verified connector library

Banner SureCross DX85 remote I/O

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
discrete_in_10U161
discrete_in_21U161
discrete_in_32U161
discrete_in_43U161
analog_in_14U161mA/V
analog_in_25U161mA/V
device_message7U161
discrete_out_18U161
discrete_out_29U161
discrete_out_310U161
discrete_out_411U161
analog_out_112U161mA/V
analog_out_213U161mA/V
control_message14U161

link settings as documented (unverified): RTU; default 19200 8N1; unit ID 1; Baud rate and parity are configured via internal DIP switches. Slave ID is configured via rotary dials.

⚠ Do not use this device for personnel protection. Using this device for personnel protection could result in serious injury or death. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsExternal terminals for C models, 5-pin M12 male quick-disconnect connector for non-C models
A/B polarityRS485 / D1 / B / + and RS485 / D0 / A / -
connector5-pin M12 male or external terminals
shield/groundComms Ground on Pin 5 of M12
power10 V DC to 30 V DC (Outside the USA: 12 V DC to 24 V DC, ± 10%). Consumption: Less than 1.4 W (60 mA) at 24 V DC.
environmentOperating temperature: -40 °C to +85 °C (Electronics), -20 °C to +80 °C (LCD). 95% max relative humidity (non-condensing). IP67/NEMA 6 or IP20/NEMA 1 depending on model.
accuracy0.1% of full scale +0.01% per °C for analog inputs and outputs
certificationsUL Listed
doc revision131629 Rev. I

generated by gemini:gemini-3.5-flash · harvested from https://info.bannerengineering.com/cs/groups/public/documents/literature/131629.pdf (Banner Engineering); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.