Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| set_value_holding | 1 | U16 | 0.5 | % |
| pump_command_holding | 40 | U16 | 1 | |
| operation_mode_holding | 42 | U16 | 1 | |
| bus_command_timer | 300 | U16 | 1 | |
| set_value_input | 400 | U16 | 0.5 | % |
| pump_command_input | 402 | U16 | 1 | |
| operation_mode_input | 10 | U16 | 1 | |
| test_register_700 | 700 | U16 | 1 |
⚠ When bus command timer state is RESET, writes from Modbus to the Setvalue, Pump command and Operation mode (holding registers 1, 40, 42) have no effect. — Starkest reads only; we never write a control register.
| terminals | marked with a (-) and b (+) |
| A/B polarity | a (-) and b (+) |
| termination | activated by setting both switches (located close to connection terminals) in the position marked with a non crossed thru resistor symbol |
| shield/ground | Shield shall be connected to chassis ground on both ends of the cable as a standard. |
| wiring notes | Characteristic impedance of the pair shall be 120 Ohm. Wiring shall be done with real shielded twisted pairs. |
| protocol notes | If input register 700 read fails, try 701 (offset issue). |
| identification notes | Software version is on a sticker close to mains terminal at Stratos series and can be read out at 4.4.2.0 for all other pump types. |
| accuracy | The flow value refers to clean water. Any additives may result in inaccurate or useless values. |
| doc revision | 2014-01-03 |
| firmware applicability | WILO Stratos series >= 5.09, WILO Stratos GIGA (all), WILO BL-E (all), WILO IP-E/DP-E >= 3.00, WILO IL-E/DL-E >= 4.00, WILO Helix EXCEL (all), WILO MVIE/MHIE/HELIX VE (1,1..4 kW) >= 3.00, WILO MVIE/HELIX VE (5,5..7,5 kW) >= 4.00 |
⚠ disputed: baud_rates: [9600] — disputed by Wilo Modbus IF-Module Guide, which states that multiple baud rates from 300 to 115200 bps are supported and configurable via Parameter A (Menu 5.2.4.0)
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.