Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Device type0I161
Measuring value sensor 1T1I160.1°C
Measuring value sensor 2T2I160.1°C
Measuring value sensor 3T3I160.1°C
Measuring value sensor 4T4I160.1°C
Measuring value sensor 5T5I160.1°C
Measuring value sensor 6T6I160.1°C
Error7U161
Measuring value- counter8U161
Status Alarm K19U161
Status Alarm K110U161
Status Alarm K111U161
Status Alarm K212U161
Status Alarm K213U161
Status Alarm K214U161
Status Alarm K315U161
Status Alarm K316U161
Status Alarm K317U161
Status Alarm K418U161
Status Alarm K419U161
Status Alarm K420U161
Status Alarm K521U161
Status Alarm K522U161
Status Alarm K523U161
Status Alarm K624U161
Status Alarm K625U161
Status Alarm K626U161
Status Alarm K727U161
Status Alarm K728U161
Status Alarm K729U161
Status relay K1/K230U161
Status relay K3/K431U161
Status relay K5/K632U161
Status relay K733U161
Analog output U134U160.01V
Analog output I135U160.01mA
Analog output U236U160.01V
Analog output I237U160.01mA
RS485 - protocol38I161
RS485 - address39U161
RS485 - baud rate40I161
RS485 - parity41I161
RS485 - stop bits42I161
Smallest measured value from sensor 1T43I160.1°C
Smallest measured value from sensor 2T44I160.1°C
Smallest measured value from sensor 3T45I160.1°C
Smallest measured value from sensor 4T46I160.1°C
Smallest measured value from sensor 5T47I160.1°C
Smallest measured value from sensor 6T48I160.1°C
Largest measured value from sensor 1T49I160.1°C
Largest measured value from sensor 2T50I160.1°C
Largest measured value from sensor 3T51I160.1°C
Largest measured value from sensor 4T52I160.1°C
Largest measured value from sensor 5T53I160.1°C
Largest measured value from sensor 6T54I160.1°C
Counter operating hour55U32LE1h
Serial number57U32LE1
Hardware-Version59U161
Firmware-Version, Application60U161
Firmware-Version, Bootloader61U161

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.