Yaskawa V1000 drive (MEMOBUS/Modbus)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
drive_status_132U161
fault_contents_133U161
data_link_status34U161
frequency_reference35U160.01Hz
output_frequency36U160.01Hz
output_voltage_reference37U160.1V
output_current38U160.01A
output_power39U160.1kW
torque_reference40I160.1%
fault_contents_241U161
alarm_contents_142U161
input_terminal_status43U161
drive_status_244U161
output_terminal_status45U161
frequency_reference_bias47I160.1%
dc_bus_voltage49U161V
torque_monitor50I161%
pid_feedback56U160.1%
pid_input57I160.1%
pid_output58I160.1%
output_frequency_rpm62U161r/min
output_frequency_percent63U160.01%
drive_status75U161
cumulative_operation_time_10h152U1610h
cumulative_operation_time_1h153U161
cooling_fan_operation_time_10h154U1610h
cooling_fan_operation_time_1h155U161
drive_rated_current171U160.01A
motor_speed172U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 31; FC 03,08,16; MEMOBUS/Modbus (using RTU mode only)

bench facts as documented (unverified)
terminalsR+, R-, S+, S-, IG
terminationBuilt-in terminating resistance enabled/disabled via DIP switch S2
connectorRemovable terminal block
max registers/read16
response timeout2000 ms
broadcastsupported
model register52
power200 V Class, Three-Phase Input: 0.1 to 18.5 kW; 200 V Class, Single-Phase Input: 0.1 to 3.7 kW; 400 V Class, Three-Phase Input: 0.2 to 18.5 kW
environmentAmbient Temperature: IP20/NEMA Type 1: -10 to +40 °C, IP20/IP00 Open-Chassis: -10 to +50 °C. Humidity: 95% RH or less. Altitude: Up to 1000 m without derating.
doc revisionSIEP C710606 16D

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.