 1 | |
| Button lock password | 2817 | U16 | 1 | |
| Keyboard multi-function button selection | 2818 | U16 | 1 | |
| Keyboard STOP button setting | 2819 | U16 | 1 | |
| Function of up/down button (knob) in status interface | 2820 | U16 | 1 | |
| Parameter code setting quick change with up/down button | 2821 | U16 | 1 | |
| Keyboard command button selection | 2822 | U16 | 1 | |
| Function of left/right buttons in status interface | 2826 | U16 | 1 | |
| Loop parameter 1 for the keyboard first line | 2827 | U16 | 1 | |
| Loop parameter 2 for the keyboard first line | 2828 | U16 | 1 | |
| Loop parameter 3 for the keyboard first line | 2829 | U16 | 1 | |
| Loop parameter 4 for the keyboard first line | 2830 | U16 | 1 | |
| Loop parameter 1 for the keyboard second line | 2831 | U16 | 1 | |
| Loop parameter 2 for the keyboard second line | 2832 | U16 | 1 | |
| Loop parameter 3 for the keyboard second line | 2833 | U16 | 1 | |
| Loop parameter 4 for the keyboard second line | 2834 | U16 | 1 | |
| Keyboard display item setting | 2836 | U16 | 1 | |
| Speed display coefficient | 2837 | U16 | 1 | |
| Power display coefficient | 2838 | U16 | 1 | |
| Monitoring parameter group display selection | 2839 | U16 | 1 | |
| Monitoring parameter filtering selection | 2840 | U16 | 1 | |
| Display during motor auto-tuning | 2841 | U16 | 1 | |
| Fault self-recovery display selection | 2843 | U16 | 1 | |
| Lower voltage limit of keyboard potentiometer | 2847 | U16 | 1 | |
| Corresponding value to lower limit of keyboard potentiometer | 2848 | U16 | 1 | |
| Upper voltage limit of keyboard potentiometer | 2849 | U16 | 1 | |
| Corresponding value to upper limit of keyboard potentiometer | 2850 | U16 | 1 | |
| Keyboard potentiometer selection | 2851 | U16 | 1 | |
| Master/Slave selection | 3072 | U16 | 1 | |
| Modbus communication address | 3073 | U16 | 1 | |
| Communication baud rate selection | 3074 | U16 | 1 | |
| Modbus communication data format | 3075 | U16 | 1 | |
| Modbus communication transmission response processing | 3076 | U16 | 1 | |
| Modbus communication response delay | 3077 | U16 | 1 | |
| Modbus communication timeout fault time | 3078 | U16 | 1 | |
| Communication disconnection processing | 3079 | U16 | 1 | |
| Receiving data (address 0x3000) zero bias | 3080 | U16 | 1 | |
| Receive data (address 0x3000) gain | 3081 | U16 | 1 | |
| Master loop transmission parameter selection | 3082 | U16 | 1 | |
| Custom address of given frequency | 3083 | U16 | 1 | |
| Command setting custom address setting | 3084 | U16 | 1 | |
| Custom address of forward running command | 3085 | U16 | 1 | |
| Custom address of reverse running command | 3086 | U16 | 1 | |
| Custom address of stop command | 3087 | U16 | 1 | |
| Custom address of reset command | 3088 | U16 | 1 | |
| Master sending command selection | 3091 | U16 | 1 | |
| RJ45 interface communication mode selection | 3092 | U16 | 1 | |
| Slave address of RJ45 interface | 3093 | U16 | 1 | |
| RJ45 interface communication baud rate selection | 3094 | U16 | 1 | |
| RJ45 interface data format | 3095 | U16 | 1 | |
| RJ45 interface transmission response processing | 3096 | U16 | 1 | |
| RJ45 interface communication response delay | 3097 | U16 | 1 | |
| RJ45 interface communication timeout fault time | 3098 | U16 | 1 | |
| RJ45 interface communication disconnection processing | 3099 | U16 | 1 | |
| DP card address | 3102 | U16 | 1 | |
| DP master-slave communication fault action | 3104 | U16 | 1 | |
| CAN mode selection | 3112 | U16 | 1 | |
| CAN communication slave address | 3113 | U16 | 1 | |
| CAN communication baud rate | 3114 | U16 | 1 | |
| CAN master-slave communication fault action | 3115 | U16 | 1 | |
| Expansion port communication disconnection processing | 3122 | U16 | 1 | |
| Extension port EX-A parameter updating | 3123 | U16 | 1 | |
| Extension port EX-B parameter updating | 3124 | U16 | 1 | |
| Extension port EX-A monitor frame address group 1 | 3125 | U16 | 1 | |
| Extension port EX-A monitor frame address group 2 | 3126 | U16 | 1 | |
| Extension port EX-A monitor frame address group 3 | 3127 | U16 | 1 | |
| Extension port EX-A monitor frame address group 4 | 3128 | U16 | 1 | |
| Extension port EX-B monitor frame address group 1 | 3129 | U16 | 1 | |
| Extension port EX-B monitor frame address group 2 | 3130 | U16 | 1 | |
| Extension port EX-B monitor frame address group 3 | 3131 | U16 | 1 | |
| Extension port EX-B monitor frame address group 4 | 3132 | U16 | 1 | |
| PID control given source | 3328 | U16 | 1 | |
| Keyboard digital of PID given/feedback | 3329 | U16 | 1 | |
| PID given change time | 3330 | U16 | 1 | |
| PID control feedback source | 3331 | U16 | 1 | |
| Feedback signal low-pass filter time | 3332 | U16 | 1 | |
| Feedback signal gain | 3333 | U16 | 1 | |
| Feedback signal range | 3334 | U16 | 1 | |
| PID control selection | 3335 | U16 | 1 | |
| PID preset output | 3336 | U16 | 1 | |
| PID preset output running time | 3337 | U16 | 1 | |
| PID control deviation limit | 3338 | U16 | 1 | |
| Proportional gain P1 | 3339 | U16 | 1 | |
| Integral time I1 | 3340 | U16 | 1 | |
| Differentiation gain D1 | 3341 | U16 | 1 | |
| Proportional gain P2 | 3342 | U16 | 1 | |
| Integral time I2 | 3343 | U16 | 1 | |
| Differentiation gain D2 | 3344 | U16 | 1 | |
| PID parameter switching conditions | 3345 | U16 | 1 | |
| Lower value of switching deviation | 3346 | U16 | 1 | |
| Higher value of switching deviation | 3347 | U16 | 1 | |
| Differentiation limit | 3349 | U16 | 1 | |
| Upper limit of PID output | 3350 | U16 | 1 | |
| Lower limit of PID output | 3351 | U16 | 1 | |
| PID output filter time | 3352 | U16 | 1 | |
| Feedback disconnection action selection | 3353 | U16 | 1 | |
| Feedback disconnection detection time | 3354 | U16 | 1 | |
| Disconnection alarm upper limit | 3355 | U16 | 1 | |
| Disconnection alarm lower limit | 3356 | U16 | 1 | |
| Sleep selection | 3357 | U16 | 1 | |
| Sleep frequency | 3358 | U16 | 1 | |
| Sleep delay time | 3359 | U16 | 1 | |
| Wake-up deviation | 3360 | U16 | 1 | |
| Wake-up delay time | 3361 | U16 | 1 | |
| PLC multi-speed 1 | 3584 | U16 | 1 | |
| PLC multi-speed 2 | 3585 | U16 | 1 | |
| PLC multi-speed 3 | 3586 | U16 | 1 | |
| PLC multi-speed 4 | 3587 | U16 | 1 | |
| PLC multi-speed 5 | 3588 | U16 | 1 | |
| PLC multi-speed 6 | 3589 | U16 | 1 | |
| PLC multi-speed 7 | 3590 | U16 | 1 | |
| PLC multi-speed 8 | 3591 | U16 | 1 | |
| PLC multi-speed 9 | 3592 | U16 | 1 | |
| PLC multi-speed 10 | 3593 | U16 | 1 | |
| PLC multi-speed 11 | 3594 | U16 | 1 | |
| PLC multi-speed 12 | 3595 | U16 | 1 | |
| PLC multi-speed 13 | 3596 | U16 | 1 | |
| PLC multi-speed 14 | 3597 | U16 | 1 | |
| PLC multi-speed 15 | 3598 | U16 | 1 | |
| PLC running mode selection | 3599 | U16 | 1 | |
| PLC segment 1 running time | 3600 | U16 | 1 | |
| PLC segment 2 running time | 3601 | U16 | 1 | |
| PLC segment 3 running time | 3602 | U16 | 1 | |
| PLC segment 4 running time | 3603 | U16 | 1 | |
| PLC segment 5 running time | 3604 | U16 | 1 | |
| PLC segment 6 running time | 3605 | U16 | 1 | |
| PLC segment 7 running time | 3606 | U16 | 1 | |
| PLC segment 8 running time | 3607 | U16 | 1 | |
| PLC segment 9 running time | 3608 | U16 | 1 | |
| PLC segment 10 running time | 3609 | U16 | 1 | |
| PLC segment 11 running time | 3610 | U16 | 1 | |
| PLC segment 12 running time | 3611 | U16 | 1 | |
| PLC segment 13 running time | 3612 | U16 | 1 | |
| PLC segment 14 running time | 3613 | U16 | 1 | |
| PLC segment 15 running time | 3614 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3615 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3616 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3617 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3618 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3619 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3620 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3621 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3622 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3623 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3624 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3625 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3626 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3627 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3628 | U16 | 1 | |
| Direction and acceleration/deceleration time of PLC segment | 3629 | U16 | 1 | |
| Given frequency | 8192 | U16 | 0.01 | Hz |
| Command setting | 8193 | U16 | 1 | |
| Drive status information | 8194 | U16 | 1 | |
| AC drive fault code | 8195 | U16 | 1 | |
| Upper frequency limit | 8196 | U16 | 0.01 | Hz |
| Torque setting | 8197 | U16 | 0.1 | % |
| Torque control forward speed limit | 8198 | U16 | 0.1 | % |
| Torque control reverse speed limit | 8199 | U16 | 0.1 | % |
| PID given | 8200 | U16 | 0.1 | % |
| PID feedback | 8201 | U16 | 0.1 | % |
| VF separation voltage setting | 8202 | U16 | 0.1 | % |
| Tension setting | 8203 | U16 | 0.1 | % |
| Roll diameter setting | 8204 | U16 | 0.1 | % |
| Linear speed setting | 8205 | U16 | 0.1 | % |
| Acceleration time 1 | 8206 | U16 | 0.01 | s |
| Deceleration time 1 | 8207 | U16 | 0.01 | s |
| Fault warning & warning code | 8208 | U16 | 1 | |
| Torque current component | 8209 | U16 | 0.1 | % |
| Torque filter time | 8210 | U16 | 0.001 | s |
| Tension PID feedback | 8211 | U16 | 1 | |
| Communication-set electric torque limit | 8212 | U16 | 1 | |
| Communication-set power generation torque limit | 8213 | U16 | 1 | |
| Reserved | 8214 | U16 | 1 | |
| Reserved | 8215 | U16 | 1 | |
| Terminal output control | 8216 | U16 | 1 | |
| AO output | 8217 | U16 | 0.01 | |
| Expanded AO output | 8218 | U16 | 0.01 | |
| Custom 1 | 8219 | U16 | 1 | |
| Custom 2 | 8220 | U16 | 1 | |
| Custom 3 | 8221 | U16 | 1 | |
| Custom 4 | 8222 | U16 | 1 | |
| Custom 5 | 8223 | U16 | 1 | |
| Given frequency | 8448 | U16 | 1 | |
| Output frequency | 8449 | U16 | 1 | |
| Output current | 8450 | U16 | 0.1 | A |
| Input voltage | 8451 | U16 | 0.1 | V |
| Output voltage | 8452 | U16 | 0.1 | V |
| Mechanical speed | 8453 | U16 | 1 | rpm |
| Given torque | 8454 | I16 | 0.1 | % |
| Output torque | 8455 | I16 | 0.1 | % |
| PID given | 8456 | I16 | 0.1 | % |
| PID feedback value | 8457 | I16 | 0.1 | % |
| Output power | 8458 | I16 | 0.1 | % |
| DC-Bus voltage | 8459 | U16 | 0.1 | V |
| Module temperature 1 | 8460 | I16 | 0.1 | °C |
| Module temperature 2 | 8461 | I16 | 0.1 | °C |
| Input terminal X connection status | 8462 | U16 | 1 | |
| Output terminal Y connection status | 8463 | U16 | 1 | |
| Analog AI1 input value | 8464 | U16 | 0.001 | V |
| Analog AI2 input value | 8465 | U16 | 0.001 | V |
| Pulse signal PUL input value | 8467 | U16 | 0.001 | kHz |
| Analog output AO | 8468 | U16 | 0.01 | V |
| Expanded AO output | 8469 | U16 | 0.01 | V |
| Counter value | 8470 | U16 | 1 | |
| Running time after power-on | 8471 | U16 | 0.1 | hours |
| Cumulative running time of this AC drive | 8472 | U16 | 1 | Hours |
| AC drive capacity | 8473 | U16 | 0.1 | kVA |
| Rated voltage of AC drive | 8474 | U16 | 1 | V |
| Rated current of AC drive | 8475 | U16 | 0.1 | A |
| Software version | 8476 | U16 | 0.01 | |
| PG feedback frequency | 8477 | U16 | 0.01 | Hz |
| Timer time | 8478 | U16 | 1 | |
| PID output value | 8479 | I16 | 0.01 | % |
| AC drive Software Sub-Version | 8480 | U16 | 1 | |
| Encoder feedback angle | 8481 | U16 | 1 | |
| Z pulse cumulative error | 8482 | U16 | 1 | |
| Z pulse count | 8483 | U16 | 1 | |
| Fault warning code | 8484 | U16 | 1 | |
| Cumulative Power Consumption (low level) | 8485 | U16 | 1 | |
| Cumulative power consumption (high level) | 8486 | U16 | 1 | |
| Power factor angle | 8487 | I16 | 1 | ° |
| Diagnostic information on fault type | 8704 | U16 | 1 | |
| Fault diagnosis information | 8705 | U16 | 1 | |
| Output frequency upon fault | 8706 | U16 | 0.01 | Hz |
| Output voltage upon fault | 8707 | U16 | 0.1 | V |
| Output current upon fault | 8708 | U16 | 0.1 | A |
| DC-Bus voltage upon fault | 8709 | U16 | 0.1 | V |
| Module temperature upon fault | 8710 | I16 | 0.1 | |
| AC drive status upon fault | 8711 | U16 | 1 | |
| Input terminal status upon fault | 8712 | U16 | 1 | |
| Output terminal status upon fault | 8713 | U16 | 1 | |
| Last fault type | 8714 | U16 | 1 | |
| Diagnosis Information of Last Fault | 8715 | U16 | 1 | |
| Operating frequency of last fault | 8716 | U16 | 1 | |
| Output voltage of last fault | 8717 | U16 | 1 | |
| Output current of last fault | 8718 | U16 | 1 | |
| Bus voltage of last fault | 8719 | U16 | 1 | |
| Module temperature upon last fault | 8720 | U16 | 1 | |
| AC drive status of last fault | 8721 | U16 | 1 | |
| Input terminal status of last fault | 8722 | U16 | 1 | |
| Output terminal status of last fault | 8723 | U16 | 1 | |
| Fault types of the first two times | 8724 | U16 | 1 | |
| Diagnosis information of the first two times | 8725 | U16 | 1 | |
| Fault types of the first three times | 8726 | U16 | 1 | |
| Diagnosis information of the first three times | 8727 | U16 | 1 | |
| PID setting | 8960 | U16 | 1 | |
| PID feedback | 8961 | U16 | 1 | |
| PID output | 8962 | U16 | 1 | |
| PID Control status | 8963 | U16 | 1 | |
| PLC running stage | 8965 | U16 | 1 | |
| PLC segment frequency | 8966 | U16 | 1 | |
| PLC segment running time | 8967 | U16 | 1 | |
| Forward and reverse command setting | 8968 | U16 | 1 | |
| Jogging command setting | 8969 | U16 | 1 | |
| AI1 pre-correction voltage/current | 8970 | U16 | 1 | |
| AI2 pre-correction voltage/current | 8971 | U16 | 1 | |
| AO pre-correction voltage/current | 8972 | U16 | 1 | |
| Expanded AO pre-correction voltage/current | 8973 | U16 | 1 | |
| Reserved | 8974 | U16 | 1 | |
| AC drive overload timing coefficient | 8975 | U16 | 1 | |
| Motor overload timing coefficient | 8976 | U16 | 1 | |
| Reserved | 8977 | U16 | 1 | |
| Reserved | 8978 | U16 | 1 | |
| Times of cycle-by-cycle current limiting | 8979 | U16 | 1 | |
| Reserved | 8980 | U16 | 1 | |
| Reserved | 8981 | U16 | 1 | |
| Reserved | 8982 | U16 | 1 | |
| Reserved | 8983 | U16 | 1 | |
| Reserved | 8984 | U16 | 1 | |
| IO extension card analog 1 | 8985 | U16 | 1 | |
| IO extension card analog 2 | 8986 | U16 | 1 | |
| IO extension card analog 3 | 8987 | U16 | 1 | |
| IO extension card input terminal status | 8988 | U16 | 1 | |
| Motor temperature detected by IO extension card | 8989 | U16 | 1 | |
| IO extension card PUL count low level | 8990 | U16 | 1 | |
| IO extension card PUL count high level | 8991 | U16 | 1 | |
| Stored parameter 1 after power-off | 8992 | U16 | 1 | |
| Stored parameter 2 after power-off | 8993 | U16 | 1 | |
| Stored parameter 3 after power-off | 8994 | U16 | 1 | |
| Stored parameter 4 after power-off | 8995 | U16 | 1 | |
| Stored parameter 5 after power-off | 8996 | U16 | 1 | |
| Stored parameter 6 after power-off | 8997 | U16 | 1 | |
| Stored parameter 7 after power-off | 8998 | U16 | 1 | |
| Stored parameter 8 after power-off | 8999 | U16 | 1 | |
| Stored parameter 9 after power-off | 9000 | U16 | 1 | |
| Stored parameter 10 after power-off | 9001 | U16 | 1 | |
| Stored parameter 11 after power-off | 9002 | U16 | 1 | |
| Stored parameter 12 after power-off | 9003 | U16 | 1 | |
| Stored parameter 13 after power-off | 9004 | U16 | 1 | |
| Stored parameter 14 after power-off | 9005 | U16 | 1 | |
| Stored parameter 15 after power-off | 9006 | U16 | 1 | |
| Stored parameter 16 after power-off | 9007 | U16 | 1 | |
| Reserved | 9008 | U16 | 1 | |
| Reserved | 9009 | U16 | 1 | |
| Cache register 0 | 9010 | U16 | 1 | |
| Cache register 1 | 9011 | U16 | 1 | |
| Cache register 2 | 9012 | U16 | 1 | |
| Cache register 3 | 9013 | U16 | 1 | |
| Cache register 4 | 9014 | U16 | 1 | |
| Cache register 5 | 9015 | U16 | 1 | |
| Cache register 6 | 9016 | U16 | 1 | |
| Cache register 7 | 9017 | U16 | 1 | |
| Cache register 8 | 9018 | U16 | 1 | |
| Cache register 9 | 9019 | U16 | 1 | |
| Extension card A software version | 9020 | U16 | 1 | |
| Extension card B software version | 9021 | U16 | 1 | |
| External keyboard version | 9022 | U16 | 1 | |
| Reserved | 9023 | U16 | 1 | |
| Running time after power-up | 9216 | U16 | 0.1 | hours |
| Cumulative running time (hour) | 9217 | U16 | 1 | hour |
| Cumulative power-on time (hour) | 9218 | U16 | 1 | hour |
| Cumulative power-on time (minute) | 9219 | U16 | 1 | minute |
| Cooling fan running time | 9220 | U16 | 1 | hour |
| Cooling fan maintenance | 9221 | U16 | 1 | % |
| Main relay maintenance | 9223 | U16 | 1 | % |
| Final tension setting | 9236 | U16 | 0.1 | N |
| Initial roll diameter value | 9237 | U16 | 1 | mm |
| Current value of linear velocity | 9238 | U16 | 0.1 | m/min |
| Current value of roll diameter | 9239 | U16 | 1 | mm |
| Tension channel torque set value | 9240 | I16 | 0.1 | % |
| Tension PID given | 9241 | I16 | 0.1 | % |
| Tension PID feedback | 9242 | I16 | 0.1 | % |
| Tension PID output | 9243 | I16 | 1 | |
| Static friction compensation value | 9244 | I16 | 0.1 | % |
| Dynamic friction compensation value | 9245 | I16 | 0.1 | % |
| Total friction compensation value | 9246 | I16 | 0.1 | % |
| Given frequency | 12544 | U16 | 0.01 | Hz |
| Command setting | 12545 | U16 | 1 | |
| AC drive status information | 12546 | U16 | 1 | |
| AC drive fault code | 12547 | U16 | 1 | |
| Upper frequency limit | 12548 | U16 | 0.01 | Hz |
| Torque setting | 12549 | U16 | 0.1 | % |
| Torque control forward speed limit | 12550 | U16 | 0.1 | % |
| Torque control reverse speed limit | 12551 | U16 | 0.1 | % |
| PID setting | 12552 | U16 | 0.1 | % |
| PID feedback | 12553 | U16 | 0.1 | % |
| VF separation voltage setting | 12554 | U16 | 0.1 | % |
| Tension setting | 12555 | U16 | 0.1 | % |
| Roll diameter setting | 12556 | U16 | 0.1 | % |
| Linear speed setting | 12557 | U16 | 0.1 | % |
| Acceleration time 1 | 12558 | U16 | 0.01 | s |
| Deceleration time 1 | 12559 | U16 | 0.01 | s |
| Fault warning & warning code | 12560 | U16 | 1 | |
| Torque current component | 12561 | U16 | 0.1 | % |
| Torque filter time | 12562 | U16 | 0.001 | s |
| Terminal output control | 12568 | U16 | 1 | |
| AO output | 12569 | U16 | 0.01 | |
| Expanded AO output | 12570 | U16 | 0.01 | |
| Custom 1 | 12571 | U16 | 1 | |
| Custom 2 | 12572 | U16 | 1 | |
| Custom 3 | 12573 | U16 | 1 | |
| Custom 4 | 12574 | U16 | 1 | |
| Custom 5 | 12575 | U16 | 1 | |
| Extension port SPI communication mode | 13312 | U16 | 1 | |
| Input terminal status | 13313 | U16 | 1 | |
| Output terminal status | 13314 | U16 | 1 | |
| Multi-function input terminal functional group 0 | 13317 | U16 | 1 | |
| Multi-function input terminal function group 1 | 13318 | U16 | 1 | |
| Multi-function input terminal function group 2 | 13319 | U16 | 1 | |
| Multi-function input terminal function group 3 | 13320 | U16 | 1 | |
| Multi-function input terminal function group 4 | 13321 | U16 | 1 | |
| Multi-function input terminal function group 5 | 13322 | U16 | 1 | |
| IO extension card input terminal status | 13323 | U16 | 1 | |
| IO extension card output terminal status | 13324 | U16 | 1 | |
| IO extension card analog 1 | 13325 | U16 | 0.01 | % |
| IO extension card analog 2 | 13326 | U16 | 1 | |
| IO extension card analog 3 | 13327 | U16 | 1 | |
| IO extension card analog 4 | 13328 | U16 | 1 | |
| IO extension card PUL frequency measurement 1 | 13329 | U16 | 1 | |
| IO extension card PUL frequency measurement 2 | 13330 | U16 | 1 | |
| A0 function 24 output | 13332 | U16 | 1 | |
| A0 function 25 output | 13333 | U16 | 1 | |
| A0 function 26 output | 13334 | U16 | 1 | |
| A0 function 27 output | 13335 | U16 | 1 | |
| A0 function 28 output | 13336 | U16 | 1 | |
| A0 function 29 output | 13337 | U16 | 1 | |
| A0 function 30 output | 13338 | U16 | 1 | |
| A0 function 31 output | 13339 | U16 | 1 | |
| IO extension card PUL port count 1 | 13340 | U16 | 1 | |
| IO extension card PUL port count 2 | 13341 | U16 | 1 | |
| Register 0 | 13568 | U16 | 1 | |
| Register 1 | 13569 | U16 | 1 | |
| Register 2 | 13570 | U16 | 1 | |
| Register 3 | 13571 | U16 | 1 | |
| Register 4 | 13572 | U16 | 1 | |
| Register 5 | 13573 | U16 | 1 | |
| Register 6 | 13574 | U16 | 1 | |
| Register 7 | 13575 | U16 | 1 | |
| Register 8 | 13576 | U16 | 1 | |
| Register 9 | 13577 | U16 | 1 | |
| Register 10 | 13578 | U16 | 1 | |
| Register 11 | 13579 | U16 | 1 | |
| Register 12 | 13580 | U16 | 1 | |
| Register 13 | 13581 | U16 | 1 | |
| Register 14 | 13582 | U16 | 1 | |
| Register 15 | 13583 | U16 | 1 | |
| Custom fault number register | 13824 | U16 | 1 | |
| Custom early-warning number register | 13825 | U16 | 1 | |
| Stored parameter 1 after power-off | 13834 | U16 | 1 | |
| Stored parameter 2 after power-off | 13835 | U16 | 1 | |
| Stored parameter 3 after power-off | 13836 | U16 | 1 | |
| Stored parameter 4 after power-off | 13837 | U16 | 1 | |
| Stored parameter 5 after power-off | 13838 | U16 | 1 | |
| Stored parameter 1 after power-off | 13839 | U16 | 1 | |
| Stored parameter 6 after power-off | 13840 | U16 | 1 | |
| Stored parameter 7 after power-off | 13841 | U16 | 1 | |
| Stored parameter 8 after power-off | 13842 | U16 | 1 | |
| Stored parameter 9 after power-off | 13843 | U16 | 1 | |
| Stored parameter 10 after power-off | 13844 | U16 | 1 | |
| Stored parameter 11 after power-off | 13845 | U16 | 1 | |
| Stored parameter 12 after power-off | 13846 | U16 | 1 | |
| Stored parameter 13 after power-off | 13847 | U16 | 1 | |
| Stored parameter 14 after power-off | 13848 | U16 | 1 | |
| Stored parameter 15 after power-off | 13849 | U16 | 1 | |
| Winding mode setting | 20481 | U16 | 1 | |
| Mechanical transmission ratio | 20482 | U16 | 1 | |
| Tension given selection | 20483 | U16 | 1 | |
| Tension keyboard digital given | 20484 | U16 | 1 | |
| Maximum tension | 20485 | U16 | 1 | |
| Tension taper coefficient | 20486 | U16 | 1 | |
| Taper compensation correction | 20487 | U16 | 1 | |
| Zero speed threshold | 20488 | U16 | 1 | |
| Zero speed tension gain | 20489 | U16 | 1 | |
| Static friction compensation coefficient | 20492 | U16 | 1 | |
| Static friction compensation delay time | 20493 | U16 | 1 | |
| Static friction compensation cutoff frequency | 20494 | U16 | 1 | |
| Start coefficient of sliding friction compensation | 20495 | U16 | 1 | |
| End coefficient of sliding friction compensation | 20496 | U16 | 1 | |
| Material interruption detection selection | 20510 | U16 | 1 | |
| Material interruption detection threshold | 20511 | U16 | 1 | |
| Material interruption detection delay | 20512 | U16 | 1 | |
| Pre-drive function selection | 20516 | U16 | 1 | |
| Pre-drive frequency gain | 20517 | U16 | 1 | |
| Pre-drive torque gain | 20518 | U16 | 1 | |
| Stop and brake hold frequency | 20522 | U16 | 1 | |
| Stop and brake hold time | 20523 | U16 | 1 | |
| Roll diameter calculation method selection | 20524 | U16 | 1 | |
| Maximum roll diameter | 20525 | U16 | 1 | |
| Roll shaft diameter | 20526 | U16 | 1 | |
| Initial roll diameter source selection | 20527 | U16 | 1 | |
| Initial roll diameter 1 | 20528 | U16 | 1 | |
| Initial roll diameter 2 | 20529 | U16 | 1 | |
| Initial roll diameter 3 | 20530 | U16 | 1 | |
| Roll diameter reset selection | 20531 | U16 | 1 | |
| Roll diameter change rate limit | 20534 | U16 | 1 | |
| Roll diameter change direction | 20535 | U16 | 1 | |
| Linear velocity input source | 20536 | U16 | 1 | |
| Maximum linear velocity | 20537 | U16 | 1 | |
| Keyboard digital setting of linear velocity | 20538 | U16 | 1 | |
| Roll diameter calculation minimum linear speed | 20539 | U16 | 1 | |
| Linear speed given 1 | 20540 | U16 | 1 | |
| Linear speed given 2 | 20541 | U16 | 1 | |
| Minimum frequency for roll diameter calculation | 20543 | U16 | 1 | |
| Number of pulses per turn of winding roller | 20548 | U16 | 1 | |
| Number of turns per layer | 20549 | U16 | 1 | |
| Material thickness set with numbers | 20550 | U16 | 1 | |
| Enable tension PID | 20555 | U16 | 1 | |
| Tension PID output reference source | 20556 | U16 | 1 | |
| Tension PID maximum output percentage | 20557 | U16 | 1 | |
| Tension PID feedback signal source | 20558 | U16 | 1 | |
| Tension PID keyboard feedback Set with keyboard digital | 20559 | U16 | 1 | |
| Tension PID feedback signal gain | 20560 | U16 | 1 | |
| Proportional gain P | 20561 | U16 | 1 | |
| Integral time T | 20562 | U16 | 1 | |
| AI1 measured voltage 1 | 22784 | U16 | 1 | |
| AI1 monitor voltage 1 | 22785 | U16 | 1 | |
| AI1 measured voltage 2 | 22786 | U16 | 1 | |
| AI1 monitor voltage 2 | 22787 | U16 | 1 | |
| AI1 measured voltage 3 | 22788 | U16 | 1 | |
| AI1 monitor voltage 3 | 22789 | U16 | 1 | |
| AI1 measured current 1 | 22790 | U16 | 1 | |
| AI1 monitor current 1 | 22791 | U16 | 1 | |
| AI1 measured current 2 | 22792 | U16 | 1 | |
| AI1 monitor current 2 | 22793 | U16 | 1 | |
| AI1 measured current 3 | 22794 | U16 | 1 | |
| AI1 monitor current 3 | 22795 | U16 | 1 | |
| AI2 measured voltage 1 | 22796 | U16 | 1 | |
| AI2 monitor voltage 1 | 22797 | U16 | 1 | |
| AI2 measured voltage 2 | 22798 | U16 | 1 | |
| AI2 monitor voltage 2 | 22799 | U16 | 1 | |
| AI2 measured voltage 3 | 22800 | U16 | 1 | |
| AI2 monitor voltage 3 | 22801 | U16 | 1 | |
| AI2 measured current 1 | 22802 | U16 | 1 | |
| AI2 monitor current 1 | 22803 | U16 | 1 | |
| AI2 measured current 2 | 22804 | U16 | 1 | |
| AI2 monitor current 2 | 22805 | U16 | 1 | |
| AI2 measured current 3 | 22806 | U16 | 1 | |
| AI2 monitor current 3 | 22807 | U16 | 1 | |
| AO measured voltage 1 | 22808 | U16 | 1 | |
| AO monitor voltage 1 | 22809 | U16 | 1 | |
| AO measured voltage 2 | 22810 | U16 | 1 | |
| AO monitor voltage 2 | 22811 | U16 | 1 | |
| AO measured voltage 3 | 22812 | U16 | 1 | |
| AO monitor voltage 3 | 22813 | U16 | 1 | |
| AO measured current 1 | 22814 | U16 | 1 | |
| AO monitor current 1 | 22815 | U16 | 1 | |
| AO measured current 2 | 22816 | U16 | 1 | |
| AO monitor current 2 | 22817 | U16 | 1 | |
| AO measured current 3 | 22818 | U16 | 1 | |
| AO monitor current 3 | 22819 | U16 | 1 |
| terminals | A+ and B- (Group 1), RJ45 (Group 2) |
| A/B polarity | A+ positive, B- negative |
| termination | 120 Ohm terminal resistance can be connected via DIP switch |
| connector | Screw terminals for A+/B-, RJ45 for Group 2 |
| shield/ground | Shielded twisted pair cable recommended, ground terminal PE |
| wiring notes | RS485 communication is standard. |
| max registers/read | 20 |
| response timeout | 1000 ms |
| broadcast | supported |
| protocol notes | For broadcast transmission, the slave station does not send a response message. |
| firmware register | C02.60 |
| power | S2: Single-phase 200 V-240 V 50/60 Hz; T2: Three-phase 200 V-240 V 50/60 Hz; T3: Three-phase 380 V-480 V 50/60 Hz; T6: Three-phase 660 V-690 V 50/60 Hz |
| environment | Altitude < 1000 m (derated by 1% per 100 m above 1000 m); Temperature: -10°C to +50°C (derated above 40°C, max 60°C); Humidity: 5% RH to 95% RH (no condensation); Vibration: 5.9 m/s² (0.6 G) at 9 Hz - 200 Hz; Storage temperature: -30°C to +60°C; Protection level: IP20; Pollution degree: II; Cooling method: Forced air cooling |
| accuracy | Output frequency accuracy: ±0.5% of Max Freq. |
| certifications | IEC61800-2 |
| doc revision | V1.0 (Aug.2021 / Dec.2022) |
⚠ disputed: set_frequency @ 8192 — disputed by Weintek/Tecnolog integration guides which state that frequency setting is mapped to 3000H (12288 decimal) and control command to 3001H (12289 decimal) depending on the active communication table
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.