ABB TRIO-20.0/27.6-TL-OUTD string inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
inverter_global_state123U161Decimal
inverter_state124U161Decimal
inverter_dcdc_channel_1_state125U161Decimal
inverter_dcdc_channel_2_state126U161Decimal
inverter_alarm_state127U161Decimal
inverter_daily_energy131F32BE1Wh
inverter_total_energy133F32BE1kWh
inverter_partial_energy135F32BE1kWh
inverter_week_energy137F32BE1kWh
inverter_monthly_energy139F32BE1kWh
inverter_yearly_energy141F32BE1kWh
inverter_grid_voltage143F32BE1V
inverter_grid_current145F32BE1A
inverter_grid_power147F32BE1W
inverter_frequency149F32BE1Hz
inverter_input_1_power151F32BE1W
inverter_input_1_voltage153F32BE1V
inverter_input_1_current155F32BE1A
inverter_input_2_power157F32BE1W
inverter_input_2_voltage159F32BE1V
inverter_input_2_current161F32BE1A
inverter_temperature163F32BE1°C
inverter_booster_temperature165F32BE1°C
inverter_isolation_resistance167F32BE1MΩ
inverter_cos_phi171F32BE1N/A
heartbeat_counter299U161Decimal
inverter_grid_reactive_power_holding300F32BE1VAR
inverter_grid_voltage_holding302F32BE1V
inverter_grid_power_holding304F32BE1W
inverter_grid_current_holding306F32BE1A

link settings as documented (unverified): RTU; default 19200 8N1; FC 03,04,06,16; Interface: RS-485 (half duplex). Start bit: 1, Stop bit: 1, Parity: No parity, Data bits: 8. Default baud rate is 9600 on USA and Japan versions, and 19200 on Europe versions.

bench facts as documented (unverified)
terminalsRS-485 serial line
broadcastsupported
model register115
serial register103
identification notesModel identifier register is 115 (0-based). Serial number registers are 103 to 108 (0-based).
doc revision1.6
firmware applicabilityMinimum Inverter Update Version: 1542C for Europe version; 1542D for USA and Japan version

generated by gemini:gemini-3.5-flash · harvested from https://library.e.abb.com/public/c4f8b5d142a7488da678076c3ae01caf/Modbus_RTU_register_map_for_TRIO-20.0(27.6)-TL-OUTD_Revision_1.6.pdf (ABB); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.