Autonics TK series PID controller (RS485 models)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
pv1000I161℃/℉/-
decimal_point_location1001U161
indicator_unit1002U161
sv_setting_value_read1003I161℃/℉/-
heating_side_mv_read1004U160.1%
cooling_side_mv_read1005U160.1%
indicator_status_word1006U161
heater_current_value_monitoring1007U160.1
sv_set_value0I161℃/℉/-
heating_mv1U160.1%
cooling_mv2U160.1%
auto_manual_control3U161
control_output_run_stop50U161
multi_sv_number51U161
heater_current_monitoring52U160.1A
alarm_output_1_low_limit53I161℃/℉/-
alarm_output_1_high_limit54I161℃/℉/-
alarm_output_2_low_limit55I161℃/℉/-
alarm_output_2_high_limit56I161℃/℉/-
sv_057I161℃/℉/-
sv_158I161℃/℉/-
sv_259I161℃/℉/-
sv_360I161℃/℉/-
alarm_output_3_low_limit61I161℃/℉/-
alarm_output_3_high_limit62I161℃/℉/-

link settings as documented (unverified): RTU; default 9600 8N2; unit ID 1; FC 01,02,03,04,05,06,16

bench facts as documented (unverified)
terminalsAWG 20 (0.50mm²) screw bolt on terminal block
A/B polarityPlease wire properly after checking the terminal polarity when connecting temperature sensor.
response timeout20 ms
broadcastnot supported
model register300105
serial register300101
firmware register300103
doc revisionMCT-TKC1-V01.7-1701EN
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults (baud_rates: [2400, 4800, 9600, 19200, 38400], default_baud: 9600, default_unit_id: 1, framing: ['RTU'], parity: 'N', stop_bits: 2) — confirmed by Autonics TK Series User Manual for Communication (MCT-TKC1-V01.7-1701EN) and plc247.com integration guide
  • confirmed: identification registers (firmware_register: 300103, model_register: 300105, serial_register: 300101) — confirmed by Autonics TK Series User Manual for Communication (MCT-TKC1-V01.7-1701EN) Read Input Registers (Func 04) table
  • confirmed: physical wiring and terminals (AWG 20 screw bolt on terminal block, check polarity when connecting temperature sensor) — confirmed by Autonics TK Series User Manual for Communication (MCT-TKC1-V01.7-1701EN) safety precautions and wiring specifications
  • confirmed: quirks (broadcast not supported, response timeout default 20ms) — confirmed by Autonics TK Series User Manual for Communication (MCT-TKC1-V01.7-1701EN) and plc247.com integration guide
  • confirmed: register map summary (pv @ 1000, decimal_point_location @ 1001, sv_set_value @ 0, heating_mv @ 1, cooling_mv @ 2, auto_manual_control @ 3) — confirmed by Autonics TK Series User Manual for Communication (MCT-TKC1-V01.7-1701EN) Modbus Mapping Table

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.