device library

WEG CFW500 drive

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
serial_interf_status316U161
logical_status680U161
speed_in_13_bits681I161
serial_usb_control682U161
serial_usb_speed_ref683I161
dox_value695U161
aox_value_1696I161%
aox_value_2697I161%
aox_value_3698I161%

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; FC 01,02,03,04,05,06,15,16,43

bench facts as documented (unverified)
terminalsPin 14: RS485-A(-), Pin 16: RS485-B(+), Pin 18: GND
A/B polarityPin 14 is A(-), Pin 16 is B(+)
termination120 Ohm | 0.25 W resistor connected between +B and -A
connectorControl terminal (CFW500-IOS), mini-USB (CFW500-CUSB), DB9 (CFW500-CRS232)
isolationGalvanically insulated
shield/groundShielded cable with twisted pair, shield must be grounded
broadcastsupported
FC 43 device IDsupported
doc revision04
field reports — community-sourced, unverified (checked 2026-06-11)
  • The Modbus RTU telegrams for request and response cannot exceed 64 bytes. Attempting to read large blocks of registers (e.g., up to 125 registers) will fail due to this buffer limit. [source]
  • In firmware versions prior to V4.1X, attempting to read a range of registers that includes a missing or skipped parameter (e.g., reading from P0007 to P0009 where P0008 is skipped) causes the drive to return an error or nothing for all parameters in that range. Firmware V4.1X resolved this by adding support for Modbus read/write continuity even with invalid addresses in the sequence. [source]
  • confirmed: comms defaults (baud rates [9600, 19200, 38400], default baud 19200, default unit ID 1, RTU framing, parity E, stop bits 1) — confirmed by WEG CFW500 Modbus RTU User's Guide (Doc 10002253377, Rev 04) parameters P0308, P0310, and P0311
  • confirmed: supported Modbus function codes (1, 2, 3, 4, 5, 6, 15, 16, 43) — confirmed by Table 5.1 of the Modbus RTU CFW500 User's Guide
  • confirmed: physical connector options (Control terminal CFW500-IOS, mini-USB CFW500-CUSB, DB9 CFW500-CRS232) — confirmed by Section 2 of the Modbus RTU CFW500 User's Guide
  • confirmed: RS485 terminals and polarity (Pin 14 is A(-), Pin 16 is B(+), Pin 18 is GND) — confirmed by Table 2.1 of the Modbus RTU CFW500 User's Guide
  • confirmed: termination resistor (120 Ohm | 0.25 W connected between +B and -A) — confirmed by Section 3.3 of the Modbus RTU CFW500 User's Guide
  • confirmed: broadcast supported on address 0 — confirmed by Section 1.1 of the Modbus RTU CFW500 User's Guide
  • confirmed: register map summary (serial_interf_status @ 316, logical_status @ 680, speed_in_13_bits @ 681, serial_usb_control @ 682, serial_usb_speed_ref @ 683, dox_value @ 695, aox_value_1 @ 696, aox_value_2 @ 697, aox_value_3 @ 698) — confirmed by the parameter list and Modbus RTU memory map where parameter numbers map directly to 0-based Modbus addresses

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.