Chromalox 6060 controller (Modbus supplement)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
input_1_process_value35112F32BE1
input_1_unprocessed_value35108F32BE1
input_2_process_value35308F32BE1
input_2_unprocessed_value35312F32BE1
input_3_process_value35508F32BE1
input_3_unprocessed_value35512F32BE1
control_deviation42976F32BE1
position_feedback42978F32BE1
controller_output_value42974F32BE1
effective_setpoint42970F32BE1
heating_current36910F32BE1
ssr_current36912F32BE1
controller_status5100U161
limit_status2170U161
limit_2_status2270U161
limit_3_status2370U161
digital_inputs_status1070U161
alarm_status250U161
digital_outputs_status251U161
analog_input_status252U161
setpoint_interface39128F32BE1

link settings as documented (unverified): RTU; baud 2400/4800/9600/19200/38400; FC 03,04,06,08,16; The max. length of a message may not exceed 256 bytes.

bench facts as documented (unverified)
terminalspins of connector B on the rear, via flat-pin connectors or via screw terminals dependent on version
A/B polarityfor signal 1 (off) Data A is positive to Data B, for signal 0 (on) Data A is negative to Data B
terminationTerminating resistors usually have a value of approx. 120 ohms, and are connected in parallel between the data lines A and B
wiring notesGND lead can be grounded at one point via a resistor 'RGND' (100 ohms, 1/4 watt).
broadcastsupported
protocol notesIf a parity error is detected upon receipt of a message, the receiving device will not generate an answer.
model register203
firmware register201
FC 43 device IDnot supported
environmentIf possible, the place of installation should be exempt of vibration, aggressive media (e.g. acid, lye), liquid, dust or aerosol.
certificationsThe device is not certified for installation in explosion-hazarded areas.
doc revisionPK539, 0037-75565, July 2016

generated by gemini:gemini-3.5-flash · harvested from https://content.chromalox.com/-/media/chromalox/documents/product-pdfs/im/im-pk539-6060-modbus-manual.ashx?rev=db94bf5b99ea402a89993bb0a89d833a (Chromalox); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.