Chint DTSU666 power meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
uab8192F32BE1V
ubc8194F32BE1V
uca8196F32BE1V
ua8198F32BE1V
ub8200F32BE1V
uc8202F32BE1V
ia8204F32BE1A
ib8206F32BE1A
ic8208F32BE1A
pt8210F32BE1W
pa8212F32BE1W
pb8214F32BE1W
pc8216F32BE1W
qt8218F32BE1var
qa8220F32BE1var
qb8222F32BE1var
qc8224F32BE1var
pft8234F32BE1
pfa8236F32BE1
pfb8238F32BE1
pfc8240F32BE1
freq8260F32BE1Hz
imp_ep4126F32BE1kWh
imp_ep_a4128F32BE1kWh
imp_ep_b4130F32BE1kWh
imp_ep_c4132F32BE1kWh
net_imp_ep4134F32BE1kWh
exp_ep4136F32BE1kWh
exp_ep_a4138F32BE1kWh
exp_ep_b4140F32BE1kWh
exp_ep_c4142F32BE1kWh
net_exp_ep4144F32BE1kWh

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,16; The factory default baud rate is 9600bps, n.8.1. The communication address of Modbus protocol is 01 (1 ~ 247).

bench facts as documented (unverified)
terminalsRS485 Terminal A (24), Terminal B (25)
A/B polarityA (+), B (-)
termination120 ohm resistor at start and end terminals if distance is over 150 meters
connectorScrew terminals
wiring notesCurrent cable terminal conductor cross-sectional area range <= 16 mm2, RS485 cable terminal 0.25-1 mm2
protocol notesSingle-precision floating point adopts standard IEEE754 format, total 32 bit (4 word). The single-precision floating point mode is assumed to be ABCD (high type in the front, low byte behind).
firmware register0000H
identification notes0000H REV. Software Version
powerPower consumption of the voltage circuit <= 1.5W and 6VA. Power consumption of the current circuit: Ib < 10A <= 0.2VA, Ib >= 10A <= 0.4VA
environmentRegulated working temperature range: -10℃~+45℃; Limited working temperature range: -25℃~+75℃; Relative humidity (Annually average): <= 75% RH; Atmospheric pressure: 63.0kPa~106.0kPa
accuracyActive class 0.5S, reactive class 2 (or Active class 1, Reactive class 2 depending on model)
certificationsIEC 61010-1:2010, IEC 61326-1:2013
doc revisionZTY0.464.1448V2
field reports — community-sourced, unverified (checked 2026-06-11)
  • The DTSU666 meter has an 'autocorrecting' CT function (enabled by default via parameters J-1 and J-2) that attempts to detect and correct CTs placed on the wrong phase. However, it only runs once upon first power-on. If an installer corrects a CT placement error later, the meter retains the old 'correction' internally, causing incorrect readings. Installers are advised to disable this function by setting J-1 and J-2 parameters to 0. [source]
  • When integrating the DTSU666 with Loxone, users report that the 'Byte Order' checkbox must be selected for all sensors to parse the Modbus data correctly, though some firmware versions may work without it. [source]
  • confirmed: comms.baud_rates: [1200, 2400, 4800, 9600, 19200] — confirmed by Chint DTSU666 Datasheet and User Manuals which list these baud rates.
  • confirmed: comms.default_baud: 9600 — confirmed by Chint DTSU666 User Manuals stating the factory default baud rate is 9600 bps.
  • confirmed: comms.default_unit_id: 1 — confirmed by Chint DTSU666 User Manuals stating the default communication address is 01.
  • confirmed: facts.certifications: IEC 61010-1:2010, IEC 61326-1:2013 — confirmed by Chint DTSU666 User Manuals stating compliance with these standards.
  • confirmed: facts.doc_revision: ZTY0.464.1448V2 — confirmed by Chint DTSU666 User Manuals carrying the document code ZTY0.464.1448.
  • confirmed: facts.environment: Regulated working temperature range: -10℃~+45℃; Limited working temperature range: -25℃~+75℃; Relative humidity (Annually average): <= 75% RH; Atmospheric pressure: 63.0kPa~106.0kPa — confirmed by Chint DTSU666 User Manuals.
  • confirmed: facts.physical: RS485 Terminal A (24), Terminal B (25) — confirmed by Chint DTSU666 User Manuals and wiring diagrams.
  • confirmed: facts.power: Power consumption of the voltage circuit <= 1.5W and 6VA. Power consumption of the current circuit: Ib < 10A <= 0.2VA, Ib >= 10A <= 0.4VA — confirmed by Chint DTSU666 User Manuals.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.