| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| gas_level | 99 | I16 | 0.1 | % FSD |
| mode | 100 | I16 | 1 | enum |
| status | 101 | I16 | 1 | enum |
| detector_signal_rate_of_change | 102 | I16 | 0.01 | |
| inst_gas_reading | 103 | I16 | 0.1 | |
| obscuration_factor | 104 | I16 | 0.1 | % |
| supply_voltage | 105 | I16 | 0.01 | V |
| temperature | 106 | I16 | 0.1 | oC |
| gas_det_level_at_zero | 303 | I16 | 1 | raw |
| ref_det_level_at_zero | 304 | I16 | 1 | |
| temp_at_zero | 305 | I16 | 0.1 | oC |
| gas_det_zero_drift | 306 | I16 | 1 | |
| ref_det_zero_drift | 307 | I16 | 1 | |
| temp_at_auto_zero | 308 | I16 | 0.1 | |
| gas_det_signal_gain_at_fsd | 309 | I16 | 1 | |
| ref_det_signal_gain_at_fsd | 310 | I16 | 1 | |
| temp_at_fsd | 311 | I16 | 0.1 | |
| level_2_alarm_threshold | 499 | I16 | 0.1 | % FSD |
| level_1_alarm_threshold | 500 | I16 | 0.1 | % FSD |
| level_1_falling_alarm_threshold | 501 | I16 | 0.1 | |
| level_2_falling_alarm_threshold | 502 | I16 | 0.1 | |
| alarm_threshold_hysteresis | 503 | I16 | 0.1 | |
| lamp_sense | 575 | I16 | 0.1 | |
| supply_voltage_test | 576 | I16 | 0.01 | |
| reg_supply_sense | 577 | I16 | 0.001 | |
| temperature_test | 578 | I16 | 0.1 |
| A/B polarity | differential of between 2 and 6 volts |
| isolation | conforming to the RS458 standard (-7 to +12 volts) |
| wiring notes | 2 wire, half duplex, multi-drop |
| max registers/read | 125 |
| response timeout | 500 ms |
| inter-frame delay | 10 ms |
| broadcast | supported |
| protocol notes | Global address 000 is used for broadcast requests, which are validated and actioned but not responded to. |
| model register | 0 |
| serial register | 4 |
| firmware register | 1 |
| FC 43 device ID | not supported |
| power | supply set to 24 volts |
| doc revision | Issue No: 3, Date: 09-Mar-06 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.