device library

Wilo Stratos IF-Module pump

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
set_value_holding1U160.5%
pump_command_holding40U161
operation_mode_holding42U161
bus_command_timer300U161
set_value_input400U160.5%
pump_command_input402U161
operation_mode_input10U161
test_register_700700U161

link settings as documented (unverified): RTU; default 9600 8E1; unit ID 1; Frame formats configurable via Parameter C (Menu 5.2.5.0). Default is 8,E,1 (Code 6).

⚠ When bus command timer state is RESET, writes from Modbus to the Setvalue, Pump command and Operation mode (holding registers 1, 40, 42) have no effect. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsmarked with a (-) and b (+)
A/B polaritya (-) and b (+)
terminationactivated by setting both switches (located close to connection terminals) in the position marked with a non crossed thru resistor symbol
shield/groundShield shall be connected to chassis ground on both ends of the cable as a standard.
wiring notesCharacteristic impedance of the pair shall be 120 Ohm. Wiring shall be done with real shielded twisted pairs.
protocol notesIf input register 700 read fails, try 701 (offset issue).
identification notesSoftware version is on a sticker close to mains terminal at Stratos series and can be read out at 4.4.2.0 for all other pump types.
accuracyThe flow value refers to clean water. Any additives may result in inaccurate or useless values.
doc revision2014-01-03
firmware applicabilityWILO Stratos series >= 5.09, WILO Stratos GIGA (all), WILO BL-E (all), WILO IP-E/DP-E >= 3.00, WILO IL-E/DL-E >= 4.00, WILO Helix EXCEL (all), WILO MVIE/MHIE/HELIX VE (1,1..4 kW) >= 3.00, WILO MVIE/HELIX VE (5,5..7,5 kW) >= 4.00

⚠ disputed: baud_rates: [9600] — disputed by Wilo Modbus IF-Module Guide, which states that multiple baud rates from 300 to 115200 bps are supported and configurable via Parameter A (Menu 5.2.4.0)

field reports — community-sourced, unverified (checked 2026-06-11)
  • Depending on the Modbus master/client system, a register offset of 1 may apply. If reading input register 700 (30701) fails, users should try reading 699 or 701 to detect the offset. [source]
  • Some manufacturers of automation equipment use the opposite marking of A and B compared to Wilo's A(-) and B(+) terminals, which can cause RS485 communication issues. [source]
  • confirmed: Default baud rate is 9600, default unit ID is 1, and default framing is 8,E,1 (Code 6) — confirmed by Wilo Modbus IF-Module Guide [1.1.6]
  • confirmed: When bus command timer state is RESET, writes from Modbus to the Setvalue, Pump command, and Operation mode (holding registers 1, 40, 42) have no effect — confirmed by Wilo Modbus IF-Module Guide
  • confirmed: The flow value refers to clean water and additives may result in inaccurate or useless values — confirmed by Wilo Modbus IF-Module Guide
  • confirmed: Wiring terminals are marked with a (-) and b (+) and termination is activated by setting both switches to the non-crossed-thru resistor symbol — confirmed by Wilo Modbus IF-Module Guide
  • confirmed: If input register 700 read fails, try 701 (or 699) to detect potential register offset — confirmed by Wilo Modbus IF-Module Guide

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.