Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| logic_command | 8192 | U16 | 1 | |
| speed_reference | 8193 | U16 | 0.1 | Hz |
| logic_status | 8448 | U16 | 1 | |
| drive_error_codes | 8449 | U16 | 1 | |
| feedback | 8451 | U16 | 0.1 | Hz |
| output_freq | 1 | U16 | 0.1 | Hz |
| commanded_freq | 2 | U16 | 0.1 | |
| output_current | 3 | U16 | 0.01 | |
| output_voltage | 4 | U16 | 0.1 | |
| dc_bus_voltage | 5 | U16 | 1 | |
| drive_status | 6 | U16 | 1 | |
| fault_1_code | 7 | U16 | 1 | |
| fault_2_code | 8 | U16 | 1 | |
| fault_3_code | 9 | U16 | 1 | |
| control_source | 12 | U16 | 1 | |
| contrl_in_status | 13 | U16 | 1 | |
| dig_in_status | 14 | U16 | 1 | |
| comm_status | 15 | U16 | 1 | |
| elapsed_run_time | 18 | U16 | 10 | |
| analog_in_0_10v | 20 | U16 | 0.1 | |
| analog_in_4_20ma | 21 | U16 | 0.1 | |
| drive_temp | 22 | U16 | 1 |
⚠ Risk of equipment damage exists if writing parameter data to Non-Volatile Storage (NVS) frequently. NVS will quickly exceed its life cycle. — Starkest reads only; we never write a control register.
| terminals | Control Terminal 16, RJ45 DSI port pins 4 and 5 |
| A/B polarity | TxRxD+, TxRxD- |
| termination | 120 ohm resistor at each end of the network cable |
| connector | RJ45 |
| isolation | Network Common is internally tied to I/O Terminal 04 (Digital Common) |
| shield/ground | The shield should be grounded at ONLY ONE location. |
| wiring notes | Only pins 4 and 5 on the RJ45 plug should be wired. |
| protocol notes | Modbus devices can be 0-based or 1-based. Register addresses may need to be offset by +1 depending on the master. |
| identification notes | To access drive parameters, the Modbus register address equals the parameter number. |
| power | 120V AC 1-Phase, 240V AC 1-Phase, 240V AC 3-Phase, 480V AC 3-Phase |
| environment | Ambient Operating Temperature: -10°C to 40°C (0 mm clearance) or 50°C (25 mm clearance). Storage: -40°C to +85°C, 0% to 95% RH non-condensing. |
| certifications | UL, CE |
| doc revision | Publication 22F-UM001D-EN-E |
| firmware applicability | FRN 1.xx - 2.xx |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.