device library

Xantrex Freedom SW inverter-charger

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Device Name0U161
FGA Number10U161
Unique ID Number20U161
Firmware Version30U161
Modbus Address40U161
Device Number41U161
System Instance42U161
Hardware Serial Number43U161
Configuration Status53U161
Configuration Refresh Counter54U32BE1
Device State64U161
Device Present65U161
Inverter Enabled66U161
Charger Enabled67U161
Active Faults Flag68U161
Active Warnings Flag69U161
Charge Mode Status70U161
Fault Bitmap 071U161
Fault Bitmap 172U161
Fault Bitmap 273U161
Warning Bitmap 074U161
Inverter Status75U161
Configuration Errors76U32BE1
Battery Voltage78U32BE0.001V
Battery Current80I32BE0.001A
Battery Power82I32BE1W
Battery Temperature84U160.01deg C
Charger Status85U161
Invert DC Current86U32BE0.001A
Invert DC Power88U32BE1W
Charge DC Current90U32BE0.001A
Charge DC Power92U32BE1W
Charge DC Power Percentage94U161%
AC1 Frequency95U160.01Hz
AC1 Voltage96U32BE0.001V
AC1 Input Current98U32BE0.001A
AC1 Input Power100U32BE1W
AC1 Input Power - Apparent102U32BE1VA
AC1 Voltage Qualified112U161
AC1 Frequency Qualified113U161
AC1 Qualified Duration114U32BE1s
Load AC Voltage120U32BE0.001V
Load AC Current130U32BE0.001A
Load AC Power132U32BE1W
Load AC Power - Apparent138U32BE1VA
Load AC Frequency140U160.01Hz
Energy From Battery This Hour144U32BE0.001kWh
Battery Discharge Active This Hour146U32BE1s
Energy From Battery Today148U32BE0.001kWh
Battery Discharge Active Today150U32BE1s
Energy From Battery This Week152U32BE0.001kWh
Battery Discharge Active This Week154U32BE1s
Energy From Battery This Month156U32BE0.001kWh
Battery Discharge Active This Month158U32BE1s
Energy From Battery This Year160U32BE0.001kWh
Battery Discharge Active This Year162U32BE1s
Energy From Battery Lifetime164U32BE0.001kWh
Battery Discharge Active Lifetime166U32BE1s
Energy To Battery This Hour168U32BE0.001kWh
Battery Charge Active This Hour170U32BE1s
Energy To Battery Today172U32BE0.001kWh
Battery Charge Active Today174U32BE1s
Energy To Battery This Week176U32BE0.001kWh
Battery Charge Active This Week178U32BE1s
Energy To Battery This Month180U32BE0.001kWh
Battery Charge Active This Month182U32BE1s
Energy To Battery This Year184U32BE0.001kWh
Battery Charge Active This Year186U32BE1s
Energy To Battery Lifetime188U32BE0.001kWh
Battery Charge Active Lifetime190U32BE1s
AC1 Input Energy This Hour192U32BE0.001kWh
AC1 Input Active This Hour194U32BE1s
AC1 Input Energy Today196U32BE0.001kWh
AC1 Input Active Today198U32BE1s
AC1 Input Energy This Week200U32BE0.001kWh
AC1 Input Active This Week202U32BE1s
AC1 Input Energy This Month204U32BE0.001kWh
AC1 Input Active This Month206U32BE1s
AC1 Input Energy This Year208U32BE0.001kWh
AC1 Input Active This Year210U32BE1s
AC1 Input Energy Lifetime212U32BE0.001kWh
AC1 Input Active Lifetime214U32BE1s
Load Output Energy This Hour216U32BE0.001kWh
Load Output Active This Hour218U32BE1s
Load Output Energy Today220U32BE0.001kWh
Load Output Active Today222U32BE1s
Load Output Energy This Week224U32BE0.001kWh
Load Output Active This Week226U32BE1s
Load Output Energy This Month228U32BE0.001kWh
Load Output Active This Month230U32BE1s
Load Output Energy This Year232U32BE0.001kWh
Load Output Active This Year234U32BE1s
Load Output Energy Lifetime236U32BE0.001kWh
Load Output Active Lifetime238U32BE1s
Inverter Enable/Disable240U161
Charger Enable/Disable241U161
Force Charger State242U161
Operating Mode243U161
Reset244U161
Clear245U161
Search Mode246U161
Inverter Mode247U161
Charge Cycle248U161
Maximum Charge Rate249U161%
Equalize Now250U161
Charger Override Enable/Disable251U161
Default Battery Temperature252U161
Battery Type253U161
Nominal Battery Voltage254U32BE0.001V
Battery Bank Capacity256U161Ah
Battery Temperature Coefficient257U16-1mV/deg C
Recharge Voltage258U32BE0.001V
Low Battery Cut Out260U32BE0.001V
Low Battery Cut Out Delay262U160.01s
AC1 Breaker Size263U160.01A
High Battery Cut Out264U32BE0.001V
Maximum Search Watts266U161W
Search Delay267U160.01s
Equalize Voltage Set Point268U32BE0.001V
Equalize Support270U161
Bulk/Boost Voltage Set Point272U32BE0.001V
Absorption Voltage Set Point274U32BE0.001V
Absorption Time276U160.016667min
Float Voltage Set Point278U32BE0.001V
AC1 Low Voltage286U32BE0.001V
AC Qualify Time288U160.01s
AC1 High Voltage290U32BE0.001V
AC1 Low Frequency292U160.01Hz
AC1 High Frequency293U160.01Hz
Identify Enable294U161
Generator Support Enable296U161
Generator Support Amps298U32BE0.001A
Refresh Configuration Data300U161
AC Output Association (Loads)301U161
AC Input Association (Generator )302U161
DC Association (Battery)303U161

link settings as documented (unverified): Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. To confirm that a Modbus Register is correctly written, you should read it back and compare it with the expected value.

⚠ UNINTENDED OPERATION: The use of this product with Modbus communications requires expertise in the design, operation, and programming of the device. Only qualified persons should program, install, alter, and commission this product. LOSS OF CONTROL: Do not assign the same address to two Modbus devices. The entire serial bus may behave unexpectedly if the master device cannot communicate with all the slave devices on the bus. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
protocol notesModbus does not provide an error response when data written to a Modbus Register is out of range or invalid.
serial register0x002B
firmware register0x001E
identification notesDevice Name is at 0x0000, FGA Number is at 0x000A, Unique ID Number is at 0x0014.
doc revisionRevision A.4
firmware applicabilityThe Conext Freedom SW Device Modbus map applies to the following products: 815-2012, 815-2024, 815-2524-02, 815-3012, 815-3024, 815-3524-02.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.