verified connector library

Control Techniques Commander C200/C300 drive (needs AI-485 adapter)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
output_frequency400I160.01
output_voltage401U161
output_power402I160.01
motor_rpm403I160.1
dc_bus_voltage404U161
current_magnitude300U160.01
torque_producing_current301I160.01
analog_input_1600I160.01
analog_input_2601I160.01
drive_ok900U161
drive_active901U161
status_word939U161
active_trip919U161
motor_rated_current406U160.01
motor_rated_speed407U160.1
motor_rated_voltage408U161
motor_rated_power_factor409U160.01
motor_rated_frequency405U160.01

link settings as documented (unverified): RTU; default 19200 8N2; unit ID 1; FC 03,06,16,23; The communications port applies a 1.25 unit load to the communications network. Default setting is 8 2 NP (8 data bits, 2 stop bits, no parity).

⚠ The STOP and Safe Torque Off functions of the drive do not isolate dangerous voltages from the output of the drive or from any external option unit. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRJ45 or screw terminals
A/B polarity
termination120 Ohm termination resistor available on RJ45 pin 1 or screw terminal pin 4
connectorRJ45 or screw terminal block
isolationSingle insulated, meets ELV requirements
shield/groundMinimum number of connections are 2, 3, 7 and shield
wiring notesStandard Ethernet cables must not be used when connecting drives on a EIA 485 network as they do not have the correct twisted pairs for the pinout of the serial comms port.
inter-frame delay20 ms
broadcastsupported
sentinel values
protocol notesThe Modbus slave device increments the register address by 1 before processing the command, which effectively prevents access to parameter Pr 00.000 in the drive or option module.
model register11.028
serial register11.052
firmware register11.029
identification notesSerial number is split into LS (11.052) and MS (11.053).
FC 43 device IDnot supported
power24 Vdc backup supply input on AI-Backup adaptor
environmentPollution Degree 2 environment or better (dry, non-conductive pollution only). Ambient temperature up to 40 °C (up to 55 °C with derating)
accuracy
certificationsCE, C Tick, UL / cUL, RoHS, Functional safety, EurAsian Conformity
doc revisionIssue: 2
firmware applicability

⚠ disputed: output_frequency @ 400, output_voltage @ 401, output_power @ 402, motor_rpm @ 403, dc_bus_voltage @ 404, current_magnitude @ 300, torque_producing_current @ 301, analog_input_1 @ 600, analog_input_2 @ 601, drive_ok @ 900, drive_active @ 901, status_word @ 939, active_trip @ 919, motor_rated_current @ 406, motor_rated_speed @ 407, motor_rated_voltage @ 408, motor_rated_power_factor @ 409, motor_rated_frequency @ 405 — disputed by Commander C200/C300 Control User Guide and Parameter Reference Guide. The standard Modbus address formula is (Menu * 100) + Parameter - 1. Therefore, Menu 5 parameters (like output_frequency Pr 05.001) map to 500, not 400. Menu 4 parameters (like current_magnitude Pr 04.001) map to 400, not 300. Menu 7 parameters (like analog_input_1 Pr 07.001) map to 700, not 600. Menu 10 parameters (like drive_ok Pr 10.001) map to 1000, not 900. The entire register map is shifted down by exactly 100 registers.

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: The communications port applies a 1.25 unit load to the communications network. Default setting is 8 2 NP (8 data bits, 2 stop bits, no parity). — confirmed by Unidrive M200/M201 Control User Guide and Commander C200/C300 Control User Guide
  • confirmed: The Modbus slave device increments the register address by 1 before processing the command, which effectively prevents access to parameter Pr 00.000 in the drive or option module. — confirmed by Commander C200/C300 Control User Guide

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.