Carrier BACnet/Modbus translator

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
modbus_address1U161
modbus_baud_rate2U161
display_units3U161
pic_bus_number4096U161
pic_address_number4097U161
pic_baud_rate4098U161
time_hour8192U161
time_minutes8193U161
time_date_status_bits8194U161
point_1_val_x116384I161
point_2_val_x116385I161
point_3_val_x116386I161
point_4_val_x116387I161
point_5_val_x116388I161
point_6_val_x116389I161
point_7_val_x116390I161
point_8_val_x116391I161
point_9_val_x116392I161
point_10_val_x116393I161
point_1_val_x1016640I160.1
point_2_val_x1016641I160.1
point_3_val_x1016642I160.1
point_4_val_x1016643I160.1
point_5_val_x1016644I160.1
point_6_val_x1016645I160.1
point_7_val_x1016646I160.1
point_8_val_x1016647I160.1
point_9_val_x1016648I160.1
point_10_val_x1016649I160.1
point_1_val_x10016896I160.01
point_2_val_x10016897I160.01
point_3_val_x10016898I160.01
point_4_val_x10016899I160.01
point_5_val_x10016900I160.01
point_6_val_x10016901I160.01
point_7_val_x10016902I160.01
point_8_val_x10016903I160.01
point_9_val_x10016904I160.01
point_10_val_x10016905I160.01
point_1_val_x100017152I160.001
point_2_val_x100017153I160.001
point_3_val_x100017154I160.001
point_4_val_x100017155I160.001
point_5_val_x100017156I160.001
point_6_val_x100017157I160.001
point_7_val_x100017158I160.001
point_8_val_x100017159I160.001
point_9_val_x100017160I160.001
point_10_val_x100017161I160.001
point_1_status20480U161
point_2_status20481U161
point_3_status20482U161
point_4_status20483U161
point_5_status20484U161
point_6_status20485U161
point_7_status20486U161
point_8_status20487U161
point_9_status20488U161
point_10_status20489U161
setpoint_1_val_x10033280I160.01
setpoint_2_val_x10033281I160.01
setpoint_3_val_x10033282I160.01
setpoint_4_val_x10033283I160.01
setpoint_5_val_x10033284I160.01
setpoint_6_val_x10033285I160.01
setpoint_7_val_x10033286I160.01
setpoint_8_val_x10033287I160.01
setpoint_9_val_x10033288I160.01
setpoint_10_val_x10033289I160.01
time_schedule_1_manual_override_hours36864U161
time_schedule_1_period_1_dow36865U161
time_schedule_1_period_1_occupied_from36866U161
time_schedule_1_period_1_occupied_to36867U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 16; FC 03,04,06,16; Default parity is None (0), default stop bits is 1. Flow control default is None (0).

bench facts as documented (unverified)
connectorCCN BACnet/MODBUS connector
wiring notesOutdoor duty rated
sentinel values-999.99
environmentOutdoor duty rated
doc revision808-356 01/05
field reports — community-sourced, unverified (checked 2026-06-11)
  • The official Modbus point definition specification has errors in status definitions for specific chiller models (such as 30HXC), causing status values to mismatch. [source]
  • The translator has a slow 30-second refresh interval for polling CCN points, making it unsuitable for real-time high-demand applications like variable water volume or backpressure control. [source]
  • The translator's communication port is not fully isolated and has a bare board structure without shielding, leading to a high failure rate in the field. [source]
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400] and default baud rate of 9600 — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Default Modbus address of 16 — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Supported Modbus RTU function codes 3, 4, 6, and 16 — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Default parity is None (0), default stop bits is 1, and default flow control is None (0) — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Physical connector (CCN BACnet/MODBUS connector) and outdoor duty rating — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Unmapped points display a sentinel value of -999.99 — confirmed by Carrier Translator Manual 808-356 01/05
  • confirmed: Register map addresses (Modbus Address @ 1, Modbus Baud Rate @ 2, Units @ 3, PIC Bus Number @ 4096, PIC Address Number @ 4097, PIC Baud Rate @ 4098, Hour @ 8192, Minutes @ 8193, Point Value Registers starting at 16384, 16640, 16896, 17152) — confirmed by Carrier Translator Manual 808-356 01/05

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.