Continental Control Systems WattNode WNC (Modbus variant)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
energy_sum1000F32LE1kWh
energy_pos_sum1002F32LE1kWh
power_sum1008F32LE1W
power_a1010F32LE1W
power_b1012F32LE1W
power_c1014F32LE1W
volt_avg_ln1016F32LE1V
volt_a1018F32LE1V
volt_b1020F32LE1V
volt_c1022F32LE1V
volt_avg_ll1024F32LE1V
volt_ab1026F32LE1V
volt_bc1028F32LE1V
volt_ac1030F32LE1V
freq1032F32LE1Hz
power_factor_avg1138F32LE1
power_factor_a1140F32LE1
power_factor_b1142F32LE1
power_factor_c1144F32LE1
power_reac_sum1146F32LE1
power_app_sum1154F32LE1
current_a1162F32LE1
current_b1164F32LE1
current_c1166F32LE1

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,04,06,16,17; Defaults to 8 data bits, no parity, and one stop bit. Parity can be configured to even (E81) with Option EP or ParityMode register.

bench facts as documented (unverified)
terminalsGreen screw terminals for voltage inputs (up to 12 AWG), black screw terminals for CT inputs, and Modbus terminals (A-, B+, C, X).
A/B polarityAuto-detects RS-485 polarity on properly biased networks.
terminationRequires 120 ohm termination resistors at both ends of the bus for longer networks.
connectorEuroblock style pluggable terminal blocks.
isolationModbus terminals are completely isolated (4500 Vac RMS isolation) from dangerous voltages.
shield/groundConnect cable shield or Modbus common to earth ground at just the Modbus master end.
inter-frame delay3 ms
broadcastsupported
model register1707
serial register1701
firmware register1708
FC 43 device IDnot supported
powerPowered from line voltage inputs: ØA to N for wye models, or ØA to ØB for delta models. Power consumption typically 1.0 to 1.6 W (3 to 4 VA).
environmentOperating temperature: -30°C to +55°C. Humidity: 5% to 90% RH non-condensing. Pollution degree 2. Indoor use or outdoor in NEMA 3R/4 enclosure.
accuracy±0.5% of reading under normal operation (Condition 1).
certificationsUL 61010-1, CAN/CSA-C22.2 No. 61010-1-04, IEC 61010-1, EN 61326: 2002, FCC Part 15 Class B, EN 55022: 1994 Class B.
doc revisionRev 1.18c
firmware applicabilityFirmware Versions 18-24

⚠ disputed: inter_frame_delay_ms: 3 — disputed by WattNode Modbus Installation and Operation Manual (Rev 1.18c) which states that the inter-frame silent interval is baud-rate dependent (3.6 ms at 9600 baud, ~2 ms at 19200 baud) rather than a fixed 3 ms.

field reports — community-sourced, unverified (checked 2026-06-11)
  • In firmware versions V14 through V22, at 9600 baud, the meter only allowed a maximum silent gap of 0.75 ms between bytes when receiving messages, causing messages to be ignored if a master inserted gaps longer than that (the Modbus standard permits up to 1.5 character times or 1.56 ms). Fixed in V23/V26. [source]
  • In firmware versions V16 through V22, the meter reported zero for energies, power, voltage, and other measurements during the first second of operation. Fixed in V23. [source]
  • In firmware version V22, the meter reported zero for energies during the first second of operation. Fixed in V23/V26. [source]
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400] and default baud rate of 9600 — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Modbus RTU framing and supported function codes [3, 4, 6, 16, 17] — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Accuracy of ±0.5% of reading under normal operation (Condition 1) — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Certifications (UL 61010-1, CAN/CSA-C22.2 No. 61010-1-04, IEC 61010-1, EN 61326: 2002, FCC Part 15 Class B, EN 55022: 1994 Class B) — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Auto-detection of RS-485 polarity on properly biased networks — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Shield grounding recommendation to connect shield to earth ground at just the Modbus master end — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)
  • confirmed: Register map summary (0-based addresses matching 1-based registers in manual) — confirmed by WattNode Modbus Installation and Operation Manual (Rev 1.18c)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.