Bronkhorst EL-FLOW/IN-FLOW digital instruments (Modbus slave)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
measure32U161%
setpoint33U161%
analog_input35U161
control_mode36U161
temperature_u161063U161
counter_value_u163329U161
capacity33128F32BE1
fmeasure41216F32BE1
fsetpoint41240F32BE1
temperature41272F32BE1
counter_value59400F32BE1
counter_limit59416F32BE1
valve_output61960U32BE1
density_actual62584F32BE1

link settings as documented (unverified): RTU/ASCII/TCP; default 19200 8E1; unit ID 1; FC 03,06,16,08,17; Modbus RTU and ASCII default to 19200 baud, address 1. Parity is even by default (configurable on MBC3/EL-FLOW Base). Modbus TCP server port is 502, supporting up to 4 clients.

⚠ Not following the guidelines could result in personal injury and/or damage to the equipment. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRJ45, M12, DB9
A/B polarityD0 Modbus (A/A'), D1 Modbus (B/B')
terminationNo integrated termination. External 120 Ohm resistors recommended.
connectorRJ45 modular jack, M12 circular connector, DB9 female connector
shield/groundShielded cables required
wiring notesPin layout on RJ45 is vendor-specific and differs from Modbus standard.
max registers/read125
response timeout100 ms
broadcastsupported
protocol notesMaximum message size for Read Holding Registers is 100 bytes at 9600 baud, 200 bytes at 19200 baud, and 400 bytes at 38400 baud.
model register61704
serial register61720
firmware register61736
identification notesReport Slave ID (FC17) returns a string containing ident number, version, and serial number.
FC 43 device IDnot supported
power15...24 Vdc
certificationsCE
doc revision9.17.035AF

generated by gemini:gemini-3.5-flash · harvested from https://products.bronkhorst.com/media/vs1lwo3b/917035-manual-modbus-slave-interface.pdf (Bronkhorst); manual-faithful — the document's claims, panel risk: HIGH — independent re-derivation disagrees on specific fields; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.