verified connector library

ABB AquaMaster 3 flowmeter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
flow_rate5016F32BE1User flow units
flow_percent5018F32BE1%
pressure5024F32BE1User units
pressure_percent5026F32BE1%
left_electrode_impedance5028F32BE1kOhm
right_electrode_impedance5030F32BE1kOhm
coil_current5038F32BE1A
pulse_output_frequency5040F32BE1Hz
calibrated_velocity5050F32BE1m/s
voltage_reference5056F32BE1V
sig_a_volts5062F32BE1V
sig_b_volts5064F32BE1V
external_power_voltage5068F32BE1V
internal_3v8_voltage5070F32BE1V
internal_3v2_voltage5072F32BE1V
totaliser_forward12002U32BE1
totaliser_reverse12004U32BE1
totaliser_net12006U32BE1
totaliser_tariff_a12008U32BE1
totaliser_tariff_b12010U32BE1
external_power_status1020U161
internal_power_status1022U161

link settings as documented (unverified): RTU; FC 01,02,03,04,05,06,15,16; AquaMaster 3 RS485 MODBUS option implements the MODBUS over Serial Line protocol. Low power mode after 10s inactivity requires 1 retry to wake up within 1s.

bench facts as documented (unverified)
connectorRS485
wiring notesRS485 MODBUS option
response timeout1000 ms
protocol notesTurnaround delay: 800ms. Low power state after 10s inactivity requires 1 retry to wake up.
identification notesTransmitterUniqueID at RO 32-Bit register 4013
powerDesigned for low power consumption so that it can be used with battery or renewable energy supplies (as well as with mains power).
certificationsUKAS Calibration Laboratory No. 0255
doc revisionCOI/FET2XX/MOD/TBL–EN
firmware applicabilityWAJC2103 v01.00.00 or above

generated by gemini:gemini-3.5-flash · harvested from https://library.e.abb.com/public/91eead459bb0d349c12577fc0033d2b5/COI_FET2XX_MOD_TBL-EN.pdf (ABB); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.