Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Diameter | 8 | F32LE | 1 | |
| 4 .. 20 mA Max | 9 | F32LE | 1 | |
| 4 .. 20 mA Min | 10 | F32LE | 1 | |
| 4 .. 20 mA Unit | 11 | F32LE | 1 | |
| Flow in mn/sec | 16 | I32LE | 0.1 | mn/sec |
| Flow in m3n/hr | 17 | I32LE | 0.1 | m3n/hr |
| Flow in ln/min | 18 | I32LE | 0.1 | ln/min |
| Flow in SCFM | 19 | I32LE | 0.1 | SCFM |
| Flow in m3n/min | 20 | I32LE | 0.1 | m3n/min |
| Flow in sfps | 21 | I32LE | 0.1 | sfps |
| Flow in mn/sec | 24 | F32LE | 1 | mn/sec |
| Flow in m3n/hr | 25 | F32LE | 1 | m3n/hr |
| Flow in ln/min | 26 | F32LE | 1 | ln/min |
| Flow in SCFM | 27 | F32LE | 1 | SCFM |
| Flow in m3n/min | 28 | F32LE | 1 | m3n/min |
| Flow in sfps | 29 | F32LE | 1 | sfps |
| Pressure in bar | 32 | I32LE | 0.1 | bar |
| Pressure in psi | 33 | I32LE | 0.1 | psi |
| Pressure in bar | 40 | F32LE | 1 | bar |
| Pressure in psi | 41 | F32LE | 1 | psi |
| Temperature in °C | 64 | I32LE | 0.1 | °C |
| Temperature in °F | 65 | I32LE | 0.1 | °F |
| Temperature in °C | 72 | F32LE | 1 | °C |
| Temperature in °F | 73 | F32LE | 1 | °F |
| Totalizer in m3n | 128 | I32LE | 0.1 | m3n |
| Totalizer in m3n | 136 | F32LE | 1 | m3n |
⚠ NEVER USE AC POWER. THIS WILL VOID WARRANTY AND BRING PERMANENT DAMAGE TO THE ELECTRONICS. CONNECT THE M12 CONNECTOR BEFORE POWERING UP THE INSTRUMENTS. — Starkest reads only; we never write a control register.
| terminals | M12 5-pin female connector |
| A/B polarity | Pin 4 RS485 B, Pin 5 RS485 A |
| termination | The VPInstruments junction box features a jumper that can be used to enable a 120 Ohm resistor. |
| connector | M12 5-pin female connector or M12 8-pin connector |
| shield/ground | Shielded twisted pair cabling must be used. Connect shield to safety ground on one point. |
| wiring notes | Connection of a third wire between the master and slave should be done to limit the common mode voltage. |
| protocol notes | Maximum polling interval is 10ms. |
| power | 12 .. 24 VDC +-10% CLASS 2 (UL), 150 mA at 24 VDC |
| environment | Ambient temperature 0 .. 60 °C / 32 .. 140 °F, IP65 when mated to connector |
| accuracy | 0.5% FSS under calibration conditions with tubing kit, 5% FSS without tubing kit |
| certifications | CE EN 61326-1(2006) Class A, EN 61000-6-1 (2007), UL / CUL 14 AZ, Industrial Control Equipment |
| doc revision | MAN-VP-SINL-EN-2300 Last Revision Date: 21-7-2023 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.