Crowcon Gasmaster III gas panel

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
time500U32BE1
status501U161
system_fault_1502U32BE1
system_fault_2503U32BE1
system_warning_1504U32BE1
system_warning_2505U32BE1
channel_1_level506F32BE1
channel_1_status507U161
channel_2_level508F32BE1
channel_2_status509U161
channel_3_level510F32BE1
channel_3_status511U161
channel_4_level512F32BE1
channel_4_status513U161
raw_adc_ch1622U161mA
raw_adc_ch2623U161mA
raw_adc_ch3624U161mA
raw_adc_ch4625U161V
raw_adc_psu626U161V
raw_adc_vsys627U161V
raw_adc_p12v628U161V
raw_adc_check_low629U161V
raw_adc_check_high630U161V
raw_adc_vlcd0631U161V
raw_adc_vlcd1632U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,16; A silent interval of 5.7mS is used to define the termination of a data packet. On receipt of a message requiring a response, the instrument will pause for a guaranteed period of at least 50mS before transmission will commence.

bench facts as documented (unverified)
inter-frame delay5 ms
broadcastsupported
protocol notesOn receipt of a message requiring a response, the instrument will pause for a guaranteed period of at least 50mS before transmission will commence.
model register1
serial register4
firmware register3
identification notesManufacturer is at address 2.
FC 43 device IDnot supported
doc revisionFGM3-002 Issue 2 January 2015
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Document revision FGM3-002 Issue 2 January 2015 — confirmed by Crowcon Gasmaster Modbus Instructions document [1.1.1]
  • confirmed: Baud rate 9600, RTU framing, and 1 stop bit (configurable) — confirmed by Crowcon Gasmaster Modbus Instructions Section 2.1
  • confirmed: Silent interval of 5.7mS and response pause of at least 50mS — confirmed by Crowcon Gasmaster Modbus Instructions Section 2.2
  • confirmed: Instrument identification registers (Model @ 1, Manufacturer @ 2, Software version @ 3, Serial @ 4) — confirmed by Crowcon Gasmaster Modbus Instructions Section 3.1
  • confirmed: Runtime registers (Time @ 500, Status @ 501, System Fault 1 @ 502, System Fault 2 @ 503) — confirmed by Crowcon Gasmaster Modbus Instructions Section 3.4
  • confirmed: Raw ADC registers (Raw ADC Ch1 @ 622 through Raw ADC VLCD1 @ 632) — confirmed by Crowcon Gasmaster Modbus Instructions Section 3.4

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.