verified connector library

Banner SureCross DX85 remote I/O

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
discrete_in_10U161
discrete_in_21U161
discrete_in_32U161
discrete_in_43U161
analog_in_14U161mA/V
analog_in_25U161mA/V
device_message7U161
discrete_out_18U161
discrete_out_29U161
discrete_out_310U161
discrete_out_411U161
analog_out_112U161mA/V
analog_out_213U161mA/V
control_message14U161

link settings as documented (unverified): RTU; default 19200 8N1; unit ID 1; Baud rate and parity are configured via internal DIP switches. Slave ID is configured via rotary dials.

⚠ Do not use this device for personnel protection. Using this device for personnel protection could result in serious injury or death. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsExternal terminals for C models, 5-pin M12 male quick-disconnect connector for non-C models
A/B polarityRS485 / D1 / B / + and RS485 / D0 / A / -
connector5-pin M12 male or external terminals
shield/groundComms Ground on Pin 5 of M12
power10 V DC to 30 V DC (Outside the USA: 12 V DC to 24 V DC, ± 10%). Consumption: Less than 1.4 W (60 mA) at 24 V DC.
environmentOperating temperature: -40 °C to +85 °C (Electronics), -20 °C to +80 °C (LCD). 95% max relative humidity (non-condensing). IP67/NEMA 6 or IP20/NEMA 1 depending on model.
accuracy0.1% of full scale +0.01% per °C for analog inputs and outputs
certificationsUL Listed
doc revision131629 Rev. I
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults (baud rate 19200, no parity, 1 stop bit, Modbus RTU) — confirmed by SureCross DX85 Modbus RTU Remote I/O Device Datasheet (p/n 131599 / 131629) [1.2.2]
  • confirmed: physical connector and terminals (5-pin M12 male or external terminals for C models) — confirmed by DX85 Modbus RTU Remote IO (4422) Device Manual (p/n 131629)
  • confirmed: RS485 polarity (RS485 / D1 / B / + and RS485 / D0 / A / -) — confirmed by Sure Cross DX85 Modbus RTU Remote I/O Device Manual (p/n 131629)
  • confirmed: shield ground (Comms Ground on Pin 5 of M12) — confirmed by Sure Cross DX85 Modbus RTU Remote I/O Device Manual (p/n 131629)
  • confirmed: analog accuracy (0.1% of full scale +0.01% per °C) — confirmed by DX85 Modbus RTU Remote IO (4422) Device Manual (p/n 131629)
  • confirmed: register map (discrete_in_1 @ 0, discrete_in_2 @ 1, discrete_in_3 @ 2, discrete_in_4 @ 3, analog_in_1 @ 4, analog_in_2 @ 5, device_message @ 7, discrete_out_1 @ 8, discrete_out_2 @ 9, discrete_out_3 @ 10, discrete_out_4 @ 11, analog_out_1 @ 12, analog_out_2 @ 13, control_message @ 14) — confirmed by DX85 Modbus RTU Remote IO (4422) Device Manual (p/n 131629)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.