Advantech ADAM-4017+/4018/4019 I/O

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
analog_input_ch00I161
analog_input_ch11I161
analog_input_ch22I161
analog_input_ch33I161
analog_input_ch44I161
analog_input_ch55I161
analog_input_ch66I161
analog_input_ch77I161

link settings as documented (unverified): RTU; Supported Protocols: ASCII command and Modbus/RTU

bench facts as documented (unverified)
connector2 x plug-in terminal block (#14 ~ 22 AWG)
isolation3,000 VDC
wiring notesBuilt-in TVS/ESD Protection
protocol notesWatchdog Timer: System (1.6 second) & Communication
powerUnregulated 10 ~ 30 VDC. Power Consumption: ADAM-4017+: 1.2 W @ 24 VDC; ADAM-4018+: 0.8 W @ 24 VDC; ADAM-4019+: 1.0 W @ 24 VDC
environmentOperating Humidity: 5 ~ 95% RH, Operating Temperature: -10 ~ 70°C (14 ~ 158°F), Storage Temperature: -25 ~ 85°C (-13 ~ 185°F)
accuracyVoltage mode: ±0.1% or better, Current mode: ±0.2% or better, Resolution: 16-bit, Sampling Rate: 10 sample/second (total), CMR @ 50/60 Hz: 120 dB, NMR @ 50/60 Hz: 100 dB, Span Drift: ±25 ppm/°C (Typical), Zero Drift: ±6 μV/°C
certificationsCE, FCC, RoHS
doc revisionLast updated: 22-Sep-2023
field reports — community-sourced, unverified (checked 2026-06-11)
  • ADAM-4000 series modules are typically shipped with the Advantech ASCII protocol enabled by default. To use Modbus RTU, the user must manually switch the protocol using the Advantech Adam/Apax .NET Utility. [source]
  • confirmed: Supported Protocols: ASCII command and Modbus/RTU — confirmed by Advantech ADAM-4000 Series User Manual [1.1.4]
  • confirmed: Accuracy (Voltage mode: ±0.1% or better, Current mode: ±0.2% or better), Resolution (16-bit), Sampling Rate (10 sample/second total), CMR (120 dB), NMR (100 dB), Span Drift (±25 ppm/°C), Zero Drift (±6 μV/°C) — confirmed by Advantech ADAM-4017+/4018+/4019+ Datasheet
  • confirmed: Power Consumption (ADAM-4017+: 1.2 W @ 24 VDC; ADAM-4018+: 0.8 W @ 24 VDC; ADAM-4019+: 1.0 W @ 24 VDC) — confirmed by Advantech ADAM-4017+/4018+/4019+ Datasheet
  • confirmed: Operating Humidity (5 ~ 95% RH), Operating Temperature (-10 ~ 70°C), Storage Temperature (-25 ~ 85°C) — confirmed by Advantech ADAM-4017+/4018+/4019+ Datasheet
  • confirmed: Isolation (3,000 VDC) and Connectors (2 x plug-in terminal block #14 ~ 22 AWG) — confirmed by Advantech ADAM-4017+/4018+/4019+ Datasheet
  • confirmed: Watchdog Timer (System 1.6 second & Communication) — confirmed by Advantech ADAM-4017+/4018+/4019+ Datasheet
  • confirmed: Analog input channels AI0 to AI7 mapped to 0-based Modbus holding register offsets 0 to 7 (registers 40001 to 40008) — confirmed by ADAM-4000 Series User Manual Modbus Mapping Table

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.