Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| phase_1_n_voltage | 4096 | F32BE | 1 | V |
| phase_2_n_voltage | 4098 | F32BE | 1 | V |
| phase_3_n_voltage | 4100 | F32BE | 1 | V |
| line_12_voltage | 4102 | F32BE | 1 | V |
| line_23_voltage | 4104 | F32BE | 1 | V |
| line_31_voltage | 4106 | F32BE | 1 | V |
| system_voltage | 4108 | F32BE | 1 | V |
| phase_1_current | 4110 | F32BE | 1 | A |
| phase_2_current | 4112 | F32BE | 1 | A |
| phase_3_current | 4114 | F32BE | 1 | A |
| neutral_current | 4116 | F32BE | 1 | A |
| system_current | 4118 | F32BE | 1 | A |
| phase_1_active_power | 4120 | F32BE | 1 | W |
| phase_2_active_power | 4122 | F32BE | 1 | W |
| phase_3_active_power | 4124 | F32BE | 1 | W |
| system_active_power | 4126 | F32BE | 1 | W |
| phase_1_apparent_power | 4128 | F32BE | 1 | VA |
| phase_2_apparent_power | 4130 | F32BE | 1 | VA |
| phase_3_apparent_power | 4132 | F32BE | 1 | VA |
| system_apparent_power | 4134 | F32BE | 1 | VA |
| phase_1_reactive_power | 4136 | F32BE | 1 | var |
| phase_2_reactive_power | 4138 | F32BE | 1 | var |
| phase_3_reactive_power | 4140 | F32BE | 1 | var |
| system_reactive_power | 4142 | F32BE | 1 | var |
| phase_1_power_factor | 4144 | F32BE | 1 | |
| phase_2_power_factor | 4146 | F32BE | 1 | |
| phase_3_power_factor | 4148 | F32BE | 1 | |
| system_power_factor | 4150 | F32BE | 1 | |
| frequency | 4186 | F32BE | 1 | Hz |
| phase_1_imported_active_energy | 5120 | F32BE | 1 | Wh |
| phase_1_exported_active_energy | 5122 | F32BE | 1 | Wh |
| phase_2_imported_active_energy | 5124 | F32BE | 1 | |
| phase_2_exported_active_energy | 5126 | F32BE | 1 | |
| phase_3_imported_active_energy | 5128 | F32BE | 1 | |
| phase_3_exported_active_energy | 5130 | F32BE | 1 | |
| system_imported_active_energy | 5132 | F32BE | 1 | Wh |
| system_exported_active_energy | 5134 | F32BE | 1 | Wh |
⚠ If CT ratio, PT ratio, wiring mode or current full scale is modified, the instrument will reset all MIN/MAX values, all DMD values, and all energy counters. — Starkest reads only; we never write a control register.
| terminals | Measuring terminals (A & V): 1/5A CT model: 1.5 ... 6 mm2, 80A model: 1.5 ... 35 mm2, Rogowski model: 1.5 ... 6 mm2. Terminals for digital output, AUX input, RS485 port: 0.14 ... 2.5 mm2 |
| A/B polarity | L1 of the voltage input = L1 of the amperometric input |
| termination | Terminal resistances (RT=120...150Ω) must be installed on the converter side and on the last instrument connected along the line. |
| isolation | RS485 optoisolated |
| shield/ground | Shielded cable with two twisted signal conductors should be used under strong electromagnetic disturbances. |
| max registers/read | 127 |
| broadcast | supported |
| protocol notes | Highest number of registers read with a single command: RTU mode: 127 registers, ASCII mode: 63 registers, TCP mode: 256 bytes. Broadcast supported only with register $2040. |
| model register | 8202 |
| serial register | 8192 |
| firmware register | 8198 |
| power | 85...265 VAC / 110 VDC ±15% |
| environment | Operating temperature: -25°C to +55°C, Max humidity: 80% (no condensation), Altitude: up to 2000 m |
| accuracy | Voltage: ±0.2% reading, Current: ±0.4% reading, Power: ±0.5% reading, Active energy: Class 1, Reactive energy: Class 2 |
| certifications | CE, 89/366/EEC, 73/23/EEC, 2014/30/EU, 2014/35/EU, EN 61010-1, EN 61010-2-030, EN 61010-2-032, EN 61326-1 |
| doc revision | Ed2111 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.