Burkert Type 8619 multiCELL controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
main_board_id0U161
main_board_module_status1U161
m1_m3_status2U161
m4_m6_status3U161
system_switch4U161
di1_status5U161
di2_status6U161
do18U161
do29U161
ao110F32BE1
ao212F32BE1
di1_frequency14F32BE1
di1_flow16F32BE1
di1_tot_a18F32BE1
di1_tot_b20F32BE1
di2_frequency22F32BE1
di2_flow24F32BE1
di2_tot_a26F32BE1
di2_tot_b28F32BE1
m1_id32U161
m1_module_status33U161
pvn10F32BE1
pvn22F32BE1
pvn34F32BE1
pvn46F32BE1
pvn58F32BE1
pvc1_status513U161
pvc1_value514F32BE1
pvc2_status516U161
pvc2_value517F32BE1
pvc3_status519U161
pvc3_value520F32BE1

link settings as documented (unverified): TCP; FC 03,04,16,23; Modbus TCP uses a Client/Server access method. The device Type 8619 is a server.

bench facts as documented (unverified)
wiring notesThe data exchange between the device Type 8619 and the other equipment of the network is only possible 25 s after the device start.
protocol notesThe device Type 8619 stores and sends the values of all variables in 'big-endian' format.
identification notesIdentity object (EtherNet/IP) lists Product Code 8619, Vendor ID 87, Product Name multiCELL.
doc revisionSupplement to Operating Instructions 2204/03_EU-ML 00569043 / Original_EN
firmware applicabilityfrom software version B.02.00
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms framing [TCP], function codes [3,4,16,23] — confirmed by Burkert Type 8619 Industrial Ethernet Supplement (00569043)
  • confirmed: facts doc_revision 'Supplement to Operating Instructions 2204/03_EU-ML 00569043 / Original_EN' — confirmed by Burkert Type 8619 Industrial Ethernet Supplement (00569043)
  • confirmed: facts firmware_applicability 'from software version B.02.00' — confirmed by Burkert Type 8619 Industrial Ethernet Supplement (00569043)
  • confirmed: physical notes 'The data exchange between the device Type 8619 and the other equipment of the network is only possible 25 s after the device start.' — confirmed by Burkert Type 8619 Industrial Ethernet Supplement (00569043)
  • confirmed: register map addresses (e.g., pvc1_status @ 513, pvc1_value @ 514) — confirmed by Burkert Type 8619 Industrial Ethernet Supplement (00569043)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.