verified connector library

Algodue UPM209 network analyzer

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
phase_1_n_voltage4096F32BE1V
phase_2_n_voltage4098F32BE1V
phase_3_n_voltage4100F32BE1V
line_12_voltage4102F32BE1V
line_23_voltage4104F32BE1V
line_31_voltage4106F32BE1V
system_voltage4108F32BE1V
phase_1_current4110F32BE1A
phase_2_current4112F32BE1A
phase_3_current4114F32BE1A
neutral_current4116F32BE1A
system_current4118F32BE1A
phase_1_active_power4120F32BE1W
phase_2_active_power4122F32BE1W
phase_3_active_power4124F32BE1W
system_active_power4126F32BE1W
phase_1_apparent_power4128F32BE1VA
phase_2_apparent_power4130F32BE1VA
phase_3_apparent_power4132F32BE1VA
system_apparent_power4134F32BE1VA
phase_1_reactive_power4136F32BE1var
phase_2_reactive_power4138F32BE1var
phase_3_reactive_power4140F32BE1var
system_reactive_power4142F32BE1var
phase_1_power_factor4144F32BE1
phase_2_power_factor4146F32BE1
phase_3_power_factor4148F32BE1
system_power_factor4150F32BE1
frequency4186F32BE1Hz
phase_1_imported_active_energy5120F32BE1Wh
phase_1_exported_active_energy5122F32BE1Wh
phase_2_imported_active_energy5124F32BE1
phase_2_exported_active_energy5126F32BE1
phase_3_imported_active_energy5128F32BE1
phase_3_exported_active_energy5130F32BE1
system_imported_active_energy5132F32BE1Wh
system_exported_active_energy5134F32BE1Wh

link settings as documented (unverified): RTU/ASCII/TCP; baud 300/600/1200/2400/4800/9600/19200/38400/57600; unit ID 1; FC 03,04,16; Supports RTU mode (8N1), ASCII mode (7E2), and TCP mode.

⚠ If CT ratio, PT ratio, wiring mode or current full scale is modified, the instrument will reset all MIN/MAX values, all DMD values, and all energy counters. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsMeasuring terminals (A & V): 1/5A CT model: 1.5 ... 6 mm2, 80A model: 1.5 ... 35 mm2, Rogowski model: 1.5 ... 6 mm2. Terminals for digital output, AUX input, RS485 port: 0.14 ... 2.5 mm2
A/B polarityL1 of the voltage input = L1 of the amperometric input
terminationTerminal resistances (RT=120...150Ω) must be installed on the converter side and on the last instrument connected along the line.
isolationRS485 optoisolated
shield/groundShielded cable with two twisted signal conductors should be used under strong electromagnetic disturbances.
max registers/read127
broadcastsupported
protocol notesHighest number of registers read with a single command: RTU mode: 127 registers, ASCII mode: 63 registers, TCP mode: 256 bytes. Broadcast supported only with register $2040.
model register8202
serial register8192
firmware register8198
power85...265 VAC / 110 VDC ±15%
environmentOperating temperature: -25°C to +55°C, Max humidity: 80% (no condensation), Altitude: up to 2000 m
accuracyVoltage: ±0.2% reading, Current: ±0.4% reading, Power: ±0.5% reading, Active energy: Class 1, Reactive energy: Class 2
certificationsCE, 89/366/EEC, 73/23/EEC, 2014/30/EU, 2014/35/EU, EN 61010-1, EN 61010-2-030, EN 61010-2-032, EN 61326-1
doc revisionEd2111

generated by gemini:gemini-3.5-flash · harvested from https://www.algodue.com/wp-content/uploads/2022/06/UPM209_User-manual-Ed2111.pdf (Algodue Elettronica); manual-faithful — the document's claims, panel risk: LOW — panel concurs, no field disagreements; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.